Siting: recirculation is the enemy
A cooling tower rejects heat by evaporating water into the air stream. If it draws back its own saturated discharge, the entering wet-bulb temperature rises and the tower cannot reach its design approach.
| Constraint | Minimum | Preferred |
|---|---|---|
| Tower to wall or building | 1.0 × tower height | 1.5 × |
| Tower to another tower (air inlet to inlet) | 1.0 × height | 1.5 × |
| Tower discharge to any opening | 15 m, and above the opening | Prevailing wind considered |
| Tower to a fresh-air intake | 20 m | Opposite side of the building |
| Tower to a boundary | Per local noise rule | Acoustic model required |
Two layouts guarantee trouble: a tower in a walled enclosure open on one side, and a tower placed below the level of a parapet that the discharge can fall back over. Both cause a plume that never leaves, and both look fine on a drawing.
Approach and range: the two numbers that define performance
| Term | Definition | Typical value |
|---|---|---|
| Range | Water in minus water out | 5 K (30 → 35 °C) |
| Approach | Water out minus entering wet-bulb | 3–5 K |
| Effectiveness | Range ÷ (range + approach) | 50%–65% |
A tower sized for a 4 K approach at 28 °C wet-bulb delivers 35 °C water only if the wet-bulb really is 28 °C. In a humid month it may be 26 °C and the tower works better; in a dry month the wet-bulb may be 22 °C, which is also better. The risk is a design wet-bulb that is too optimistic: at 30 °C wet-bulb, a 4 K approach gives 34 °C water, which is fine, but at 32 °C it gives 36 °C and the chiller’s condensing pressure rises with it.
Piping: the parts that are usually missing
| Component | Function | If omitted |
|---|---|---|
| Equalising line between basins | Keeps levels equal on multi-cell towers | One cell overflows, one runs dry |
| Make-up with float valve | Replaces evaporation and blowdown | Basin runs dry, pump cavitates |
| Overflow | Safe discharge | Water damage |
| Blowdown | Controls cycles of concentration | Scaling, then biological growth |
| Bypass valve | Keeps flow during low load | Tower freezes in winter |
| Strainer before the condenser | Traps debris | Condenser tubes block |
| Vibration isolators | Structure-borne noise | Noise complaint |
| Flexible connections | Differential movement | Pipe strain, leaks |
The equalising line is the one most often left out on multi-cell installations. Without it, the cells interact through the distribution pipes and one basin level drifts until it trips.
Water balance: cycles of concentration
Every kilogram of water evaporated leaves its dissolved solids behind. Blowdown removes those solids, and the ratio of solids in the circulating water to solids in the make-up is the cycles of concentration.
| Parameter | Make-up | Circulating water at 3 cycles | Limit |
|---|---|---|---|
| Conductivity | 300 µS/cm | 900 µS/cm | 1,500 µS/cm |
| Chloride | 60 mg/L | 180 mg/L | 300 mg/L |
| Hardness as CaCO3 | 120 mg/L | 360 mg/L | 500 mg/L |
| pH | 7.5 | 8.3 | 8.0–9.0 |
| Suspended solids | 5 mg/L | 15 mg/L | 25 mg/L |
At 3 cycles, a tower evaporating 2% of its flow needs a blowdown of about 1% of the flow. At 5 cycles, blowdown falls to 0.5% and water use drops, but the scaling risk rises. Most towers run most reliably at 3–4 cycles with a treatment program that includes scale and biological control.
Freeze protection in winter
| Measure | When | Note |
|---|---|---|
| Basin heater | Any climate with frost | Sized on basin surface area |
| Bypass on low load | Water below 10 °C | Protects against ice in the fill |
| Fan cycling or VFD | Below design wet-bulb | Maintains the minimum water temperature |
| Drain-down | Long shutdown | Cheaper than heating an empty tower |
| Heat trace on make-up | Exposed pipework | Only where the pipe can freeze |
Running a tower in winter without a bypass is the usual cause of split basins and crushed fill. The chiller needs a minimum condensing pressure to operate; keeping the water warm is part of the chiller’s requirement, not an optional extra.
Noise and drift
| Source | Typical level | Control |
|---|---|---|
| Fan, 1 m from the tower | 70–85 dB(A) | Low-noise fan, VFD, acoustic inlet |
| Water splash | 65–75 dB(A) | Splash attenuators, low-noise fill |
| Drift | 0.001%–0.02% of flow | Drift eliminators |
Water lost as drift carries treatment chemicals and bacteria. Drift eliminators reduce it to a few liters per hour on a medium tower, and they also reduce the visible plume. If the tower is near a car park or a public area, this matters.
Longkang Environmental Equipment Co., Ltd. sizes the cooling water circuit with the chiller, including the design wet-bulb assumption, so the tower selection and the chiller selection are based on the same weather data. Phone: +86 400-878-0280 | +86 130-0200-1280
Questions from installers
How far should the tower be from the chiller?
As close as practical, ideally under 30 m one way. Long runs add pump head and heat gain in the cooling water pipes. Beyond 50 m, re-check the pump and consider a plate heat exchanger to separate the circuits.
Can the tower sit on the roof above the plant room?
Yes, and that is the usual arrangement. Check the structural load with water in the basin, provide access for cleaning, and make sure the discharge does not enter any rooftop intake within 15 m.
Why does the tower lose water faster than expected?
Evaporation is about 1% of flow per 5 K of range, plus drift and blowdown. A 300 m³/h circuit losing 3 m³/h is normal; losing 8 m³/h suggests a leaking basin or a float valve passing.
Do I need water treatment for a small tower?
Yes. Even a 50 m³/h tower will scale and grow biofilm within a season without treatment. The cost of treatment is a fraction of the cost of cleaning a fouled condenser.
What is a safe approach temperature to specify?
4 K at design wet-bulb is realistic for a standard tower; 3 K requires a larger tower and more fan power. Be wary of a specification that promises 2 K — it usually means the tower is oversized or the wet-bulb is optimistic.
How do I stop the plume being visible in winter?
A plume is condensed water vapor, not smoke. It can be reduced with a dry coil section, a hybrid tower, or by operating at a lower range. It cannot be eliminated on a purely evaporative tower in cold weather.