With a 5 °C mains and 7% losses, design energy is about 470 kWh per day, or 47 kW average over a 10-hour window.
Step 3 — Peak hour, and why the tank does the work
A dormitory peak is concentrated. Measured profiles put 40%–50% of daily consumption into one hour after the evening shift or after lights-out, and another 15%–20% into the morning.
For 8 m³ a day, a 45% peak is 3.6 m³ in one hour. Producing 3.6 m³ in an hour would need 167 kW of heating capacity — five times the average load, and a plant that would run at 10% load for the rest of the day. Storage is the cheaper answer: heat at night, store, and let the tank absorb the peak.
Usable storage = peak-hour draw − heat produced during that hour
With 47 kW running through the peak, the plant delivers 47 ÷ (4.187 × 40 ÷ 3,600) ≈ 1.0 m³ in that hour. So usable storage must be at least 3.6 − 1.0 = 2.6 m³. Because stratification and blending mean only 70%–80% of a tank’s nominal volume is usable, specify:
Nominal tank volume = 2.6 ÷ 0.75 ≈ 3.5 m³, practical minimum 4 m³
Most designers add a full day of buffer for a dormitory because a failure on a Sunday night cannot be fixed until Monday. A 6–8 m³ total volume, split into two tanks so one can be isolated for cleaning, is the usual answer for 100 people.
Step 4 — Choosing the units
| Configuration | Output | Capital | Redundancy | Comment |
|---|---|---|---|---|
| 1 × 40 kW | 40 kW | Lowest | None | Marginal on the coldest week |
| 2 × 20 kW | 40 kW (20 kW standby) | +15% | One unit down = 50% | Good balance for 100 people |
| 3 × 15 kW | 45 kW (15 kW standby) | +25% | One unit down = 67% | Better staging at low load |
| 2 × 25 kW | 50 kW | +25% | One down = 50% | Allows for future expansion |
For 100 people with a 47 kW design load, two 25 kW units or three 15 kW units are the sensible choices. Two units also halve the starting current and let the controller rotate the lead unit weekly, which evens out compressor hours.
Derate for the actual winter ambient. A unit rated 25 kW at 7 °C delivers roughly 19–21 kW at −5 °C and 15–17 kW at −15 °C, depending on the model. At a design ambient of −5 °C, two 25 kW units give 40 kW — short of the 47 kW load, which is why the tank, not the unit count, absorbs the difference on the coldest three days of the year.
Step 5 — Plant room, power and pipework
| Item | Requirement for 2 × 25 kW | Note |
|---|---|---|
| Plant room floor area | 12–16 m² | Includes 0.8 m service access |
| Clearance to walls | 0.6 m min, 1.0 m preferred | Coil face is the critical side |
| Power supply | 380–400 V 3 ph, 2 × 32 A | Plus pump and controls |
| Total running current | 26–30 A per phase | Both units at full load |
| Main pipe size | DN50 | Velocity 1.0–1.3 m/s at 25 kW |
| Tank connection | DN65 flanged | Two tanks, balance pipe DN50 |
| Recirculation pump | 0.5–0.75 kW, variable speed | Return loop insulated |
Put the units where the discharge air cannot short-circuit back into the coil — a 1.5 m clear discharge is the rule, and 2.5 m is better. If the plant room is enclosed, duct both the inlet and the discharge; a louvre with 50% free area will starve a 25 kW unit.
Step 6 — Running cost
| Item | Value | Basis |
|---|---|---|
| Daily heat delivered | 470 kWh | Winter, 5 °C mains |
| Seasonal COP | 3.2 | Includes defrost penalty |
| Daily electricity | 147 kWh | 470 ÷ 3.2 |
| Annual electricity | 53,700 kWh | 365 days, no seasonal correction |
| Annual cost at 0.7 CNY/kWh | 37,600 CNY | — |
| Cost per person per day | about 1.03 CNY | 100 residents |
Compare with electric resistance heating at COP 0.95: 495 kWh a day, 180,700 kWh a year, 126,500 CNY. The heat pump saves roughly 89,000 CNY a year, which is more than the entire plant’s capital cost in most projects — and that is the calculation that gets a dormitory project approved.
Mistakes that show up after handover
- Sizing on summer mains temperature. The plant then runs flat out in January and the residents complain, correctly.
- One tank instead of two. Cleaning requires a shutdown; a single tank also stratifies worse at high draw-off rates.
- No recirculation loop. Residents in the far block run the tap for 40 seconds and report “no hot water”, when the tank is full of it.
- Return pump running continuously. It destroys stratification overnight; fit a timer or a thermostat set to start at 45 °C return.
- Ignoring the shower flow rate. Low-flow heads at 6 L/min turn an 8 m³ design into 5 m³ of actual use — a 30% capital saving if the specification is fixed before the units are ordered.
Longkang Environmental Equipment Co., Ltd. supplies modular units from 10 to 100 kW with cascade controllers that stage and rotate automatically, which suits a two- or three-unit dormitory plant without a separate BMS. Phone: +86 400-878-0280 | +86 130-0200-1280
Questions from project teams
How many liters per person should I use for a school dormitory?
70–80 L per person per day at 55 °C for a boarding school with timed evening showers; 90–100 L where students have en-suite bathrooms. Confirm the shower head flow rate and the shower timings, because those two facts move the figure more than the standard.
Can one 40 kW unit serve 100 people?
In a mild climate, yes, with a large tank. Where the design ambient falls below −5 °C, a single unit has no standby and its output drops exactly when demand peaks. Two smaller units cost about 15% more and remove that risk.
How long does the plant take to reheat after the evening peak?
With 8 m³ of storage and 47 kW of capacity, recovering 3 m³ of draw-off takes about three hours. If the tariff allows, heat at night and let the tank carry the evening; if it does not, add storage rather than capacity.
Do I need a water softener for a dormitory?
Check hardness first. Above 200 mg/L as CaCO₃, scale will form on the water side within two years and the plant will lose 10%–15% of capacity. A softener for 8 m³ a day is a small cost against descaling a heat exchanger.
What temperature should the tank be set to?
Store at 60 °C and deliver at 50–55 °C through a thermostatic mixing valve. Storing below 55 °C in a dormitory risks legionella in the dead legs of a building that is empty for holidays; storing at 60 °C costs about 4% more energy and removes the risk.
Is a heat pump worth it compared with a gas boiler?
At a gas price of 3.0 CNY/m³ and 0.7 CNY/kWh electricity, a heat pump at COP 3.2 costs about 0.22 CNY per kWh of heat; a condensing boiler at 92% efficiency costs about 0.32 CNY. The heat pump wins on running cost and avoids the flue and gas supply, but the capital cost is higher and it needs three-phase power.