The three formulas
| Quantity | Formula | Unit |
|---|---|---|
| Daily volume | V = N × q | liters per day |
| Daily energy | Q = V ÷ 1,000 × ΔT × 1.163 | kWh per day |
| Peak-hour volume | V_peak = V × k | liters per hour |
| Peak heating load | P = V_peak ÷ 1,000 × ΔT × 1.163 | kW |
Where N is the number of users (people, rooms or beds), q is consumption per user per day, ΔT is the temperature rise from inlet to setpoint, and k is the peak-hour factor — the share of daily demand drawn in the busiest hour.
The constant 1.163 converts tonne-kelvin into kilowatt-hours: one tonne of water raised by 1 K absorbs 1.163 kWh.
Consumption figures by building type
| Building type | Unit | Consumption (L/day) | Notes |
|---|---|---|---|
| Hotel 3-star | per room | 100–160 | Higher with bathtubs |
| Hotel 4–5 star | per room | 160–240 | Includes laundry and kitchen |
| Guesthouse | per room | 60–100 | Occupancy varies widely |
| School dormitory | per student | 40–80 | Two shower windows per day |
| University | per student | 50–90 | Larger peak at term start |
| Factory dormitory | per worker | 50–80 | Shift change dominates |
| Hospital | per bed | 100–200 | Plus staff, cleaning, laundry |
| Office | per person | 10–20 | Canteen adds a lunch peak |
| Restaurant | per seat | 15–30 | Peaks at service times |
| Gym / sports center | per user | 40–60 | Shower dominated |
These ranges are industry-typical starting values. A building with a known history — an existing hotel being refurbished, for example — should be measured rather than estimated.
The factors that adjust the raw number
Simultaneity. Not everyone showers at once. For hotels, 0.7–0.9 of rooms occupied and a simultaneity factor of 0.6–0.8 within the peak hour is common practice. For dormitories with a fixed shower window, simultaneity approaches 1.0 and the peak factor rises accordingly.
Pipe and storage losses. Distribution losses of 5%–15% are typical; long uninsulated runs and poorly insulated tanks push this higher. Add the loss to the daily energy figure, not to the tank volume.
Cold inlet temperature. In winter, mains water can be 5–10 °C rather than the 15 °C used in summer calculations. This raises ΔT and therefore energy, typically by 10%–20% in cold climates.
Setpoint and mixing. If hot water is stored at 60 °C and blended to 45 °C at the outlet, the volume required from storage is lower than the volume delivered at the tap. Mixing valves change the arithmetic; be explicit about which temperature the calculation refers to.
Worked example 1: 80-room hotel
| Step | Calculation | Result |
|---|---|---|
| Rooms | 80 | — |
| Consumption | 120 L per room | 9,600 L/day |
| Occupancy factor | × 0.8 | 7,680 L/day |
| Design volume (with 10% margin) | × 1.1 | 8,450 L/day ≈ 8.5 t |
| ΔT | 15 °C → 55 °C = 40 K | — |
| Daily energy | 8.5 × 40 × 1.163 | 395 kWh/day |
| Peak-hour factor | 12% | 1.01 t/h |
| Peak load | 1.01 × 40 × 1.163 | 47 kW |
| Heating hours available | 16 h | — |
| Required capacity | 395 ÷ 16 | 24.7 kW |
| Tank volume | 40% of daily | 3.4 t |
The peak load (47 kW) is far higher than the average load (24.7 kW). That gap is what the storage tank covers, and it is why tank volume and heat pump capacity must be calculated separately.
Worked example 2: 500-student dormitory
| Step | Calculation | Result |
|---|---|---|
| Students | 500 | — |
| Consumption | 60 L per student | 30,000 L/day = 30 t |
| Daily energy | 30 × 40 × 1.163 | 1,396 kWh/day |
| Shower window | 18:00–21:00, 3 h | — |
| Peak-hour factor | 30% | 9 t/h |
| Peak load | 9 × 40 × 1.163 | 419 kW |
| Heating hours available | 12 h (night and day) | — |
| Required capacity | 1,396 ÷ 12 | 116 kW |
| Tank volume | 45% of daily | 13.5 t |
Here the peak load is more than three times the average, because three hours carries a third of the day’s demand. The tank does most of the work at 19:00; the heat pumps recharge it overnight.
Worked example 3: factory with shift change
| Step | Calculation | Result |
|---|---|---|
| Workers per shift | 300 | — |
| Consumption | 60 L per worker | 18,000 L/day |
| Shifts | 2 | Demand repeats twice daily |
| Peak window | 30 min at shift end | — |
| Simultaneity | 0.6 | 180 simultaneous showers |
| Peak flow | 180 × 70 L ÷ 0.5 h | 25.2 t/h |
| Tank volume | Sized to 25.2 t/hr peak | 15–20 t |
| Heat pump capacity | Sized on daily energy ÷ 14 h | 60 kW |
Industrial sites are peak-dominated: the tank is large relative to the heat pump, because the demand arrives in half an hour and the equipment has the rest of the day to recover.
Checking the result
Three sanity checks catch most arithmetic errors:
- Liters per person per day — does the final figure fall inside the typical range for that building type?
- kWh per tonne — for a 40 K rise, it should be about 46.5 kWh per tonne. If it is not, ΔT or the conversion constant is wrong.
- Peak load versus average load — the ratio should roughly equal 24 ÷ peak hours. A ratio of 1 means the peak factor was set to zero.
Frequently asked questions
Should I use liters per person or liters per room?
Whichever matches how the building is operated. Hotels are usually calculated per room because occupancy is the variable; dormitories per person; hospitals per bed.
How do I handle a building with both guest rooms and a restaurant?
Calculate each demand separately and add the daily volumes, but check whether the peaks coincide. A hotel restaurant peak (07:00–09:00) often overlaps the guest shower peak, which raises the tank requirement.
What if the client cannot provide occupancy data?
Use the upper end of the published range and state the assumption. Then specify a tank size that tolerates the uncertainty — extra storage is cheaper than a second heat pump installed later.
Does a recirculation loop change the calculation?
It adds continuous loss — typically 5%–10% of daily energy for a well-insulated loop, more for a poorly insulated one. It also affects the pump and control design, so it should be identified at this stage.
Can I calculate demand from the water meter?
Yes, and it is the most reliable method for an existing building. Take at least two weeks of readings including a full weekend, and convert to daily volume at the recorded hot water temperature.
How much does inlet temperature variation matter?
Going from 15 °C to 5 °C inlet raises ΔT from 40 K to 50 K, a 25% increase in energy. In cold climates, size on the winter inlet temperature, not the annual average.
Longkang Environmental Equipment Co., Ltd. provides demand calculations with the consumption figure, occupancy factor and peak factor stated separately, so each assumption can be reviewed against the project. Phone: +86 400-878-0280 | +86 130-0200-1280