Water Chiller Fault Codes and Troubleshooting

Record the condition before resetting

Record Why
Code and timestamp Distinguishes a one-off from a pattern
Leaving and entering water temperature Shows load at the time
Condenser water temperature Shows heat rejection condition
Ambient or wet-bulb Explains pressure limits
Load percentage Low load causes as many alarms as high
Whether it restarts and how long it runs Separates start faults from running faults

An alarm that occurs 40 minutes after start is a different problem from one that occurs 4 seconds after start, even with the same code.

High pressure (condensing pressure too high)

Check in order Target Finding
Condenser water flow Design ±10% Pump, valve, strainer
Cooling tower performance Approach 3–5 K Fan, fill, distribution
Condenser fouling Approach below 4 K Scale, biofilm
Air in the condenser No air, correct venting Poor commissioning
Refrigerant charge Subcooling 5–10 K Overcharge after a top-up
Non-condensables Discharge pressure high, approach normal Incomplete evacuation

On an air-cooled machine, the same alarm usually means a dirty coil, a failed fan, or recirculation. Check the coil before the refrigerant.

Low pressure (suction pressure too low)

Cause Confirm by Action
Low refrigerant charge Subcooling low, superheat high Leak test and recharge
Restricted liquid line Temperature drop across the drier Replace the drier
Low load Load below the minimum stable point Add buffer volume, stage machines
Low chilled water temperature Setpoint or sensor error Verify sensor
Faulty pressure transducer Gauge disagrees with display Replace and calibrate

Low pressure at low load is a design issue, not a fault. A chiller running at 10% load for long periods will trip unless the machine has unloading capability or a buffer tank to smooth the load.

Low evaporator temperature / freeze protection

Reading Meaning Action
Water out below 4 °C with normal flow Setpoint or control fault Check setpoint and sensor
Water out below 4 °C with low flow Flow problem Pump, strainer, air, valve
Sudden drop with normal flow Expansion valve overfeeding Check superheat
Repeated trips after reset Sensor calibration Compare with a reference thermometer

Freeze protection is the last line before a burst tube. Never increase the time delay or lower the cut-out to stop nuisance trips; find out why the water is getting cold.

Water flow failure

Condition Cause Check
Pump not running Electrical, overload, control Contactor, overload, signal
Pump running, no differential Air lock, closed valve, blocked impeller Vent, valve position, strainer
Flow switch closed but no flow Stuck switch Remove and test
Flow present but switch open Air pocket at the switch Relocate or vent

Flow switches fail more often than pumps. Test the switch by removing it and operating it by hand before replacing a pump.

Oil pressure and oil level faults

Indication Cause Check
Low oil pressure at start Oil diluted with refrigerant Oil heater, oil temperature
Low oil pressure while running Oil filter blocked, pump wear Filter differential, pump
Oil level falling Leak, carry-over, incorrect charge Oil return, separator
High oil temperature Cooler fouled, low charge Oil cooler water flow

Oil pressure faults are the ones that destroy compressors fastest. If the machine trips twice on oil pressure, stop starting it and investigate. Each restart with poor lubrication removes bearing life.

Motor and starter faults

Code type Meaning Check
Overload trip Current above the limit Phase current, voltage, mechanical load
Overcurrent at start Locked rotor, winding fault Winding resistance, insulation
Earth fault Moisture or damaged cable Insulation resistance
Inverter overheat Cooling fan, heatsink, ambient Clean, check fan
Phase loss Supply problem Voltage on all three phases

Always measure insulation resistance before replacing a starter or a compressor. A winding at 0.5 MΩ will fail again, and a new starter will not fix it.

Communication and sensor faults

Symptom Cause Check
Controller cannot see the module Cable, address, termination Continuity, DIP switches
Sensor reading implausible Open circuit, short, drift Resistance against table
BMS shows a value but no alarm Point mapping Point list against controller
Random alarms Earthing, interference Screen continuity, cable routing

A sensor reading that is plausible but wrong is the hardest fault to find. Compare every temperature with an independent instrument at commissioning and at each annual service; that is how drift is caught.

A sequence that finds the cause

  1. Confirm the alarm is current, not historic.
  2. Check the water side before the refrigerant side.
  3. Compare displayed values with independent instruments.
  4. Record approach temperatures; they locate the problem in the evaporator or the condenser.
  5. Only then connect gauges, and record before and after.
  6. Change one thing at a time and re-measure.
Measurement Normal Where it points
Evaporator approach above 3 K Fouling or low flow Water side
Condenser approach above 4 K Fouling, air, low flow Water or air side
Superheat above 12 K Undercharge or restriction Refrigerant side
Subcooling above 12 K Overcharge or condenser flooding Refrigerant side
Current above FLA at rated condition Mechanical or electrical Compressor or supply

Longkang Environmental Equipment Co., Ltd. maintains a code table per controller generation, because a code number that means “low pressure” on one version can mean “sensor fault” on the next. Phone: +86 400-878-0280 | +86 130-0200-1280

Questions from service engineers

The chiller trips on high pressure only in summer. Why?

Condensing pressure follows the wet-bulb and the ambient. A condenser that is marginally fouled passes in spring and fails in July. Check the condenser approach; if it is above 4 K, clean it.

Can I run the chiller with the low-pressure switch bypassed?

No. The low-pressure switch protects against freezing and against operating with a lost charge. Bypassing it turns a repairable fault into a destroyed compressor.

Why does it trip at night when the load is low?

Low load reduces flow through the evaporator and lowers the suction pressure. Machines with limited unloading cannot run below about 20%–25% of capacity. A buffer tank or a smaller machine for night load solves it.

How do I know whether the problem is the sensor or the system?

Measure at the sensor pocket with a calibrated thermometer. If the independent reading is normal and the display is not, the sensor or its wiring is at fault.

How many resets are acceptable?

One, to see whether the fault is transient. A second reset without a diagnosis is a decision to risk the compressor. Oil pressure and freeze alarms should never be reset without investigation.

What should be in the spares kit?

Pressure transducers, one temperature sensor of each type, a flow switch, contactor coils, fuses and a set of gaskets. These cover most call-outs and allow diagnosis by substitution.