The one number that matters most
Approach temperature = leaving water temperature − saturated refrigerant temperature.
On a new machine the evaporator approach is 1–2 K and the condenser approach 1–2.5 K. Fouling adds to both. A condenser approach that has risen from 1.5 K to 3.5 K means the machine is condensing 2 K higher than it should, which costs roughly 2%–3% in power at the same load. That is small in one month and large over five years.
| Approach change | Likely cause | Action |
|---|---|---|
| +1 K over a season | Light fouling | Brush clean at next service |
| +2 K | Fouling or reduced flow | Clean tubes, check strainer and pump |
| +4 K | Heavy scale | Chemical clean, review water treatment |
| +6 K or more | Blocked tubes or air in condenser | Inspect, rod through, check venting |
The schedule
| Interval | Task | Who | Acceptance |
|---|---|---|---|
| Daily | Log temperatures, pressures, current | Operator | Within 5% of baseline |
| Weekly | Check for leaks, unusual noise, oil level | Operator | No change |
| Monthly | Water treatment test and dosing check | Treatment contractor | Within limits |
| Monthly | Clean strainers | Technician | Differential below 10 kPa |
| Quarterly | Check electrical terminations and contactors | Electrician | No heat discolouration |
| 6-monthly | Verify safeties and interlocks | Technician | Each operates |
| Annually | Brush-clean condenser and evaporator tubes | Technician | Approach back within 1 K of baseline |
| Annually | Oil sample and analysis (screw) | Laboratory | Moisture, acidity, metals within limits |
| Annually | Leak check and refrigerant log | Certified engineer | No leak above threshold |
| Annually | Vibration reading at each bearing | Technician | Within 50% of baseline |
| 3–5 years | Replace contactors, check capacitors, inspect starters | Electrician | Within tolerance |
| 8–10 years | Major overhaul: bearings, seals, oil change | Manufacturer | Per overhaul manual |
Tube cleaning: brushing versus chemical
| Method | Suited to | Advantage | Limitation |
|---|---|---|---|
| Nylon brush | Soft fouling, annual routine | No chemicals, quick | Does not remove scale |
| Rotary brush | Moderate scale | Better contact | Needs access at both ends |
| Chemical circulation | Hard scale, tight tubes | Reaches everywhere | Waste disposal, corrosion risk |
| Mechanical rodding | Blocked tubes | Clears debris | Can damage tube ends |
Brush cleaning needs the tube pull space described in the installation guide. If that space was not left, the only option is chemical cleaning, which is slower and produces waste. This is why layout decisions are maintenance decisions.
Water treatment is not optional
| Parameter | Target | Failure mode |
|---|---|---|
| pH | 7.5–9.0 | Acid corrosion or scale |
| Conductivity | Below 500 µS/cm | Scale and corrosion |
| Chloride | Below 200 mg/L | Pitting of stainless steel |
| Hardness | 60–200 mg/L as CaCO3 | Scale above 300 |
| Iron | Below 0.5 mg/L | Deposits, under-deposit corrosion |
| Bacteria (cooling water) | Below 10⁴ CFU/mL | Biofilm, Legionella risk |
Biofilm is worse than scale in a cooling circuit: it insulates, it blocks, and it harbors bacteria. A tower that is not treated will grow a film within weeks in warm weather.
Oil and refrigerant
| Check | Interval | Acceptance |
|---|---|---|
| Oil level | Weekly | Between sight glass marks |
| Oil color | Monthly | Clear, not dark |
| Moisture in oil | Annually | Below 100 ppm |
| Acidity | Annually | Within the oil supplier’s limit |
| Metal content | Annually | Trend, not absolute |
| Refrigerant charge | Annually, by approach | No unexplained drift |
| Leak test | Annually | No leak above the regulatory threshold |
Oil analysis is the cheapest early warning of bearing wear available. A rising iron or copper reading over two samples means something is wearing, and it is far cheaper to investigate then than after a seizure.
Electrical and controls
| Item | Check | Interval |
|---|---|---|
| Terminal torque | Per manufacturer’s table | Annually |
| Contactor pitting | Visual | Annually |
| Capacitor capacitance | Within 10% | 3 years |
| Sensor calibration | Compare with reference | Annually |
| BMS points | All report correctly | Annually |
| Alarm history | Review and clear | Monthly |
Sensor drift is a silent efficiency thief. A chilled water sensor reading 1 K low makes the machine run at a lower setpoint than necessary, which costs about 3% per Kelvin.
Longkang Environmental Equipment Co., Ltd. provides a service log template with the chiller that records approach temperatures at every visit, so the trend is visible rather than reconstructed from memory. Phone: +86 400-878-0280 | +86 130-0200-1280
Questions from facility managers
How often should chiller tubes be cleaned?
Annually for most buildings, based on approach temperature rather than the calendar. If the condenser approach rises by 2 K, clean it; if it has not moved in two years, the water treatment is working.
Can I clean the tubes myself?
Brush cleaning is within the capability of a trained maintenance team, provided the tube ends are accessible and the water is isolated and drained. Chemical cleaning should be done by a contractor with waste handling arrangements.
What does an annual service cost relative to a breakdown?
A preventive visit is typically a small fraction of an emergency call-out plus lost cooling. The bigger saving is energy: a fouled condenser can add 10%–15% to chiller power, which over a season exceeds the service cost.
What service life should I expect from a chiller?
Fifteen to twenty years with proper maintenance, and often longer for centrifugal machines that are overhauled at ten years. Neglected water treatment can halve that.
Do I need to change the oil every year?
Not necessarily. Oil analysis decides. Many screw chillers go three to five years between oil changes if the analysis is clean. Changing oil on a calendar alone wastes money; never changing it risks the compressor.
What records should be kept?
Baseline commissioning data, approach temperatures at every service, oil analysis results, refrigerant added and recovered, and alarm history. These four sets answer almost every warranty and performance question.