Water Chiller Maintenance Schedule and Service Plan

The one number that matters most

Approach temperature = leaving water temperature − saturated refrigerant temperature.

On a new machine the evaporator approach is 1–2 K and the condenser approach 1–2.5 K. Fouling adds to both. A condenser approach that has risen from 1.5 K to 3.5 K means the machine is condensing 2 K higher than it should, which costs roughly 2%–3% in power at the same load. That is small in one month and large over five years.

Approach change Likely cause Action
+1 K over a season Light fouling Brush clean at next service
+2 K Fouling or reduced flow Clean tubes, check strainer and pump
+4 K Heavy scale Chemical clean, review water treatment
+6 K or more Blocked tubes or air in condenser Inspect, rod through, check venting

The schedule

Interval Task Who Acceptance
Daily Log temperatures, pressures, current Operator Within 5% of baseline
Weekly Check for leaks, unusual noise, oil level Operator No change
Monthly Water treatment test and dosing check Treatment contractor Within limits
Monthly Clean strainers Technician Differential below 10 kPa
Quarterly Check electrical terminations and contactors Electrician No heat discolouration
6-monthly Verify safeties and interlocks Technician Each operates
Annually Brush-clean condenser and evaporator tubes Technician Approach back within 1 K of baseline
Annually Oil sample and analysis (screw) Laboratory Moisture, acidity, metals within limits
Annually Leak check and refrigerant log Certified engineer No leak above threshold
Annually Vibration reading at each bearing Technician Within 50% of baseline
3–5 years Replace contactors, check capacitors, inspect starters Electrician Within tolerance
8–10 years Major overhaul: bearings, seals, oil change Manufacturer Per overhaul manual

Tube cleaning: brushing versus chemical

Method Suited to Advantage Limitation
Nylon brush Soft fouling, annual routine No chemicals, quick Does not remove scale
Rotary brush Moderate scale Better contact Needs access at both ends
Chemical circulation Hard scale, tight tubes Reaches everywhere Waste disposal, corrosion risk
Mechanical rodding Blocked tubes Clears debris Can damage tube ends

Brush cleaning needs the tube pull space described in the installation guide. If that space was not left, the only option is chemical cleaning, which is slower and produces waste. This is why layout decisions are maintenance decisions.

Water treatment is not optional

Parameter Target Failure mode
pH 7.5–9.0 Acid corrosion or scale
Conductivity Below 500 µS/cm Scale and corrosion
Chloride Below 200 mg/L Pitting of stainless steel
Hardness 60–200 mg/L as CaCO3 Scale above 300
Iron Below 0.5 mg/L Deposits, under-deposit corrosion
Bacteria (cooling water) Below 10⁴ CFU/mL Biofilm, Legionella risk

Biofilm is worse than scale in a cooling circuit: it insulates, it blocks, and it harbors bacteria. A tower that is not treated will grow a film within weeks in warm weather.

Oil and refrigerant

Check Interval Acceptance
Oil level Weekly Between sight glass marks
Oil color Monthly Clear, not dark
Moisture in oil Annually Below 100 ppm
Acidity Annually Within the oil supplier’s limit
Metal content Annually Trend, not absolute
Refrigerant charge Annually, by approach No unexplained drift
Leak test Annually No leak above the regulatory threshold

Oil analysis is the cheapest early warning of bearing wear available. A rising iron or copper reading over two samples means something is wearing, and it is far cheaper to investigate then than after a seizure.

Electrical and controls

Item Check Interval
Terminal torque Per manufacturer’s table Annually
Contactor pitting Visual Annually
Capacitor capacitance Within 10% 3 years
Sensor calibration Compare with reference Annually
BMS points All report correctly Annually
Alarm history Review and clear Monthly

Sensor drift is a silent efficiency thief. A chilled water sensor reading 1 K low makes the machine run at a lower setpoint than necessary, which costs about 3% per Kelvin.

Longkang Environmental Equipment Co., Ltd. provides a service log template with the chiller that records approach temperatures at every visit, so the trend is visible rather than reconstructed from memory. Phone: +86 400-878-0280 | +86 130-0200-1280

Questions from facility managers

How often should chiller tubes be cleaned?

Annually for most buildings, based on approach temperature rather than the calendar. If the condenser approach rises by 2 K, clean it; if it has not moved in two years, the water treatment is working.

Can I clean the tubes myself?

Brush cleaning is within the capability of a trained maintenance team, provided the tube ends are accessible and the water is isolated and drained. Chemical cleaning should be done by a contractor with waste handling arrangements.

What does an annual service cost relative to a breakdown?

A preventive visit is typically a small fraction of an emergency call-out plus lost cooling. The bigger saving is energy: a fouled condenser can add 10%–15% to chiller power, which over a season exceeds the service cost.

What service life should I expect from a chiller?

Fifteen to twenty years with proper maintenance, and often longer for centrifugal machines that are overhauled at ten years. Neglected water treatment can halve that.

Do I need to change the oil every year?

Not necessarily. Oil analysis decides. Many screw chillers go three to five years between oil changes if the analysis is clean. Changing oil on a calendar alone wastes money; never changing it risks the compressor.

What records should be kept?

Baseline commissioning data, approach temperatures at every service, oil analysis results, refrigerant added and recovered, and alarm history. These four sets answer almost every warranty and performance question.