Classification comes before selection
A chiller for a hazardous area is specified by the area, not by the machine. Three pieces of information are needed:
- Zone: where the flammable atmosphere can occur, and for how long.
- Gas group: how easily the gas ignites, IIA (propane), IIB (ethylene), IIC (hydrogen, acetylene).
- Temperature class: the maximum surface temperature the gas can tolerate, T1 (450 °C) to T6 (85 °C).
| Zone | Definition | Typical chiller approach |
|---|---|---|
| Zone 0 | Continuous flammable atmosphere | No chiller inside; remote plant only |
| Zone 1 | Likely during normal operation | Ex-rated machine or remote plant |
| Zone 2 | Unlikely, short duration | Ex-rated or purged machine |
| Safe area | No flammable atmosphere | Standard machine, ducted air if needed |
Most chemical plants put the chiller in a safe area and circulate chilled water or glycol into the hazardous zone. That is cheaper, easier to maintain and easier to certify than an Ex machine inside Zone 1.
Protection concepts and what they mean
| Concept | Code | How it works | Suited to |
|---|---|---|---|
| Flameproof enclosure | Ex d | Contains an internal explosion | Compressors, motors in Zone 1 |
| Increased safety | Ex e | Prevents sparks and hot spots | Terminal boxes, luminaires |
| Pressurised | Ex p | Keeps flammable gas out with air | Control panels, large enclosures |
| Intrinsic safety | Ex ia/ib | Limits energy in the circuit | Sensors, instrumentation |
| Encapsulation | Ex m | Seals the components | Small devices |
| Dust protection | Ex t | Enclosure for combustible dust | Flour, sugar, coal plants |
A chiller in a hazardous area typically combines several: Ex d motors, Ex e terminals, Ex p panel, Ex ia sensors. The combination is stated on the nameplate and in the certificate.
Temperature class and surface temperature
| Class | Maximum surface temperature | Gases that require it |
|---|---|---|
| T1 | 450 °C | Most common gases |
| T2 | 300 °C | Ethylene, some solvents |
| T3 | 200 °C | Hydrogen sulfide, petrol |
| T4 | 135 °C | Diethyl ether, acetaldehyde |
| T5 | 100 °C | Rare, special cases |
| T6 | 85 °C | Carbon disulphide |
A compressor discharge line at 90 °C is acceptable in a T4 area but not in a T5 area. That constraint can eliminate a high-condensing-temperature design, which is why the condenser and the refrigerant choice matter as much as the motor.
Refrigerant choice in hazardous areas
| Refrigerant | Flammability | Comment |
|---|---|---|
| R134a | Non-flammable | Common, A1 |
| R513A | Non-flammable | A1, lower GWP |
| R410A | Non-flammable | A1, higher pressure |
| R32 | A2L, mildly flammable | Adds a second ignition source risk |
| Ammonia | B2L, toxic and flammable | Needs a dedicated machine room |
| CO₂ | Non-flammable, high pressure | Transcritical, specialist |
Adding a flammable refrigerant to a hazardous area complicates the risk assessment. For most chemical plants, an A1 refrigerant is the simpler approval path.
Arrangement options
| Arrangement | Capital | Maintenance | Certification |
|---|---|---|---|
| Standard chiller in a safe area, glycol to the process | Lowest | Easy | Simple |
| Standard chiller with ducted outdoor air and remote condenser | Low | Easy | Moderate |
| Ex-rated packaged chiller in Zone 2 | High | Specialist | Complex |
| Ex-rated split system, condenser in a safe area | Medium | Moderate | Moderate |
| Ammonia plant in a dedicated room | High | Specialist | Complex |
The first option should always be considered first. Piping glycol 30 m is usually cheaper than certifying a machine for Zone 1.
Installation requirements
| Item | Requirement |
|---|---|
| Earthing and bonding | All metal parts bonded, resistance below 1 Ω |
| Cable glands | Ex-rated, matched to the cable |
| Cable type | Armored or conduit, no exposed flexibles |
| Isolation | Lockable, outside the hazardous area |
| Ventilation | Designed for the area, with gas detection |
| Gas detection interlock | Trips the plant on alarm |
| Hot surfaces | Insulated and guarded to the T class |
| Maintenance procedure | Gas clearance before opening |
The interlock matters: if gas is detected, the chiller should stop, not continue running with a sparking contactor. The trip should be hard-wired, not dependent on the BMS.
Reactor cooling: the process side
| Requirement | Detail |
|---|---|
| Temperature stability | ±0.5 K is often required for reaction control |
| Turn-down | 10%–100% with stable temperature |
| Fluid | Glycol or a heat transfer fluid, not water |
| Control | Cascade from reactor temperature to chiller capacity |
| Buffer | A tank to smooth exothermic peaks |
| Safety | Relief and over-temperature protection on the reactor side |
A reactor cooling load can change by 50% in a minute when a reaction starts. The chiller needs a buffer tank and a fast-acting control valve, or the reactor temperature will run away.
A configuration example
A fine chemical plant, 350 kW reactor cooling at −5 °C, Zone 2 area:
| Item | Selection | Reason |
|---|---|---|
| Chiller | 2 × 200 kW screw, glycol 35% | N+1, −8 °C leaving |
| Location | Safe area, 25 m from the reactor building | Avoids Ex certification |
| Panel | Ex p purged, mounted in the safe area | Certified control |
| Piping | Welded stainless, no flanged joints in the zone | Leak reduction |
| Buffer | 3 m³ | Exothermic peak smoothing |
| Detection | Gas detection interlocked to the chiller | Safety |
| Earthing | Bonded grid, below 1 Ω | Static control |
The distance from the reactor building is the key decision: it removes the need for an Ex-rated compressor and makes maintenance possible without a gas clearance certificate.
Longkang Environmental Equipment Co., Ltd. supplies hazardous-area schemes with the zone drawing, the Ex certificate list and the interlock schedule, so the installation can be inspected against a single document set. Phone: +86 400-878-0280 | +86 130-0200-1280
Questions from chemical plant engineers
Can a standard chiller be installed in Zone 2?
Only with additional protection, such as pressurisation or a local Ex enclosure, and with a documented risk assessment. In most jurisdictions a standard machine is not acceptable in Zone 2 without modification.
What is the cheapest compliant arrangement?
A standard chiller in a safe area with glycol piped to the process. It avoids Ex equipment entirely and is easier to maintain.
How is the temperature class determined?
By the gas present and its ignition temperature, taken from the plant’s hazardous area classification drawing. Do not guess: the drawing is the reference.
Does the refrigerant need to be non-flammable?
It is strongly preferred. A2L refrigerants add a second flammable source and complicate the assessment; A1 refrigerants keep the analysis simple.
How often must Ex equipment be inspected?
Typically annually for visual and close inspection, with a detailed inspection every three years. The regime is defined in the local electrical code for hazardous areas.
What happens if gas is detected?
The chiller should trip automatically through a hard-wired interlock, the area should be ventilated, and the plant should not restart until the atmosphere is clear and the cause is found.