Map the process loads first
| Process | Temperature | Load characteristic | Circuit |
|---|---|---|---|
| Raw material chilling | 0–4 °C | Continuous, varies with intake | Glycol or direct expansion |
| Rapid cooling after cooking | 0–5 °C in under 2 h | Batch, high peak | Glycol, high flow |
| Cold store | −25 to 0 °C | Continuous | Refrigeration, not chilled water |
| Fermentation control | 8–15 °C | Continuous, tight tolerance | Chilled water |
| Packaging area | 10–18 °C | Continuous | Chilled water |
| Comfort | 24–26 °C | Working hours | Chilled water |
Chilled water at 7/12 °C is too warm for most product cooling. Food plants usually need 0–2 °C water, which means glycol, a lower evaporating temperature and a lower COP. Design the process circuit separately from the comfort circuit.
The load profile is flat, and that changes the machine choice
| Plant type | Load profile | Chiller choice |
|---|---|---|
| Beverage bottling | Flat, 24 h, high | Screw, water-cooled, high hours |
| Meat processing | Day shift peak, washdown | Screw with VSD, N+1 |
| Dairy | Flat with CIP peaks | Screw, heat recovery |
| Bakery | Batch peaks | Screw plus buffer tank |
| Prepared meals | Two shifts, rapid cooling peaks | Screw, glycol, thermal buffer |
A flat 24-hour load is the most favorable case for a water-cooled chiller: the capital premium is recovered quickly because the machine runs at high load for 7,000 hours a year.
Glycol circuits: the efficiency penalty
| Glycol concentration | Freeze point | Capacity penalty | Pump power penalty |
|---|---|---|---|
| 10% | −4 °C | 3%–5% | 8%–12% |
| 20% | −9 °C | 6%–10% | 15%–20% |
| 30% | −15 °C | 10%–15% | 25%–30% |
| 40% | −24 °C | 15%–20% | 35%–45% |
Every percent of glycol costs capacity and pump energy. Use the minimum concentration that gives the required freeze protection, and do not specify 30% because “it is safer”.
Hygiene and washdown
| Requirement | Detail |
|---|---|
| Chiller location | Outside the production area, or in a separate plant room |
| Panel rating | IP65 minimum, IP66 in washdown zones |
| Materials | Stainless or coated, no exposed insulation |
| Pipework | Stainless or food-grade, welded where possible |
| Insulation | Closed cell with a sealed jacket, no fabric facing |
| Drainage | Trapped, with a fall, no ponding |
| Cleaning | Equipment accessible for foam cleaning |
| Pest control | No gaps, no ledges |
A chiller in a washdown area will be hosed. If the panel is IP54 and the cable entries are not sealed, water will find the control board within a month.
Food safety documentation
| Document | Purpose |
|---|---|
| Material certificates | Contact surfaces and insulation |
| Cleaning procedure | For the chiller and the circuit |
| Temperature log | Continuous, with alarm |
| Change control | Any modification recorded |
| Refrigerant record | Charge, leaks, recovery |
| Commissioning record | Flows, temperatures, capacity |
Auditors ask for these during a food-safety audit. A chiller without a temperature log is a non-conformity waiting to happen.
Heat recovery: the strongest argument in food plants
A food plant has simultaneous cooling and heating demand: process cooling rejects heat, and CIP (clean-in-place), washdown and boiler feed need hot water at 60–80 °C.
| Recovery method | Temperature available | Share of heating demand |
|---|---|---|
| Desuperheater | 45–65 °C | 15%–25% |
| Full condenser recovery | 35–50 °C | 40%–60% |
| Heat pump on condenser water | Up to 75 °C | 60%–80% |
| Dedicated heat recovery chiller | 50–70 °C | Simultaneous, high |
A plant with 1,000 kW of cooling rejects about 1,250 kW of heat. Recovering even a third of it displaces a significant amount of boiler fuel, and the payback is often under three years.
Redundancy for a production line
| Criticality | Redundancy | Comment |
|---|---|---|
| Product cooling, single line | N+1 on the chiller | A stoppage spoils product |
| Multiple lines | N+1 plant, sectional headers | One failure does not stop all lines |
| Cold store | 2N or standby | Product loss is severe |
| Comfort | N | Acceptable |
The cost of a chiller failure in a food plant is not the repair; it is the product in the line. That justifies redundancy that a comfort system would never carry.
A configuration example
A prepared-meals plant, 800 kW process cooling at 0 °C, 200 kW comfort:
| Item | Selection | Reason |
|---|---|---|
| Process chiller | 2 × 450 kW screw, glycol 25% | N+1, 0 °C water |
| Comfort chiller | 1 × 250 kW air-cooled | Independent, low hours |
| Buffer tank | 10 m³ | Smooths batch peaks |
| Heat recovery | Desuperheater on both process machines | CIP preheat |
| Towers | 2 cells | Turndown |
| Panel | IP66, stainless | Washdown |
| Monitoring | Temperature log to the QA system | Audit trail |
The separate comfort chiller is deliberate: it keeps the process circuit simple and lets the plant run the comfort system only during shifts.
Longkang Environmental Equipment Co., Ltd. supplies food-plant chillers with IP66 panels, stainless frames and a documented cleaning procedure, so the equipment can be included in the plant’s food-safety system rather than treated as an exception. Phone: +86 400-878-0280 | +86 130-0200-1280
Questions from food plant engineers
Can a standard chiller be used in a food plant?
Mechanically yes, but the panel, the materials and the cleaning arrangements usually fail an audit. Specify IP66, stainless and a sealed insulation jacket from the start.
How do I cool product to 0 °C with chilled water?
Use glycol at −2 to 0 °C, or a direct-expansion system. Chilled water at 7 °C cannot cool product to 0 °C.
Is ammonia better than HFC for a food plant?
Ammonia is more efficient and has no GWP, but it needs a machine room with gas detection, qualified operators and a safety regime. Many plants use HFC or HFO systems for smaller loads and ammonia for large central plants.
How much buffer tank do I need?
Enough for 10–20 minutes at peak flow, typically 5–15 m³. The buffer absorbs batch peaks and lets the chiller run at steady load.
What happens during a power failure?
The chiller stops, but the product does not wait. Either provide generator backup for the process circuit or design the process to tolerate a short interruption. Check the cold chain requirement first.
How often should the condenser be cleaned?
Quarterly in a food plant, because airborne fat and flour coat the coil. A coated coil loses capacity quickly and is a fire risk in extreme cases.