Heat Pump versus Gas Boiler for Hot Water: Running Cost and Carbon

The two efficiencies are not comparable directly

A gas boiler is rated on its gross or net efficiency, typically 88%–92% for a modern condensing unit, or 80%–85% for an older atmospheric boiler. A heat pump is rated on COP, typically 3.0–4.5. To compare them, put both on the same basis: energy delivered per unit of purchased energy.

System Efficiency Purchased energy per 52.3 kWh of heat
Old atmospheric boiler 0.75–0.82 64–70 kWh gas
Modern condensing boiler 0.90–0.94 56–58 kWh gas
Air-source heat pump, 20 °C COP 4.0 13.1 kWh electricity
Air-source heat pump, 7 °C COP 3.3 15.8 kWh electricity
Air-source heat pump, −5 °C COP 2.4 21.8 kWh electricity

So a heat pump uses roughly a quarter of the purchased energy of a condensing boiler, in units. Whether that is cheaper depends entirely on the price ratio.

The price ratio decides everything

Let P_g be the gas price per kWh and P_e the electricity price per kWh. The heat pump is cheaper when:

P_e ÷ COP < P_g ÷ boiler efficiency

Gas price Boiler efficiency Electricity price at which heat pump breaks even (COP 3.3)
USD 0.03/kWh 0.90 USD 0.110/kWh
USD 0.04/kWh 0.90 USD 0.147/kWh
USD 0.05/kWh 0.90 USD 0.183/kWh
USD 0.06/kWh 0.90 USD 0.220/kWh
USD 0.08/kWh 0.90 USD 0.293/kWh

In most markets electricity costs three to four times as much as gas per kWh, and a COP of 3.3 gives a break-even ratio of about 3.0. That is why the answer is marginal in some countries and decisive in others.

A worked comparison

Assumptions: 10 m³ per day at ΔT 45 K, gas at USD 0.05/kWh, electricity at USD 0.12/kWh, condensing boiler at 92%, heat pump at COP 3.2 annual average.

Item Gas boiler Heat pump
Heat required per day 523 kWh 523 kWh
Purchased energy per day 568 kWh gas 163 kWh electricity
Daily cost USD 28.40 USD 19.60
Annual cost USD 10,370 USD 7,150
Annual saving — USD 3,220 (31%)
Capital cost Baseline +USD 18,000–28,000
Simple payback — 6–9 years

A 31% saving and a six-to-nine-year payback is a real but unspectacular case. Change the electricity price to USD 0.08/kWh and the saving becomes 54% with a three-to-four-year payback. Change gas to USD 0.03/kWh and the heat pump loses.

Where the heat pump wins clearly

Condition Why
No gas grid available LPG or diesel is far more expensive than gas
Gas price high, electricity moderate Common in import-dependent markets
Cooling demand on the same site Waste heat or shared infrastructure
Carbon or green certification target Gas cannot decarbonise without biogas
Electrical capacity already available Avoids a new gas connection
Urban air quality restrictions Gas NOx limits tightening

Where the boiler still wins

Condition Why
Very cheap gas, expensive electricity The ratio is against the heat pump
Peak load only, a few hours a year Capital cost cannot be recovered
Very high temperature process steam Beyond heat pump range
Existing boiler in good condition, short remaining life of the building Stranded asset risk
No space for outdoor units or storage Physical constraint

The honest answer for many retrofits is a hybrid: heat pumps for the base load, the boiler for peak and backup. That captures most of the saving with less capital and keeps resilience.

Hybrid sizing: how much heat pump?

Heat pump share of annual demand Saving achieved Capital Comment
30% About 25% Low Boiler still runs most of the winter
50% About 45% Medium Good balance for retrofits
70% About 65% Medium-high Boiler for cold snaps only
100% About 90% High Needs redundancy and low-temperature design

The first 50% of the load is the cheapest to capture, because it runs the most hours. Beyond 70%, the marginal cost rises steeply as the plant has to cover the coldest hours.

Carbon comparison

Source CO₂ per kWh heat Relative
Gas boiler at 92% 0.21 kg 100%
Heat pump COP 3.3, grid 0.55 kg/kWh 0.17 kg 79%
Heat pump COP 3.3, grid 0.30 kg/kWh 0.09 kg 43%
Heat pump COP 4.0, grid 0.20 kg/kWh 0.05 kg 24%

On a coal-heavy grid the heat pump’s carbon advantage is modest; on a cleaner grid it is large. Because grids are decarbonising, the heat pump’s advantage improves over its life, while the boiler’s does not.

Practical differences beyond cost

Factor Gas boiler Heat pump
Plant room Gas train, flue, ventilation, leak detection Outdoor units, storage, no flue
Maintenance Annual service, gas safety check Coil cleaning, refrigerant check
Life 12–20 years 15–20 years
Noise Burner and flue Fan and compressor
Response Fast Slower, needs storage
Safety Combustion, CO risk Refrigerant, electrical
Regulation Increasingly restricted Favored in new build

Refitting a boiler plant: the constraints that decide

Constraint Check before committing
Flow temperature Existing radiators may need 70–80 °C; heat pump prefers 55
Storage Boiler systems often have little; heat pump needs more
Electrical supply Typically needs a significant upgrade
Space Outdoor units and tanks need room the boiler did not
Flue and gas route Can be removed, which frees plant room space

The flow temperature is the constraint that kills most retrofits. A boiler system designed for 80/60 °C cannot simply be fed at 55 °C; the emitters have to be enlarged or the heat pump has to be a high-temperature model with a lower COP.

Longkang Environmental Equipment Co., Ltd. builds the comparison around the site’s actual gas and electricity tariffs and the existing boiler’s measured efficiency, rather than a generic ratio, because a 10% error in the gas price changes the conclusion. Phone: +86 400-878-0280 | +86 130-0200-1280

Questions from retrofit projects

Is a heat pump always cheaper to run than a gas boiler?

No. It depends on the price ratio. With gas at USD 0.03/kWh and electricity at USD 0.15/kWh, a boiler at 92% is cheaper than a heat pump at COP 3.3. Do the arithmetic before promising a saving.

What COP should I use in the calculation?

The seasonal average at the actual water temperature, not the rated COP at 7 °C. For 60 °C storage in a cold climate, 2.5–3.0 is realistic; for 45 °C in a mild climate, 3.5–4.0.

Can I keep the boiler as backup and still claim the saving?

Yes, and it is the usual approach. Model the hybrid: the saving is proportional to the share of load the heat pump carries, not to its rated capacity.

How long does a boiler-to-heat-pump conversion take?

Four to ten weeks for a commercial plant, including electrical upgrade and storage. The electrical work is often the critical path, not the heat pump.

Do I need to change the radiators?

If the existing system runs at 80/60 °C, probably yes, or add surface area. If it runs at 60/45 °C, the heat pump can usually match it. Measure the actual flow temperature before deciding.

What about NOx and air quality rules?

Many cities now limit NOx from gas boilers, and some restrict new gas connections entirely. Check the local rules; they can make the decision for you regardless of price.