The four stages
1. Evaporation. Low-pressure liquid refrigerant enters the evaporator, where it is exposed to the returning chilled water. Because its boiling point is far below the water temperature, it boils and absorbs heat. The chilled water leaves at the supply setpoint, usually 7 °C.
2. Compression. The compressor draws in the vapor and raises its pressure, which also raises its temperature — above the temperature of the outdoor air or the cooling tower water, so that heat can flow out of it.
3. Condensation. The hot high-pressure vapor passes through the condenser. Air-cooled machines use fans and a finned coil; water-cooled machines use a shell-and-tube condenser with cooling tower water. The refrigerant condenses to liquid as it gives up heat.
4. Expansion. The liquid passes through an expansion valve or orifice, where the pressure drops sharply, the temperature falls, and the refrigerant is ready to absorb heat again.
| Stage | Where | Refrigerant state | What the water does |
|---|---|---|---|
| Evaporation | Evaporator | Liquid → vapor | Chilled water gives up heat, cools to 7 °C |
| Compression | Compressor | Low-pressure vapor → high-pressure vapor | No water contact |
| Condensation | Condenser | Vapor → liquid | Air or tower water absorbs the heat |
| Expansion | Expansion valve | High-pressure liquid → low-pressure mixture | No water contact |
What the four components do
| Component | Function | Common problem |
|---|---|---|
| Compressor | Raises pressure and temperature | Winding failure, valve wear, oil loss |
| Evaporator | Absorbs heat from chilled water | Freeze damage at low flow, fouling |
| Condenser | Rejects heat to air or water | Scaling and fouling — the most common capacity killer |
| Expansion valve | Meters refrigerant flow | Blockage, incorrect superheat setting |
Two accessories matter more than their cost suggests: the chilled water flow switch, which prevents the evaporator freezing when the pump stops, and the high-pressure cut-out, which protects the compressor when the condenser cannot reject heat — for example, on a hot day with a fouled coil.
Air-cooled versus water-cooled
| Aspect | Air-cooled | Water-cooled |
|---|---|---|
| Heat rejection | Fans and finned coil | Cooling tower |
| Efficiency | Lower, varies with weather | Higher, more stable |
| Installation | No tower, no condenser pumps | Tower, pumps, water treatment |
| Footprint | Large, outdoors | Compact, indoors |
| Maintenance | Coil cleaning | Coil cleaning plus tower and water treatment |
| Suited to | Small to medium loads, no plant room | Medium to large loads, tower space available |
The efficiency gap exists because air temperature in summer is much higher than the wet-bulb temperature that a cooling tower can approach. A water-cooled chiller therefore compresses against a lower condensing temperature, which costs less work.
What “7/12 °C” means, and why it matters
The standard rating condition is 7 °C chilled water supply and 12 °C return — a 5 K range. That 5 K drives everything downstream:
- Flow: 1 m³/h carries 5.8 kW at a 5 K range.
- Pipe size, pump head and pressure drop all follow from that flow.
- A wider range (say 7/15 °C) reduces flow and pipe cost but requires terminal units designed for it.
- A narrower range increases flow and pumping energy.
Changes to the chilled water temperature also change chiller capacity: roughly 3% of capacity per kelvin of evaporating temperature. Lowering the supply from 7 °C to 4 °C may cost 10%–15% of capacity.
Why the condenser is the maintenance priority
Chillers rarely lose capacity because the compressor wore out. They lose it because the condenser stopped rejecting heat: scale on a water-cooled bundle, dust and pollen on an air-cooled coil, or a cooling tower that is no longer distributing water evenly. The symptoms are consistent — high condensing pressure, reduced capacity, higher power draw, and eventually a high-pressure trip on the hottest afternoon of the year.
Cleaning the condenser is the cheapest capacity recovery available. On a fouled machine it can restore 10%–20% of output.
Frequently asked questions
What is the difference between a chiller and an air conditioner?
An air conditioner is a chiller plus an air-side distribution system. A chiller produces chilled water; fan coil units, air handling units or process heat exchangers then use that water. The refrigeration cycle is identical.
Does a chiller need a cooling tower?
Only water-cooled machines do. Air-cooled chillers reject heat directly to the atmosphere and need no tower, which is why they dominate small and rooftop installations.
How cold can chilled water be?
Standard machines go to about 4–5 °C supply. Below that, and certainly below 0 °C, a low-temperature machine and a glycol or brine loop are required.
Why does my chiller run at high pressure in summer?
Because the condenser is rejecting heat to hotter air or warmer tower water, or because it is fouled. Check the condenser condition and the tower performance before suspecting the refrigerant charge.
How much electricity does a chiller use?
Divide cooling capacity by COP. A 500 kW chiller at COP 5.0 draws about 100 kW. Add 10%–20% for pumps and tower fans to get plant-level consumption.
Can a chiller heat water as well?
A reversible machine can, and heat recovery chillers capture condenser heat for preheating domestic hot water. The economics depend on whether heating and cooling demands coincide.
Longkang Environmental Equipment Co., Ltd. manufactures air-cooled and water-cooled water chillers across scroll, screw and centrifugal types, and supplies the operating data needed to verify performance after commissioning. Phone: +86 400-878-0280 | +86 130-0200-1280