Air-Source Heat Pump Fault Codes and Troubleshooting

Read the code with the condition

Before touching anything, record four things: the code, the water temperature at the time, the ambient temperature, and whether the fault appears at start-up or after a period of running. The same code means different things in those two cases.

Timing Meaning of the pattern
Immediate on start Interlock, sensor, phase or configuration
Within 30 seconds Flow, rotation, or a protection set too tight
After 10–30 minutes Charge, airflow, or a gradually rising pressure
Only on cold mornings Defrost, low ambient, or frost protection
Intermittent, random Loose connection, sensor drift, or supply quality

High pressure protection (E1 / HP)

The unit has exceeded its discharge pressure limit, typically 30–32 bar for R410A.

Check in order What you are looking for Typical finding
1. Airflow Blocked coil, recirculation, failed fan Dirty coil on a unit in a recess
2. Water flow Pump, strainer, valve, air Blocked strainer
3. Charge Overcharge after a top-up Subcooling above 12 K
4. Non-condensables Pressure high with normal temperatures Poor evacuation at installation
5. Water temperature Storage setpoint too high Setpoint above 60 °C

Do not reset and restart repeatedly. Each reset with the underlying cause present drives the compressor further into the limit and shortens its life. Fix the cause, then reset once.

Low pressure protection (E2 / LP)

Suction pressure has fallen below the cut-out, typically 2–4 bar.

Cause Confirm by Action
Low charge Subcooling low, superheat high Leak test, repair, recharge by weight
Restricted liquid line Temperature drop across the filter drier Replace the drier
Low water temperature / low load Unit running below its minimum load Check minimum load, add buffer volume
Low ambient Operation below the rated range Confirm model selection
Faulty low-pressure switch Switch open with normal pressures Replace switch

A unit that trips on low pressure only in the early morning, then runs all day, is usually short of charge rather than faulty. Cold ambient lowers the suction pressure enough to cross the limit that is only just met in the afternoon.

Water flow and frost protection (E3 / E4)

Code Meaning First check
E3 Water flow failure Pump running? Strainer clear? Air in circuit?
E4 Water temperature too low (frost risk) Setpoint, sensor reading, actual water temperature

E3 with the pump running is nearly always air or a blocked strainer. E3 with the pump not running is electrical: contactor, overload, or the pump’s own thermal trip. E4 in a system with correct flow points to a sensor that is reading low, or to a genuinely undersized unit that cannot hold temperature.

Defrost faults (E5 / E6)

Symptom Cause Action
Defrost never starts, coil iced Coil sensor open or displaced Check sensor resistance and clip
Defrost starts too often Sensor reading low, airflow restricted Compare sensor with ambient
Defrost does not terminate Sensor stuck, four-way valve fault Check valve operation
Water pools and refreezes Drain blocked or base too low Clear drain, raise base

Defrost faults are seasonal and environmental. A unit that defrosts every 25 minutes in damp, 2 °C air may be behaving correctly; the same unit defrosting every 25 minutes at 8 °C is not.

Communication and sensor faults (E7 / E8 / E9)

Code Meaning Check
E7 Communication failure between controller and module Cable, termination, address setting
E8 Discharge temperature too high Charge, airflow, sensor
E9 Sensor fault (ambient, coil, water) Resistance against a temperature table

Sensor faults are the easiest to confirm and the easiest to misdiagnose. Measure the sensor resistance and compare with the manufacturer’s table at the measured temperature; a 5 K error is enough to cause a defrost fault or a capacity shortfall without any code appearing at all.

Compressor protection and inverter faults

Indication Likely cause Check
Overload trip Supply voltage, winding, mechanical seizure Insulation resistance, current per phase
Inverter overcurrent IPM module, DC bus, short circuit Fault memory, module temperature
Inverter overheat Fan, heatsink blocked, high ambient Clean heatsink, check fan
Earth fault Moisture in terminal box, damaged cable Insulation test

Inverter faults are rarely caused by the inverter alone. Before replacing a module, confirm the compressor winding resistance is balanced and the insulation resistance is above 1 MΩ. A failing compressor will destroy a new module within hours.

A diagnostic sequence that works

  1. Confirm the fault is real by checking the physical condition, not just the display.
  2. Compare the displayed temperatures with an independent thermometer or clamp meter.
  3. Check the water side first — flow, air, strainer — because it is the cheapest to fix and the most common.
  4. Check the air side second — coil, fan, clearance, recirculation.
  5. Only then look at the refrigerant circuit, and only with gauges connected.
  6. Record the pressures, temperatures and current before and after the fix.
Reading Normal Suspicious
Water ΔT 4–5 K Above 7 K or below 3 K
Superheat 5–8 K Below 3 K or above 12 K
Subcooling 5–10 K Below 3 K or above 12 K
Discharge temperature 70–85 °C Above 95 °C
Compressor current Below nameplate FLA Above FLA at rated condition

Longkang Environmental Equipment Co., Ltd. publishes a code table matched to each controller version, because the same code number can mean different things across generations. Phone: +86 400-878-0280 | +86 130-0200-1280

Questions from service engineers

The unit shows a high-pressure fault but the gauge reads normal. Why?

The controller may be reading a different sensor, or the fault may be stored from an earlier event. Check the fault log with timestamps rather than the current alarm, and compare the controller’s pressure reading with a gauge on the same port.

Can I bypass a pressure switch to test the unit?

For a short diagnostic run, with gauges connected and a person watching, yes. As a permanent repair, no. A bypassed high-pressure switch removes the only protection between a blocked coil and a burst pipe.

Why does the unit trip only at night?

Lower ambient temperature reduces suction pressure, and lower water demand reduces flow through the unit. Either can cross a limit that is not reached during the day. Check the minimum load and the low-pressure cut-out setting.

How do I tell a sensor fault from a genuine temperature problem?

Measure the water or air temperature independently at the sensor location. If the independent reading is normal and the controller shows a large error, the sensor or its wiring is at fault. A 5 K error is common and rarely triggers a code.

Is it safe to keep resetting the unit?

Once, to see whether the fault is transient. Repeated resets with a real fault present cause repeated hard starts, which is how compressors are destroyed. Find the cause first.

What spare parts should be kept for fault finding?

A pressure switch pair, one temperature sensor of each type, a fan capacitor, a contactor and a set of fuses. These cover the majority of call-outs and let you confirm a diagnosis by substitution.