Heat pumps · Chillers · Sludge drying systems
Knowledge

What Is a Water Chiller? Working Principle, Types and Selection

Key facts at a glance

Question Short answer
What does it do? Produces chilled water for process or comfort cooling
Standard temperatures 7 °C supply / 12 °C return
Main configurations Air-cooled, water-cooled; screw, centrifugal, scroll
Typical COP Screw 4.5–6.0; centrifugal above 6.0 at design condition
What matters more than COP? Part-load performance, expressed as IPLV
What limits capacity? Condensing conditions, ambient temperature, chilled water temperature

How the refrigeration cycle works

Evaporation. Low-pressure refrigerant enters the evaporator, where it absorbs heat from the returning chilled water and boils. The chilled water leaves at the supply setpoint, typically 7 °C.

Compression. The compressor raises the refrigerant’s pressure and temperature so that it can reject heat to the condensing medium.

Condensation. In an air-cooled machine, fans draw ambient air across a finned coil and the refrigerant condenses, rejecting heat to the atmosphere. In a water-cooled machine, heat passes to condenser water and is carried to a cooling tower.

Expansion. The liquid refrigerant passes through the expansion device, pressure drops, temperature falls, and the cycle repeats.

Stage What happens Consequence
Evaporation Refrigerant absorbs heat from chilled water Chilled water cools to setpoint
Compression Pressure and temperature rise Heat becomes rejectable
Condensation Heat rejected to air or tower water Condenser must stay clean
Expansion Pressure drops Refrigerant ready to absorb heat again

Why condensing conditions dominate performance

A chiller’s capacity and efficiency are governed by the temperature lift between evaporating and condensing. On a 38 °C day, an air-cooled chiller rejects heat to hot air, so the condensing temperature rises, the compressor works harder and capacity drops. The same machine on a 25 °C day performs noticeably better. Water-cooled machines avoid this by rejecting heat to tower water held near wet-bulb temperature, which is why they are more efficient in hot climates — provided the tower and water treatment are maintained.

Types and how they compare

Type Condensing Efficiency Suited to Constraints
Air-cooled scroll Air Moderate Small to medium loads, no plant room Capacity limited by ambient; coil cleaning critical
Air-cooled screw Air Moderate to good Medium loads, outdoor installation Footprint and noise
Water-cooled screw Cooling tower Good (COP 4.5–6.0) Medium to large plants Needs tower, pumps, water treatment
Water-cooled centrifugal Cooling tower High (COP above 6.0) Large plants, long operating hours High first cost; specialist maintenance
Magnetic-bearing centrifugal Cooling tower High, strong part load Large plants with variable load Higher capital cost, electronic expertise
Low-temperature / brine Either Lower Process cooling below 0 °C Glycol loop, material selection
Explosion-proof Either Lower Hazardous areas Certification and enclosure cost

The choice is rarely about the highest COP on a datasheet. It is about which machine delivers the highest efficiency across the load profile the plant will actually see, at a capital cost the project can carry.

COP versus IPLV

COP is measured at a single full-load design point. It is useful for comparing machines of similar type at the same conditions, and it is the figure most often quoted in tenders.

IPLV integrates efficiency across part-load ratios — typically 100%, 75%, 50% and 25%. Because most plants run below full load for most of the year, IPLV is the more honest indicator of annual energy use.

A machine with a slightly lower full-load COP but a much better part-load curve will usually consume less energy over a year. This is why variable-speed drives and multiple-compressor staging matter: they let the machine follow the load instead of cycling on and off.

Metric Measures Use it when
COP Full-load efficiency at design point Comparing machines at identical conditions
IPLV Weighted part-load efficiency Estimating annual energy consumption
Annual energy simulation Hourly load versus ambient Sizing a plant with a known load profile

Selection criteria

1. Cooling load and profile. Not just the peak figure, but how many hours the plant spends at 25%, 50% and 75% load.

2. Chilled water temperatures. Standard 7/12 °C. Lower supply temperatures reduce capacity and efficiency, and may require a different machine or a glycol loop.

3. Condensing conditions. Design ambient temperature for air-cooled; tower approach and wet-bulb for water-cooled.

4. Redundancy. N+1 arrangement, and whether the plant can be maintained without a full shutdown.

5. Physical constraints. Footprint, weight, noise at the nearest sensitive receiver, structural loading on a roof.

6. Refrigerant and regulation. Charge limits, phase-down schedules and local rules affect which refrigerant is acceptable.

7. Electrical supply. Starting current, harmonic distortion and available capacity at the point of connection.

Installation and maintenance

Item Interval Why it matters
Clean condenser (air-cooled coil or tower) 3–12 months Fouling raises condensing pressure and cuts capacity
Check refrigerant charge and leaks Annually Slow leaks degrade performance silently
Oil and filter service (oil-lubricated) Per manufacturer schedule Contaminated oil damages bearings
Chilled water strainer cleaning 3–6 months Blockage causes low flow and freeze risk
Safety device testing Annually High-pressure and low-temperature protection must actually trip
Control calibration Annually Sensor drift causes unstable operation
Water treatment (water-cooled) Continuous Scaling and biological growth destroy efficiency

Magnetic-bearing machines have no oil circuit, which removes one maintenance item but adds a requirement for clean power and specialist diagnostics.

Frequently asked questions

What is the difference between a chiller and a heat pump?

Both use a vapor-compression cycle. A chiller’s useful output is the heat removed at the evaporator — chilled water. A heat pump’s useful output is the heat rejected at the condenser — hot water or warm air. Reversible machines can do both.

How do I calculate the cooling load?

Sum the sensible and latent gains: equipment, people, lighting, solar and fabric gains, plus process heat and any fresh-air load. Add a safety margin appropriate to the application, not a blanket percentage.

Can a chiller operate below 0 °C?

Yes, with a low-temperature machine and a glycol or brine secondary loop. Water alone cannot be used below 0 °C.

Why does capacity drop in summer?

Air-cooled machines reject heat to hotter air, which raises condensing temperature and reduces capacity. Water-cooled machines are affected mainly through tower performance and wet-bulb temperature.

How long does a chiller last?

Typically 15–20 years for a well-maintained water-cooled machine, somewhat less for air-cooled units in corrosive or dusty environments.

Should I choose one large chiller or several smaller ones?

Several smaller units give redundancy and better part-load staging. One large unit may have lower capital cost and a better full-load COP. The load profile usually decides.

What to include in a specification

Chilled water flow and return temperatures, design ambient or tower conditions, cooling load profile, allowable noise, footprint and weight limits, electrical supply, refrigerant preference, redundancy requirement, and the maintenance access available in the plant room.

Longkang Environmental Equipment Co., Ltd. manufactures air-cooled and water-cooled water chillers, including screw, centrifugal and magnetic-bearing types, with selection calculations, interface drawings and commissioning support. Phone: +86 400-878-0280 | +86 130-0200-1280

Related reading

Frequently asked questions