Classification, four ways
Every chiller sits at the intersection of four choices. Getting those four right narrows the catalog to a handful of models; arguing about model numbers before that is wasted effort.
| Classification | Options | What it decides |
|---|---|---|
| Compressor | Scroll, screw, centrifugal, magnetic bearing centrifugal | Capacity range, part-load behavior, maintenance |
| Heat rejection | Air-cooled, water-cooled, evaporative | Plant room space, water availability, COP |
| Refrigerant | R410A, R32, R134a, R513A, R1234ze | GWP compliance, pressure, charge limit |
| Duty | Comfort cooling, process cooling, low temperature | Leaving water temperature, control precision |
The series map
| Series type | Capacity range | Typical COP | Where it fits |
|---|---|---|---|
| Air-cooled scroll | 3–60 kW | 2.8–3.2 | Small commercial, no plant room, no cooling tower |
| Air-cooled screw | 60–500 kW | 3.0–3.4 | Mid-size buildings, rooftop or compound siting |
| Water-cooled scroll | 10–80 kW | 4.5–5.2 | Plant rooms with a tower, small process loads |
| Water-cooled screw | 100–1,000 kW | 5.2–6.0 | Offices, hotels, factories, district cooling |
| Water-cooled centrifugal | 300–3,000 kW | 5.8–6.6 | Large commercial, airports, campuses |
| Magnetic bearing centrifugal | 200–2,000 kW | 6.2–7.0 at full load, better part load | Data centers, hospitals, low-noise sites |
| Low-temperature process | 5–500 kW | 2.0–3.0 | Below 5 °C leaving water, brine or glycol |
| Heat recovery | 50–1,000 kW | — | Simultaneous cooling and hot water demand |
Capacity is quoted in kW or in refrigeration tons, where 1 RT = 3.517 kW. A “500 RT” machine is 1,759 kW, and a quotation that mixes the two units without saying so is a warning sign.
Decoding a model number
Manufacturers use their own schemes, but most follow a pattern of compressor code, nominal capacity, refrigerant and variant. A typical designation might read LSBLG-500M/R134a, which decodes as screw (L), water-cooled (S), flooded evaporator, 500 kW nominal, M variant, R134a.
| Field | Common codes | Meaning |
|---|---|---|
| Compressor | W / L / X / C | Scroll, screw, centrifugal, magnetic bearing |
| Condenser | F / S | Air-cooled (fan), water-cooled |
| Evaporator | G / B | Shell-and-tube, plate |
| Capacity | Number | kW nominal, occasionally RT |
| Variant | A / M / H | Revision, high-ambient, heat recovery |
The number in the model is nominal capacity at rating conditions, not at site conditions. A 500 kW machine at 7 °C leaving water and 30 °C entering condenser water delivers far less at 2 °C leaving water, or with 35 °C condenser water in August.
The rating conditions behind the catalog figures
Two rating frameworks dominate, and they are close but not identical.
| Parameter | GB/T 18430.1 | AHRI 550/590 |
|---|---|---|
| Chilled water leaving | 7 °C | 6.7 °C (44 °F) |
| Chilled water flow | 0.172 m³/(h·kW) | 2.4 gpm/ton |
| Condenser water entering | 30 °C | 29.4 °C (85 °F) |
| Condenser water flow | 0.215 m³/(h·kW) | 3.0 gpm/ton |
| Fouling factor | 0.000086 m²·K/W | 0.0001 m²·K/W |
A chiller rated COP 6.0 at these conditions will deliver about 5.4 if the condenser water arrives at 32 °C instead of 30 °C — a 5%–8% loss per 2 K, which matters in a tropical summer. Always ask for the correction table.
Selection matrix by application
| Application | First choice | Alternative | Key constraint |
|---|---|---|---|
| Office 5,000–20,000 m² | Water-cooled screw | Air-cooled screw | Plant room and tower space |
| Hotel | Water-cooled screw with heat recovery | Air-cooled screw | Simultaneous hot water demand |
| Factory process cooling | Water-cooled screw, plate exchanger | Air-cooled screw | Water quality, 24/7 duty |
| Data center | Magnetic bearing centrifugal or screw | Water-cooled screw | Part-load efficiency, redundancy |
| Hospital | Screw with N+1 | Magnetic bearing | Noise, infection control areas |
| Small retail or restaurant | Air-cooled scroll | — | No plant room, no tower |
| Chemical reactor cooling | Low-temperature screw, brine | Plate chiller + tower | Corrosion, explosion protection |
| Cold store pre-cooling | Low-temperature screw | — | Glycol, low evaporating temperature |
Three of these deserve a note. Hotels need heat recovery because the chiller rejects heat all day into a building that also heats water all day; the recovered heat can supply 60%–80% of the domestic hot water load in summer. Data centers need part-load performance, not full-load, because a 2N plant runs at 25%–40% for most of its life. Chemical plants need the wetted materials decided by the process fluid, not by the catalog.
Refrigerant choice in 2026
| Refrigerant | GWP (AR4) | Pressure | Status |
|---|---|---|---|
| R22 | 1,810 | Medium | Phase-out under the Montreal Protocol; no new equipment |
| R410A | 2,088 | High | Still common, being displaced |
| R32 | 675 | High | Growing share in small and mid-size |
| R134a | 1,430 | Low | Common in centrifugal and screw |
| R513A | 631 | Low | Drop-in for R134a |
| R1234ze | under 10 | Low | New centrifugal machines |
Ask for the charge in kilograms, not just the refrigerant type. A 1,000 kW centrifugal with 400 kg of R134a is a different compliance question from one with 250 kg of R1234ze, and some jurisdictions set charge thresholds that trigger leak detection and reporting.
Capacity control and part-load
The compressor type decides how the machine behaves below full load, and that is where most of the annual energy is spent.
| Compressor | Capacity control | Part-load behavior |
|---|---|---|
| Scroll | On/off stages or inverter | Inverter scroll holds 10%–100% smoothly |
| Screw | Slide valve, 25%–100% | Good, but efficiency falls below 40% |
| Centrifugal | Inlet guide vanes, 10%–100% | Excellent at high load, surge risk at low load |
| Magnetic bearing | Variable speed, 5%–100% | Flattest part-load curve, no oil system |
For a plant that spends its life between 30% and 60% load, a machine with a flat curve at part load beats one with a higher nominal COP. That is the argument for IPLV or integrated part-load value as the selection metric, and it is set out in our comparison of COP and IPLV.
Configuration: how many machines
| Plant size | Usual configuration | Reason |
|---|---|---|
| Under 300 kW | 1 machine + 1 standby, or 2 at 60% | Redundancy without complexity |
| 300–1,000 kW | 2–3 machines | Staging, maintenance without shutdown |
| 1,000–3,000 kW | 3–4 machines, mixed sizes | Wide efficient band |
| Above 3,000 kW | 4+ machines or centrifugal train | Redundancy, staged investment |
Mixed sizes — one large and one small — widen the band over which at least one machine runs near full load. Three equal machines give better redundancy but a poorer part-load curve in the 10%–30% range, where a single small machine would be ideal.
Longkang Environmental Equipment Co., Ltd. supplies air-cooled and water-cooled screw chillers from 60 to 1,000 kW with R134a or R513A, and provides capacity correction tables for condenser water temperatures from 25 °C to 40 °C with each quotation. Phone: +86 400-878-0280 | +86 130-0200-1280
Questions buyers ask
Is an air-cooled chiller less efficient than a water-cooled one?
Yes, typically 20%–30% at full load, because the air-cooled condenser works against a dry-bulb temperature of 35 °C rather than a wet-bulb-driven cooling tower at 30 °C. Air-cooled units win on installation cost, water use and plant room space, not on COP.
What does a “low-temperature” chiller mean?
Usually leaving water between −5 °C and +5 °C, using glycol or brine. Below 0 °C the evaporator must be rated for the mixture and the compressor for a higher pressure ratio; a comfort-cooling chiller cannot simply have its setpoint lowered.
How do I compare two quotations with different capacities?
Convert both to the same conditions: same leaving water temperature, same condenser water entering temperature, same flow, same fouling factor. Then compare kW per kW of cooling and check the part-load figures at 50% and 25%.
Does the number in the model equal the kW?
Usually the nominal kW at rating conditions, but some manufacturers use RT or a nominal horsepower. Confirm on the datasheet, and check the capacity table rather than the model number.
How much space does a 500 kW water-cooled chiller need?
Roughly 3.5 × 1.6 m in plan plus 1.0–1.2 m clear at the tube ends for cleaning, and space above for lifting the compressor. Allow a further 30%–40% for pumps, headers and the control panel.
Is heat recovery worth specifying?
If the building has a year-round hot water load — hotel, hospital, swimming pool — yes. A heat recovery chiller can deliver 60%–80% of the summer hot water demand at a marginal cost of 5%–10% on the chiller, and it removes that load from the boilers.
Related reading