Answers to the questions that decide selection and delivery
Frequently asked questions by product system, based on LONGCOM technical articles and project practice. For a project-specific answer, send the duty conditions directly.
Air-source heat pump systems
Can a heat pump deliver 60 °C reliably in winter
At −5 °C ambient, most units reach 55–60 °C with reduced capacity. Specify an immersion top-up for the final 5–10 K so the tank always reaches 60 °C, and size the heat pump on the 55 °C duty.
Read the full technical article →Is a separate circuit for theatres really necessary
Yes. Theatres need assured temperature, no interruption and often filtered water. Sharing a circuit with the laundry means a laundry peak can affect a scrub sink.
Read the full technical article →How much storage should a hospital hold
Enough for the peak plus one disinfection cycle: typically 20%–30% of daily demand for wards, and one full day for CSSD. Storage also provides the buffer that lets the plant run at a steady load.
Read the full technical article →What documentation does a hospital project need
A water safety plan, schematic with dead legs, temperature monitoring schedule, commissioning records for every circuit, and a validation report for the legionella regime. Expect the estate team to audit all of it.
Read the full technical article →Industrial cooling systems
Which is more reliable
Both are mature. Screw machines tolerate abuse better and are simpler to service; centrifugal machines have fewer moving parts in the compressor but need surge protection and, in oil-fed designs, careful oil management.
Read the full technical article →Can a centrifugal run at 10% load
Most cannot without hot gas bypass, which wastes energy. Below 20%–30%, a smaller machine or a screw is the better answer.
Read the full technical article →Is a magnetic bearing chiller worth the premium
Where maintenance access is difficult, where oil contamination is unacceptable, or where part-load efficiency is the priority. The premium is typically 15%–30% and is recovered through efficiency and maintenance.
Read the full technical article →How does refrigerant choice affect the decision
Large centrifugal machines historically used low-pressure refrigerants; modern designs use HFCs or HFOs with different charge sizes and safety classifications. Check the charge against local refrigerant regulations.
Read the full technical article →Sludge drying systems
What cake solids should I design for
Use the measured value from the actual press and sludge, not the catalog. If the press is not yet installed, use a pilot test or a conservative figure 2–3 points below the brochure.
Read the full technical article →Is lime conditioning compatible with drying
It works but it is inefficient: lime adds mass that has to be heated and reduces the organic content. Use it only if the downstream route requires pH adjustment.
Read the full technical article →How big should the cake buffer be
Eight hours of production is the normal minimum; 24 hours gives much more flexibility and is worth the space in a plant that runs a single shift.
Read the full technical article →Can the dryer take cake directly from the press
Yes, with a buffer and a variable-speed feeder. Direct feeding without a buffer causes the dryer to cycle and the product moisture to vary.
Read the full technical article →