Answers to the questions that decide selection and delivery
Frequently asked questions by product system, based on LONGCOM technical articles and project practice. For a project-specific answer, send the duty conditions directly.
Air-source heat pump systems
The unit shows a high-pressure fault but the gauge reads normal. Why
The controller may be reading a different sensor, or the fault may be stored from an earlier event. Check the fault log with timestamps rather than the current alarm, and compare the controller's pressure reading with a gauge on the same port.
Read the full technical article →Can I bypass a pressure switch to test the unit
For a short diagnostic run, with gauges connected and a person watching, yes. As a permanent repair, no. A bypassed high-pressure switch removes the only protection between a blocked coil and a burst pipe.
Read the full technical article →Why does the unit trip only at night
Lower ambient temperature reduces suction pressure, and lower water demand reduces flow through the unit. Either can cross a limit that is not reached during the day. Check the minimum load and the low-pressure cut-out setting.
Read the full technical article →How do I tell a sensor fault from a genuine temperature problem
Measure the water or air temperature independently at the sensor location. If the independent reading is normal and the controller shows a large error, the sensor or its wiring is at fault. A 5 K error is common and rarely triggers a code.
Read the full technical article →Industrial cooling systems
Which is more reliable
Both are mature. Screw machines tolerate abuse better and are simpler to service; centrifugal machines have fewer moving parts in the compressor but need surge protection and, in oil-fed designs, careful oil management.
Read the full technical article →Can a centrifugal run at 10% load
Most cannot without hot gas bypass, which wastes energy. Below 20%–30%, a smaller machine or a screw is the better answer.
Read the full technical article →Is a magnetic bearing chiller worth the premium
Where maintenance access is difficult, where oil contamination is unacceptable, or where part-load efficiency is the priority. The premium is typically 15%–30% and is recovered through efficiency and maintenance.
Read the full technical article →How does refrigerant choice affect the decision
Large centrifugal machines historically used low-pressure refrigerants; modern designs use HFCs or HFOs with different charge sizes and safety classifications. Check the charge against local refrigerant regulations.
Read the full technical article →Sludge drying systems
Is it safe to dry solvent-bearing sludge
Only with the right precautions. A closed-loop heat pump dryer at 60–70 °C stays below the flash point of most solvents, but the air loop must be monitored for LEL, and the electrical equipment in the dryer hall must be rated for the zone. Where solvent content is significant, an inert-gas or ATEX-rated arrangement is required, and that is a different machine.
Read the full technical article →How do I know whether drying will pay back
Divide the disposal saving per day by the net daily cost of drying. The disposal saving is the reduction in wet mass multiplied by the gate fee; the drying cost is the specific energy multiplied by the water evaporated and the electricity price, plus maintenance at 3%–5% of capital a year.
Read the full technical article →Can the dried cake be incinerated on site
Sometimes, and it is worth checking: at 35% moisture the calorific value is typically 6–9 MJ/kg, which can support combustion with auxiliary fuel. Whether the permit allows on-site incineration is a separate question.
Read the full technical article →What material should the belt be
316L where chlorides exceed 200 mg/L, 304 otherwise. Titanium is used for very high chloride or low pH, at 2.5–3 times the cost of 316L.
Read the full technical article →