Step 1 — Establish daily hot water demand
Demand is the product of the number of users and a per-capita consumption figure, adjusted for the application. Published figures vary widely between sources, so the number matters less than being explicit about which one you used.
| Application | Typical consumption | Note |
|---|---|---|
| Hotel, 3-star and above | 100–160 L per room per day | Higher with bathtubs and laundry |
| Guesthouse / inn | 60–100 L per room per day | Occupancy variation is large |
| School dormitory | 40–80 L per student per day | Concentrated into fixed shower windows |
| Factory dormitory | 50–80 L per worker per day | Shift pattern drives the peak |
| Hospital ward | 100–200 L per bed per day | Includes staff and cleaning loads |
| Office / canteen | 10–20 L per person per day | Small, but peaks at lunch |
| Swimming pool | Heat loss, not consumption | See pool heating sizing |
Two adjustments are usually needed: an occupancy or simultaneity factor (rarely is every room occupied at once), and an allowance for pipe losses, which can add 5%–15% in a large distribution network.
Step 2 — Convert daily demand into peak-hour demand
Storage volume is sized on the peak, not the daily total. The peak-hour factor is the share of daily demand drawn in the busiest hour.
| Application | Peak-hour factor | Consequence |
|---|---|---|
| Hotel, 24-hour occupancy | 10%–15% of daily | Moderate storage, continuous generation |
| School, fixed shower window | 25%–35% of daily | Large storage, short generation window |
| Factory, shift change | 20%–30% of daily | Large storage, staged units |
| Sports facility | 30%–40% of daily | Storage dominated |
If 30% of daily demand arrives in one hour, a tank that holds only 20% of the daily volume will run cold regardless of how many heat pumps are installed.
Step 3 — Calculate daily energy, not daily volume
The energy needed to raise water temperature is:
Q (kWh) = V (tonnes) × ΔT (K) × 1.163
That constant comes from water’s specific heat: 4.187 kJ/kg·K ÷ 3,600. For 1 tonne of water heated from 15 °C to 55 °C, ΔT is 40 K, so Q = 46.5 kWh. This figure is the backbone of every sizing calculation that follows.
Step 4 — Size heating capacity with an ambient correction
Dividing daily energy by available heating hours gives the required capacity at design conditions. Nominal capacity, however, is quoted at a standard ambient condition — usually 20 °C dry bulb — and real capacity falls as the air gets colder.
| Ambient temperature | Indicative capacity factor | Note |
|---|---|---|
| 20 °C | 1.00 | Nominal rating point |
| 7 °C | 0.80–0.90 | Typical winter day, mild climate |
| 0 °C | 0.65–0.80 | Frost cycles begin |
| −7 °C | 0.50–0.65 | Standard models lose a large share of output |
| −15 °C | 0.35–0.50 | Enhanced vapor injection models perform better here |
The factors are indicative and differ between models. Always ask for the manufacturer’s capacity table at the actual design ambient temperature, and size on that number rather than on the nominal figure.
Step 5 — Set the storage tank volume
Tank volume must cover the peak draw-off that the heat pumps cannot generate in real time, plus a margin.
| Situation | Tank as % of daily volume |
|---|---|
| Continuous demand, 24-hour operation | 25%–35% |
| Two to three demand peaks per day | 35%–50% |
| Single concentrated peak (school, factory shift) | 50%–70% |
| Intermittent use, long recovery time available | 70%–100% |
A tank that is too small causes cold-water complaints at exactly the moment the building notices. A tank that is too large adds standing losses, structural load and capital cost. The peak-hour factor from Step 2 is the input that resolves the trade-off.
Step 6 — Check what the site will actually accept
Three constraints kill otherwise sound designs: power supply, physical space, and noise.
- Power: a 10 HP (about 7.5 kW input) commercial unit needs a three-phase supply; confirm the available capacity at the distribution board rather than assuming it.
- Space: inlet and outlet clearances, maintenance access, and a structural check for the loaded tank — water is 1 tonne per cubic meter.
- Noise: units placed next to guest rooms or bedrooms need vibration isolation and, sometimes, acoustic screening.
Worked example: 100-person dormitory
| Item | Value | Basis |
|---|---|---|
| Occupants | 100 students | Given |
| Consumption | 60 L/person/day | Mid-range for dormitory |
| Daily volume | 6.0 t | 100 × 60 L |
| Inlet / outlet | 15 °C / 55 °C | Mains water, standard setpoint |
| Daily energy | 279 kWh | 6.0 × 40 × 1.163 |
| Available heating hours | 14 h | Overnight plus daytime top-up |
| Required capacity at design ambient | 20 kW | 279 ÷ 14 |
| Design ambient | −2 °C | Local winter condition |
| Correction factor at −2 °C | 0.72 | Indicative |
| Required nominal capacity | 27.8 kW | 20 ÷ 0.72 |
| Units selected | 2 × 15 kW nominal | Parallel, staged, N+1 partial |
| Tank volume | 3.0 t | 50% of daily volume |
Note what the correction factor did: it raised the nominal requirement by nearly 40%. A designer who skipped Step 4 would have specified 20 kW of nominal capacity and delivered a system that runs short in the coldest month.
Common sizing errors
| Error | Consequence | Fix |
|---|---|---|
| Sizing on daily average flow | Cold water at peak | Use peak-hour factor for storage |
| Using nominal capacity at design ambient | Undersized in winter | Apply the manufacturer’s low-temperature table |
| Ignoring pipe losses | Slight but systematic shortfall | Add 5%–15% for distribution |
| Oversizing “for safety” | Higher capital cost, more cycling, lower efficiency | Size on data, then verify with a second method |
| Ignoring the existing tank | Paying twice for storage | Survey what is already installed |
Frequently asked questions
How much margin should I add?
Add margin where uncertainty is real — unknown occupancy, unknown inlet temperature — and state it. A blanket 20% added to a well-surveyed project usually buys cycling losses rather than reliability.
Can I size from the number of showers instead of liters per person?
Yes, and it is often more accurate for gyms and factories. A shower at 8–10 L/min for 8 minutes is roughly 70 L; multiply by the number of simultaneous users.
Does a larger tank reduce running cost?
Usually yes, up to a point: it lets the heat pump run in the efficient part of the day and reduces start-stop cycling. Beyond the peak requirement, extra volume only adds standing loss.
What if the building has an existing electric boiler?
Keep it as backup and size the heat pump for the base load, or for full load with the boiler as a peak top-up. Hybrid arrangements are common and often the most economic retrofit.
How do I confirm the design after installation?
Measure supply and return temperatures, flow rate and power draw during a representative peak. If measured recovery time exceeds the design value, the ambient correction or the peak factor was wrong.
Is 55 °C enough for a hotel?
For most domestic hot water systems yes, provided the distribution loop is designed for it. Where legionella control requires higher storage temperatures, store at 60 °C and blend down at the point of use.
Longkang Environmental Equipment Co., Ltd. issues sizing sheets with the assumptions stated in writing — ambient condition, inlet temperature, peak factor and heating hours — so the design can be checked rather than trusted. Phone: +86 400-878-0280 | +86 130-0200-1280
Related reading
- Air-source heat pump water heater product page
- How to calculate hot water demand
- Matching heat pump capacity to tank volume
- Commercial versus residential heat pump water heaters