Sound power and sound pressure are not the same number
Catalogs quote either sound power level (Lw) or sound pressure level (Lp). The difference matters: a unit with Lw 78 dB(A) produces roughly 65 dB(A) at 1 m in free field, and only 55 dB(A) at 4 m. Always check which figure a datasheet uses before comparing two machines, and insist on the measurement standard.
| Distance from unit | Level if 65 dB(A) at 1 m | Typical comparison |
|---|---|---|
| 1 m | 65 dB(A) | Normal conversation at close range |
| 3 m | 56 dB(A) | Quiet office |
| 5 m | 51 dB(A) | Suburban street at night |
| 10 m | 42 dB(A) | Library |
| 20 m | 36 dB(A) | Quiet bedroom at night |
| 40 m | 30 dB(A) | Background in a rural area |
In a courtyard or between two buildings, reflections add 3–6 dB(A) to every figure above, which is why the same unit can be acceptable on an open roof and unacceptable in an air well.
Where the noise actually comes from
| Source | Character | Share of total | What reduces it |
|---|---|---|---|
| Compressor | Low frequency 50–200 Hz, tonal | 40%–55% | Anti-vibration mounts, acoustic blanket, inverter drive |
| Axial fan and blade passing | Broadband with a tone at blade-pass frequency | 25%–35% | Lower fan speed, larger slower fan, ECM motor, night mode |
| Airflow and turbulence at the coil | Broadband “whoosh” | 10%–20% | Ducted inlet/outlet, clearance from walls |
| Casing vibration | Structure-borne | 5%–15% | Stiffened panels, resilient mounts, flexible pipe connectors |
| Defrost and reversing valve | Intermittent click and hiss | Occasional | Correct charge, valve maintenance |
Low-frequency compressor noise is the hardest to treat after installation, because it travels through structure rather than air. Getting the mounts and the structural connection right at the design stage is far cheaper than fixing it later.
The measures, in order of cost-effectiveness
| Measure | Typical reduction | Cost | Comment |
|---|---|---|---|
| Move the unit from a corner to an open position | 3–8 dB(A) at the boundary | Low | Removes reflection and recirculation at once |
| Anti-vibration mounts plus flexible connectors | 3–6 dB(A) structure-borne | Low | Essential on roofs and upper floors |
| Correct clearance: 1 m inlet, 3 m discharge | 2–5 dB(A), plus COP recovery | Low | Also fixes short-circuit of hot air |
| Night mode, lower fan speed | 3–6 dB(A) | Free | Small capacity penalty, usually acceptable at night |
| Inverter-driven fans and compressor | 4–8 dB(A) at part load | +10%–18% equipment | Pays back in energy as well |
| Acoustic enclosure or louvred screen | 8–15 dB(A) | Moderate | Must not restrict airflow; design with the supplier |
| Barrier wall between unit and receptor | 5–12 dB(A) | Moderate | Height and mass decide the result |
| Relocate to a plant room with intake/discharge ducts | 15–25 dB(A) at the receptor | High | Suited to hospitals and city hotels |
A common mistake is to build a solid box around the unit. That reduces the noise at one point and destroys the airflow, which reduces capacity and increases run time — often making the perceived noise worse because the unit runs at full speed for longer.
What the regulations expect
Most jurisdictions set a limit at the nearest sensitive receptor, not at the unit. In China, GB 22337 sets social-life environmental noise limits that commonly work out to about 55 dB(A) by day and 45 dB(A) by night at the boundary of a residential area; in the UK, BS 4142 compares the rating level with the background; EU member states set their own night limits, often 40–45 dB(A) at the facade. Always check the local authority’s requirement, and measure the background level before designing — a unit that is 5 dB(A) above a quiet rural background is a complaint, while 5 dB(A) above a city-center background is not.
A practical design check: subtract 6 dB(A) for every doubling of distance from 1 m, add 3 dB(A) if the unit is against a wall, and compare the result with the limit at the receptor. If the margin is under 3 dB(A), add a measure.
Sitting and installation checklist
- Keep 1 m clear at the intake and 3 m at the discharge; never face two units at each other.
- Do not install directly below or beside a bedroom window, even on a different floor — structure-borne noise travels.
- On a roof, mount on a concrete plinth or a steel frame with resilient pads; never bolt directly to profiled decking.
- Use flexible braided connectors on the water pipes and a flexible conduit on the cable.
- Avoid mounting on a lightweight partition wall shared with a habitable room.
- If a screen is used, leave the same free area as the unit’s coil face and keep the screen at least 1 m away.
Frequently asked questions
How loud is a unit at a neighboring window?
Take the 1 m figure, subtract 6 dB(A) per doubling of distance, add 3 dB(A) if there is a reflecting wall, and subtract any barrier attenuation. A 65 dB(A) unit 8 m from a window with no barrier gives about 47 dB(A) — above a typical 45 dB(A) night limit, which means a measure is needed.
Can I install a unit on a balcony?
Only if the balcony is open on at least two sides and the discharge does not blow into the flat or into the neighbor’s balcony. Enclosed balconies recirculate hot air, which raises the condensing temperature, cuts capacity and increases noise. Most manufacturers will not warrant a unit installed in an enclosed space.
Does night mode reduce capacity?
Yes, typically by 10%–20% of fan speed and a few percent of capacity. In a system with adequate storage this is invisible to the user, because the tank carries the night load. It is only a problem when the unit is already marginal on capacity.
Is the unit noisier in winter?
Usually yes, for two reasons: the fan runs at higher speed to keep the coil clear of frost, and defrost cycles add intermittent reversing-valve noise. A unit that is acceptable in summer can be 3–5 dB(A) louder on a cold, humid night.
Will an acoustic enclosure overheat the unit?
It will if it is designed as a box. A proper acoustic enclosure is a flow path: intake plenum, lined baffle, discharge duct sized for the unit’s airflow, with the pressure drop checked against the fan curve. Ask the supplier for the enclosure pressure drop and the resulting capacity correction.
What should be in the contract about noise?
A contracted sound pressure level at a stated distance and measurement standard, the test conditions, and the remedy if the guarantee is missed. Without a stated distance and standard, a “low noise” claim cannot be enforced.