Classify the fault before opening the panel

Pattern Category First place to look
Alarm at start, nothing runs Interlock or supply E-stop, door switch, phase
Runs, but no drying Airflow or refrigerant Filter, fan, coil, charge
Product too wet, temperature normal Residence time or feed rate Feed rate, belt speed
Product too dry, energy high Control or humidity sensor Humidity sensor, setpoint
Alarm after hours of running Heat build-up or blockage Coil, filter, condensate
Random alarms Wiring or sensor drift Screens, sensor comparison

High temperature

Cause Confirm by Action
Low airflow Filter differential high, fan current low Clean filter, check belt
Fan failure Fan not turning, alarm on VFD Repair or replace
Overcharge or hot gas valve stuck Discharge pressure high Check charge, valve
Feed stopped, chamber empty Feed motor fault, hopper bridging Restore feed
Sensor error Independent thermometer disagrees Replace sensor

High temperature with an empty chamber is common after a feed blockage: the dryer keeps heating air with nothing to evaporate. The feed alarm should stop the compressor, and if it does not, that interlock is the real fault.

Low temperature / no heating

Cause Confirm by Action
Compressor not running Contactor, overload, code Electrical check
Low refrigerant charge Subcooling low, suction low Leak test and recharge
Defrost stuck Coil iced, defrost sensor Check sensor and valve
Air leak into the chamber Cold spot at a seal, humidity low Seal test
Ambient too low Room below 5 °C Heat the space

A dryer that cannot reach temperature in winter is often not faulty: it is losing heat through an uninsulated chamber or an open door. Check the envelope before the refrigerant.

Airflow and fan faults

Alarm Cause Check
Fan overload Belt too tight, bearing seized, blockage Belt tension, bearing, duct
Low differential pressure Belt broken, fan eroded, damper closed Belt, impeller, damper
High differential pressure Filter blocked, duct crushed Filter, duct route
VFD fault Overcurrent, overheat, earth fault Motor insulation, heatsink

Fans in sludge service erode. If the impeller is worn, the airflow falls gradually and nobody notices until the capacity is 20% down. Inspect the impeller annually.

Compressor and refrigeration faults

Code type Meaning Check
High pressure Condensing pressure above limit Coil, fan, charge, ambient
Low pressure Suction below limit Charge, restriction, low load
Overload Current above limit Voltage, winding, mechanical
High discharge temperature Above 95 °C Charge, airflow, sensor
Oil pressure Below limit Oil level, heater, pump
Defrost fault Cycle not completing Sensor, valve, timer

The coil in a sludge dryer fouls faster than in any other application. A high-pressure alarm on a dryer is a coil-cleaning alarm until proven otherwise.

Condensate faults

Symptom Cause Action
High level alarm Pump failed, strainer blocked, drain blocked Clean, test pump
Water in the chamber Tray overflow, trap failed Clear, replace trap
Odor in the plant room Trap dry or bypassed Refill, repair trap
Condensate cloudy with solids Carry-over from the chamber Check airflow and feed

Condensate is the second-largest output of the process after dried product. If it is not removed reliably, the plant stops.

Feed and discharge faults

Alarm Cause Action
Feed overload Oversized object, wet cake, blockage Metal detection, reduce rate
Hopper bridging Angle, moisture, polymer dose Agitator, angle, dose review
Discharge blockage Product too wet, chute too narrow Moisture check, widen
Belt misalignment Uneven feed, roller Center feed, adjust
Emergency stop Operator action or faulty circuit Investigate before reset

Sensors and communication

Symptom Cause Check
Humidity reads 100% constantly Condensate on the sensor Relocate, dry, recalibrate
Temperature offset by a fixed amount Sensor drift Compare, replace
Controller offline Supply, cable, address 24 V, continuity, DIP
BMS value frozen Communication timeout Cable, termination

A humidity sensor coated with condensate is the most common cause of a dryer producing over-dry product: the controller believes the air is saturated and keeps drying. Clean the sensor at every service.

A sequence that works

  1. Read the alarm with the timestamp and the operating state.
  2. Check the material path: hopper, feeder, chamber, discharge.
  3. Check the air path: filter, fan, duct, seals.
  4. Check the condensate path: tray, trap, pump.
  5. Check the refrigerant only after the first four.
  6. Record the readings before and after the repair.
Measurement Normal Points to
Chamber temperature 40–75 °C per setting Control or airflow
Exhaust humidity Falling as product dries Sensor or airflow
Filter differential Below the marked limit Filter
Compressor current Below FLA Charge or mechanical
Condensate flow Roughly equal to evaporation Blockage or carry-over

Longkang Environmental Equipment Co., Ltd. supplies a fault table matched to the controller fitted to each unit, because the same code number is not used consistently across generations. Phone: +86 400-878-0280 | +86 130-0200-1280

Questions from maintenance engineers

Why does the dryer trip on high pressure after a filter change?

A new filter fitted with the wrong orientation, or a plastic wrapper left inside, restricts airflow. Check the differential pressure and the airflow direction arrow.

The product is too dry and the energy has gone up. Why?

Usually the humidity sensor. If it reads high, the controller keeps drying. Clean or replace the sensor and re-check the setpoint.

Can I run the dryer with the condensate pump failed?

For a few hours, if the tray is monitored and emptied manually. Overnight, no: the chamber will flood and the insulation will be ruined.

What causes ice on the heat pump coil?

Low refrigerant charge, a defrost sensor fault, or operation below the rated ambient. Ice on the coil lowers capacity and eventually stops the machine.

How do I clear a blocked discharge chute?

Stop the feed, let the chamber cool, isolate the conveyor, and clear from the access hatch with the correct tool. Never reach into a running conveyor, and never use a hose on an energised panel.

How many alarms before I call a service engineer?

One alarm with a clear cause, such as a blocked filter, can be handled in-house. Three alarms of the same type in a week, or any oil pressure or compressor alarm, warrants a service visit.