The formula
Electricity (kWh) = volume (t) × ΔT (K) × 1.163 ÷ COP
The 1.163 factor converts tonne-kelvin into kilowatt-hours. For a 40 K rise and a COP of 4, the result is 11.6 kWh per tonne; at a COP of 3, it is 15.5 kWh.
| COP during operation | kWh per tonne (40 K rise) | Note |
|---|---|---|
| 4.5 | 10.3 | Mild weather, good installation |
| 4.0 | 11.6 | Typical annual average |
| 3.5 | 13.3 | Cool climate, hard water |
| 3.0 | 15.5 | Cold weather, high water temperature |
| 2.5 | 18.6 | Severe cold, poorly maintained unit |
Worked examples
Hotel, 60 rooms. Daily volume 7.2 t, COP 4.0: 7.2 × 40 × 1.163 ÷ 4 = 84 kWh/day. Over a month, about 2,500 kWh.
School dormitory, 500 students. Daily volume 30 t, COP 4.0: 30 × 40 × 1.163 ÷ 4 = 349 kWh/day. Months of operation matter more than the daily figure — a school running 200 days a year uses about 70,000 kWh annually.
Factory shower block, 300 workers. Daily volume 18 t, COP 3.8: 18 × 40 × 1.163 ÷ 3.8 = 220 kWh/day.
| Application | Daily volume | COP | kWh/day | kWh/month |
|---|---|---|---|---|
| Guesthouse, 20 rooms | 2.4 t | 4.0 | 28 | 840 |
| Hotel, 60 rooms | 7.2 t | 4.0 | 84 | 2,520 |
| Hotel, 150 rooms | 18 t | 3.9 | 215 | 6,450 |
| Dormitory, 100 students | 6.0 t | 4.0 | 70 | 2,100 |
| Dormitory, 500 students | 30 t | 4.0 | 349 | 10,470 |
| Factory, 300 workers | 18 t | 3.8 | 220 | 6,600 |
What actually drives the number up
Cold inlet water. Mains water at 5 °C instead of 15 °C raises ΔT from 40 K to 50 K — a 25% increase in energy for the same volume.
Low ambient temperature. COP falls as the air gets colder. A unit at COP 4.0 in October may run at 2.8 in January, and the same hot water then costs 40% more.
Higher setpoint. Storing at 60 °C instead of 55 °C adds 5 K to every liter heated, about 12% more energy, plus higher standing losses.
Scaling and fouling. A scaled condenser or heat exchanger reduces heat transfer, lowers COP and lengthens run times. In hard-water areas this can cost 10%–20% within two or three years if the coil is never cleaned.
Standing losses. An uninsulated tank and long uninsulated pipe runs lose heat continuously. In a hotel with low night occupancy this can be 10%–15% of daily energy.
Short cycling. Oversized capacity relative to storage causes frequent start-stop, each with an efficiency penalty. Correct tank sizing is an energy measure, not just a comfort measure.
How to cut consumption without changing equipment
| Measure | Typical saving | Cost |
|---|---|---|
| Insulate tank and hot pipework | 5%–15% | Low |
| Clean the heat exchanger annually | 5%–15% (where fouled) | Low |
| Lower setpoint from 60 °C to 55 °C | 8%–12% | None |
| Shift heating to off-peak tariff hours | 20%–40% of cost, not energy | None with a timer |
| Fix leaks and dripping taps | 3%–10% | Low |
| Add a mixing valve and store hotter, draw less | 5%–10% | Moderate |
| Correct over-sizing by adding storage | 3%–8% | Moderate |
The last item surprises people: adding a tank can reduce electricity, because it lets the heat pump run in longer, more efficient blocks instead of cycling.
Comparing with alternatives
| System | Energy per tonne (40 K) | Relative cost |
|---|---|---|
| Electric resistance | 46.5 kWh | Highest |
| Gas boiler (85% efficiency) | 54.7 kWh gas equivalent | Tariff dependent |
| Air-source heat pump at COP 4.0 | 11.6 kWh | Lowest in most tariffs |
| Solar thermal with electric backup | Variable | Lowest where sun is reliable |
Frequently asked questions
How many kWh does a household unit use?
A family of four using 200 L a day needs about 2.3 kWh at COP 4.0 — roughly 70 kWh a month, or a third of what an electric resistance heater would use.
Can I estimate from the electricity bill?
Yes. If the heat pump is on a dedicated meter, divide the monthly kWh by the monthly hot water volume to get kWh per tonne, then compare with the 11–15 kWh benchmark to see whether the unit is performing.
Why is my consumption higher in winter?
Two reasons: colder inlet water and lower COP. Both increase energy per liter, and they compound. Winter consumption is often 30%–50% higher than summer for the same volume.
Does the unit consume power when idle?
Only for controls and, on some models, a crankcase heater — typically 20–80 W. Over a month that is 15–60 kWh, worth switching to a lower-power standby mode if the building has long vacant periods.
Is a higher COP always lower consumption?
At the same conditions, yes. Across conditions, a unit with a modest rated COP that holds up well in cold weather can beat one with a high nominal COP that collapses at 0 °C.
How do I verify the COP after installation?
Measure the electrical input and the water flow and temperature rise simultaneously. COP = (flow × ΔT × 1.163) ÷ electrical input. Do it on a mild day and a cold day to see the range.
Longkang Environmental Equipment Co., Ltd. supplies units with measured performance at handover — flow, temperature rise and power draw recorded on site — so the electricity figure is verified rather than assumed. Phone: +86 400-878-0280 | +86 130-0200-1280