The heat pump only ever sees the water the operator produces. Twenty answers on the parameters that matter to the machine, and on the operating habits that keep them in band.
| Parameter | Typical band | Effect on the unit |
|---|---|---|
| Free chlorine | 1–3 mg/L public pool | Corrosion of the wrong alloys |
| pH | 7.2–7.8 | Scale above, metal attack below |
| Total alkalinity | 80–120 mg/L as CaCO3 | pH stability |
| Calcium hardness | 200–400 mg/L | Scaling risk at the exchanger |
1. Chemistry the machine cares about
Q1. What free chlorine level should be held?
Typically 1–3 mg/L in a public pool, according to the local code and bather load, with combined chlorine kept as low as practical. More free chlorine does not compensate for missing water exchange.
Q2. Why does pH matter to a heat pump?
Low pH attacks the passivating film on metals and degrades coatings; high pH precipitates calcium carbonate and scales the exchanger. The 7.2–7.8 band protects both the pool and the machine.
Q3. Why does the exchanger scale so readily?
Warm water plus hardness plus a pH above band precipitates salts on the hottest surface, which is the exchanger. Scale adds thermal resistance and traps chlorides, so the corrosion rate rises under the deposit.
Q4. Does water chemistry affect capacity or just life?
Both. Scale removes heat transfer immediately, so capacity falls and head pressure rises; corrosion removes wall thickness over years. The first is measurable in weeks, the second in seasons.
Q5. Is high water temperature worse for scaling?
Yes. Spa and hot-spring duties at 38–42 °C scale faster than competition pools at 27 °C, which is why cleaning intervals and water treatment are tighter in that segment.
2. Filtration, strainers and salt
Q6. What filtration rate should the sand filter run at?
Within the manufacturer’s stated band — commonly around 15–25 m/h for sand — because faster filtration removes less and backwashes more often. The heat pump cares because filtration protects its exchanger.
Q7. What strainer mesh belongs before the heat pump?
Fine enough to protect the tubes, coarse enough not to blind weekly: typically 0.5–1 mm, in a body that can be opened and cleaned without disturbing the circuit.
Q8. Does backwashing affect the heat pump?
It can: backwash changes flow, drops level and introduces air. The unit should be interlocked to stop or unload during backwash, and the air vent at the high point should be working.
Q9. What is different about a salt-chlorinator pool?
Chloride is continuously generated and present, so pH discipline matters more, the air side corrodes faster, and the material package should be specified for salt from the start.
Q10. Is a sea-water pool the same as a salt-chlorinator pool?
No. Sea water is far more conductive and carries other ions; the exchanger needs the highest grade available and the plant room needs a full corrosion package with a wash-down regime.
Q11. Where should dosing points sit relative to the heat pump?
Upstream of the pool, never immediately at the heat pump inlet: concentrated acid or chlorine passing through the exchanger is the fastest way to destroy it. A dosing point close to the unit is a design error.
3. Water quality and efficiency
Q11. Does algae recurring in the pool indicate a heat pump problem?
No, but it indicates a water problem that becomes a machine problem: algae raises chlorine demand and organic load, biofilm forms on the exchanger, and efficiency drops.
Q12. Can poor water quality really raise electricity consumption?
Yes, measurably. A scaled exchanger and a loaded filter increase pressure drop and reduce heat transfer, so the compressor runs longer for the same delivered heat, and flow protection may start tripping.
Q13. What is a combined water-treatment and heating unit?
A packaged plant combining filtration, disinfection, heating and sometimes dehumidification in one hydraulic arrangement. It simplifies interfaces at the cost of flexibility per subsystem.
Q14. How should dosing and the heat pump be interlocked?
Through flow and time: dosing only with proven circulation, and the heat pump inhibited while a concentrated dose is passing. Simple interlocks prevent most exchanger damage.
Q15. Do iron and manganese in make-up water matter?
Very much: they precipitate as deposits at the exchanger, are difficult to remove, and support biofilm. Pre-treatment or a different water source is the answer, not more cleaning.
4. Records and operating discipline
Q16. Does make-up water quality affect the heat pump?
It sets the scaling and corrosion baseline for everything in the circuit. A pool topped up with hard or iron-bearing water will foul the exchanger faster than its treatment regime suggests.
Q17. What should the water log record?
Free and combined chlorine, pH, alkalinity, hardness, temperature, make-up volume, and backwash dates. The log is what turns a fault from a mystery into a trend.
Q18. How often should chemistry be tested?
Daily for chlorine and pH in a commercial pool, weekly for alkalinity and hardness, and after any event that loads the pool heavily. Domestic pools can run less frequently but not less carefully.
Q19. How is a scaled exchanger detected early?
By differential pressure across it at constant flow, and by a falling water-side temperature rise. Both are cheap to trend and both precede any alarm.
Q20. Can scaling be reversed?
Light scale can be removed by circulation cleaning with an appropriate agent under the exchanger supplier’s instructions. Heavy scale on a plate pack may not be recoverable, which is why detection matters.
Q21. What is the single most effective water habit?
Holding pH in band. It protects the pool, the structure and the machine in one action, and it is the cheapest maintenance item on site.
Q22. Is a circulation turnover requirement part of water quality?
Yes: turnover sets how quickly the pool clears contamination, and it also guarantees the flow the heat pump needs. Both requirements point the same way, which is why flow and filtration are designed together.