Read the noise before opening the panel
| Sound | Most likely cause | First check |
|---|---|---|
| Metallic knocking, rhythmic | Liquid slugging, oil dilution | Superheat, crankcase heater, expansion valve |
| Continuous rattle at start and stop | Loose mounting, worn resilient pads | Mounting bolts and pads |
| High-pitched whine rising with load | Bearing wear or low oil | Oil level, oil pressure, oil color |
| Loud hum, compressor not starting | Single phasing, contactor, capacitor (single-phase) | Voltage on all three phases |
| Clicking then trip | Contactor chatter, control voltage dip | Control circuit voltage, contactor contacts |
| Hissing at the shell joints | Refrigerant leak | Leak detector |
| Screech from the coupling area | Coupling wear (open-drive machines) | Coupling alignment and element |
A screw compressor that has ingested liquid sounds like gravel in the housing and will damage the rotors within minutes. Stop it immediately; do not “run it clear”.
Overload trips: the six causes
| Cause | Signature | Test |
|---|---|---|
| High condensing pressure | Current high at high ambient or with a fouled condenser | Condenser approach, cooling water temperature |
| Overcharge | High current, high subcooling, high discharge pressure | Subcooling, weigh-in charge |
| Low supply voltage | Current high, contactor buzzing, other equipment affected | Voltage at the terminals under load |
| Phase loss or imbalance | Compressor will not start, or trips instantly | Voltage and current on each phase |
| Winding insulation failure | Trips after a few minutes, smell of varnish | Insulation resistance to earth |
| Control or protection fault | Trips with normal current | Compare displayed current with a clamp meter |
A useful rule: if the measured current is within the nameplate full-load amps and the overload still trips, the protection module or the contactor is the problem, not the compressor.
The current check that saves hours
Measure current on all three phases with the machine at steady load:
| Reading | Interpretation |
|---|---|
| All three within 5% of each other and below FLA | Electrically healthy; look at refrigerant and protection |
| One phase 10%–20% different | Supply imbalance or a contactor contact burning |
| All three 10%–15% above FLA | High load: condensing pressure, overcharge, or mechanical drag |
| Current rises steadily over minutes then trips | Winding heating, or increasing mechanical friction |
| Current spikes at start then normal | Normal for direct-on-line; check start time against the limit |
Voltage imbalance matters more than people expect: a 3% voltage imbalance can produce a 10%–15% current imbalance and a winding temperature rise of 20 K, which is enough to shorten motor life dramatically.
Liquid slugging and why it happens
Liquid refrigerant returning to the compressor washes oil off the bearings and can break valves. It happens when:
- Superheat is set too low, so the expansion valve feeds more than the evaporator can boil off.
- The crankcase heater is failed, so refrigerant condenses in the oil during shutdown.
- The evaporator is starved of load — low water flow or a very low load — while the valve stays open.
- A defrost or hot-gas bypass cycle is not properly timed.
Check superheat at the evaporator outlet: 5–8 K is normal. Below 3 K is a slugging risk; above 12 K means the evaporator is starved and the machine is losing capacity.
Cooling capacity after the repair
Compressor replacement is expensive enough that the cause must be fixed first:
| Failure mode | Underlying cause to fix | Consequence if not fixed |
|---|---|---|
| Valve plate broken | Liquid slugging | New compressor fails within months |
| Bearings worn | Oil starvation, low oil pressure | Second failure |
| Motor winding burnt | Voltage imbalance, single phasing, short cycling | Repeat burnout |
| Rotor contact damage (screw) | Liquid ingestion | Rotor and housing damage |
Electrical safety
All electrical checks on the compressor circuit must be done by a qualified electrician with the machine isolated and locked out, and with the capacitor discharged where fitted. Insulation resistance is measured with the compressor disconnected from the drive; a reading below 1 MΩ suggests moisture or winding degradation and needs investigation before re-energising.
Frequently asked questions
Is some compressor noise normal?
Yes. A screw compressor has a characteristic hum and a scroll a smooth whine; both are steady and change only with load. Any new knocking, rattling or metallic sound is not normal and should be investigated the same day.
Can I run the chiller with the overload bypassed?
No. The overload protects the winding from a fault that will otherwise destroy it. Bypassing it converts a repairable problem into a compressor replacement.
Why does it trip only on hot afternoons?
High ambient raises the condensing pressure, which raises the current. If the condenser is already fouled or the cooling tower is marginal, the current crosses the protection threshold only on the hottest days.
How do I know if it is the compressor or the contactor?
Compare the clamp-meter reading with the controller’s displayed current. If they agree and are below FLA, the compressor is drawing normal current and the trip is in the protection circuit or the contactor. If the contactor is pitted or buzzing, replace it.
Does a low refrigerant charge cause overload?
It usually lowers the current rather than raising it, because the compressor is moving less mass. A low charge shows as low suction pressure and high superheat, sometimes with overheating — a different failure mode from an overload trip.
When should the compressor be replaced rather than repaired?
When insulation resistance is below 1 MΩ, when there is mechanical damage to the rotors or valves, or when the machine is more than 12 years old and a second failure is likely. For a semi-hermetic machine, valve plates and bearings can be replaced in situ.
Longkang Environmental Equipment Co., Ltd. records compressor current, superheat and approach at commissioning and supplies the protection setpoints in the manual, so an overload trip can be compared with measured baseline values instead of guessed at. Phone: +86 400-878-0280 | +86 130-0200-1280