The pressure tells you the evaporating temperature
| Refrigerant | Evaporating temp | Pressure, absolute | Condition |
|---|---|---|---|
| R134a | 10 °C | 0.41 MPa | High load, warm chilled water |
| R134a | 5 °C | 0.35 MPa | Normal for 7 °C leaving water |
| R134a | 0 °C | 0.29 MPa | Low load or low setpoint |
| R134a | −5 °C | 0.24 MPa | Investigate |
| R134a | −10 °C | 0.20 MPa | Cut-out range |
| R410A | 5 °C | 0.93 MPa | Normal for 7 °C leaving water |
| R410A | −10 °C | 0.57 MPa | Cut-out range |
If the unit trips at an evaporating temperature well above the cut-out, suspect the transducer or the low-pressure switch rather than the circuit.
The evaporator approach is the key measurement
Evaporator approach = leaving chilled water temperature − evaporating temperature.
A clean evaporator runs at 1–2 K approach. Above 4 K, either the tubes are fouled or the flow is low; the machine is already working harder for the same output, and the low-pressure trip is the second symptom rather than the first.
The five causes
| Cause | Signature | Confirm by | Fix |
|---|---|---|---|
| Refrigerant leak | Low pressure at any load, high superheat, bubbles in the sight glass | Leak detection, standing pressure | Repair, evacuate, recharge by weight |
| Low chilled water flow | Approach high, ΔT high, pump differential low | Flow measurement, strainer | Restore flow, clean strainer, set pump |
| Expansion valve fault | Low suction with normal charge, superheat wandering or fixed | Superheat at the valve outlet | Clean or replace the valve, adjust superheat |
| Low chilled water setpoint | Trips only at low load or at night | Compare setpoint with design | Raise setpoint or add a buffer tank |
| Restricted liquid line | Frost or temperature drop across the filter drier | Touch test, pressure drop | Replace the filter drier |
Why low load causes low pressure
At 20% load with a fixed-speed compressor, the evaporator has more surface than the load needs and the suction pressure falls until the cut-out opens. This is not a fault — it is a control problem, and it is the most common cause of night-time low-pressure trips on a plant sized for the design day.
Three fixes, in order of cost:
- Add a buffer tank of 5–10 L/kW so the chiller can run in longer blocks at higher load.
- Use a chiller with cylinder unloading or an inverter so capacity can follow the load down to 20%–25%.
- Raise the chilled water setpoint where the process allows, which lifts the evaporating temperature and removes the risk of freezing.
Protecting the evaporator
The real risk in a low-pressure event is a frozen evaporator: water freezes in the tubes, expands, and splits them. The repair is a tube replacement, and the machine is out of service for weeks.
| Protection | How it works | Check |
|---|---|---|
| Low-pressure cut-out | Stops the compressor before 0 °C evaporating | Setpoint and switch calibration |
| Anti-freeze thermostat | Stops the compressor on low leaving water temperature | Sensor position and setpoint |
| Flow switch | Prevents operation without flow | Test by closing the valve briefly |
| Freeze stat on the evaporator shell | Detects ice formation | Annual test |
| Water-side drain and heater | Protects an idle evaporator in winter | Operational check before winter |
A flow switch that has been bypassed, or one wired to a pump contactor rather than to a real flow sensor, is a common finding on retrofitted plants and the usual reason an evaporator freezes during a pump failure.
Diagnostic sequence
- Read the fault code and the pressure at trip; convert to temperature.
- Measure chilled water flow, entering and leaving temperatures, and calculate the approach.
- Check superheat at the evaporator outlet: 5–8 K is normal, above 12 K suggests undercharge or a restricted valve.
- Check the liquid line for a temperature drop across the filter drier.
- Leak-test before adding any refrigerant. Adding gas to a leaking system simply moves the problem a few weeks later.
Frequently asked questions
Can I just add refrigerant to clear the alarm?
Only as a temporary measure, and only after a leak search. A system that needed gas is a system with a leak, and topping it up repeatedly releases refrigerant and leaves the real fault in place.
Why does it trip only at night?
Because the load falls and the compressor’s capacity does not. It is a part-load control problem — a buffer tank, unloading or an inverter solves it, and simply raising the low-pressure cut-out setpoint does not.
How do I tell a leak from a restricted expansion valve?
Superheat. A leak gives high superheat everywhere and low subcooling. A restricted valve gives high superheat at the evaporator with normal subcooling and a pressure drop across the drier or the valve itself.
Can low water flow cause a low-pressure trip?
Yes, and it is the second most common cause. Low flow raises the evaporator approach, drops the evaporating temperature and can freeze the water in the tubes. Check the strainer and the pump before the refrigerant circuit.
What is a safe low-pressure cut-out setting?
It should sit above the freezing point of the chilled water with a margin — typically an evaporating temperature of −2 to 0 °C for a 7 °C system, never below −5 °C unless glycol is used.
Does glycol solve the problem?
It removes the freeze risk, at the cost of 5%–15% lower heat transfer and a larger pump duty. It is the right answer for low-temperature process duty, not a workaround for a badly controlled chiller.