Start with three measurements
Before opening any panel, record:
- Outlet water temperature and return water temperature at the unit.
- Water flow rate through the unit, from the pump curve or a clamp-on flow meter.
- Suction and discharge pressure, converted to evaporating and condensing temperature using the refrigerant’s pressure-temperature chart.
From these you can compute the three numbers that matter:
| Metric | Formula | Normal | What an abnormal value means |
|---|---|---|---|
| Water-side ΔT | Outlet − return | 4–6 K at design flow | Low ΔT: flow too high, or capacity low |
| Condensing approach | Condensing temp − outlet water temp | 3–5 K | Above 8 K: scale or fouling in the condenser |
| Superheat | Suction temp − evaporating temp | 5–8 K | High: undercharge or blocked expansion valve |
The six causes, in the order to check them
| # | Cause | Tell-tale sign | Check | Fix |
|---|---|---|---|---|
| 1 | Setting or mode | Unit stops at a lower temperature than expected | Read the setpoint and any timer or economy mode | Correct the setpoint; check the time schedule |
| 2 | Water flow | ΔT above 8 K, high discharge pressure, unit cycling on protection | Compare pump curve with design flow | Set the pump to the design duty; clear a blocked strainer; open a throttled valve |
| 3 | Frost or blocked coil | Low suction pressure, ice visible, fan running hard | Visual check of the coil and the discharge clearance | Clear the obstruction; repair defrost; never chip ice off the coil |
| 4 | Scaled condenser | Approach above 8 K, high discharge pressure, long run times | Approach calculation; water hardness record | Chemical clean or dismantle and brush; treat the water |
| 5 | Low refrigerant charge | Low suction pressure, high superheat, bubbles in the sight glass | Leak search with an electronic detector and soap solution | Repair the leak, evacuate, recharge by weight |
| 6 | Ambient outside the envelope | Capacity falls on cold days only, no fault code | Compare ambient with the unit’s rated range | Add a cold-climate unit, storage, or backup heat |
Causes 2 and 4 are the two that are routinely misdiagnosed as “the heat pump is too small”. A unit with a scaled condenser can lose 20%–30% of its capacity while every electrical parameter looks normal.
Why scale is the most common hidden cause
A 1 mm scale layer on the water side of a plate heat exchanger adds roughly 10%–15% to the heat transfer resistance. The controller compensates by raising the condensing temperature, which raises the discharge pressure, which reduces the compressor’s volumetric efficiency — and the outlet temperature creeps down while the electricity bill goes up. In hard water above 200 mg/L as CaCO₃, without water treatment, this happens within two to three seasons.
The check is the approach temperature, not a visual inspection: you cannot see inside a brazed plate exchanger. If the approach is above 8 K at design flow, clean it and record the approach again; recovery to 3–5 K confirms the diagnosis.
What “correct flow” means
Heat pump water heaters are usually specified at a 5 K water-side temperature rise. For a 40 kW unit that is:
Flow = 40 ÷ (5 × 1.163) = 6.9 m³/h
If the pump delivers 10 m³/h, the ΔT falls to 3.4 K, the unit cannot reach its setpoint at the outlet because the water passes too quickly, and the compressor runs continuously. If the pump delivers 4 m³/h, the ΔT rises to 8.6 K, the condensing temperature climbs and the high-pressure switch may trip. Both look like “not enough capacity” and neither is.
| Unit capacity | Flow at ΔT 5 K | Typical pipe size | Pump head guide |
|---|---|---|---|
| 10 kW | 1.7 m³/h | DN25 | 6–8 m |
| 20 kW | 3.4 m³/h | DN32 | 8–10 m |
| 40 kW | 6.9 m³/h | DN40 | 10–12 m |
| 80 kW | 13.8 m³/h | DN50 | 12–15 m |
When it is genuinely a sizing problem
If all six causes are excluded and the unit still cannot hold the setpoint on the coldest days, the machine is undersized for the design conditions. Before replacing it, three cheaper options usually exist:
- Add storage. More tank volume lets the unit run at full output for longer and ride through the peak, which is often enough.
- Lower the winter setpoint to 50 °C and use a mixing valve. This reduces the lift and can recover 8%–12% of capacity.
- Add a small electric backup sized for the peak hour only, rather than replacing the whole plant.
Commissioning values to record
At handover, write these into the commissioning sheet so that a future fault can be compared with a known-good baseline: outlet temperature, return temperature, ΔT, flow rate, suction and discharge pressure, condensing approach, superheat, ambient temperature and compressor current. A unit that is 3 K worse on approach two years later has a fouling problem, and you know it before the complaint arrives.
Frequently asked questions
The water is warm but never hot. Is the unit failing?
Warm-but-never-hot usually means the unit is running continuously at reduced capacity — causes 3, 4 or 5. A unit that reaches 45 °C and then stops has a control or setpoint issue instead; check the setpoint and any timer before looking at refrigeration.
Can I just raise the setpoint to compensate?
No. If the unit cannot reach 55 °C because of scale or charge, asking for 65 °C will not help and will raise the discharge pressure further. Fix the cause, then set the temperature the application actually needs.
How do I know whether it is scale or refrigerant?
Compare approach and superheat. High approach with normal superheat points to scale on the water side. High superheat with low suction pressure points to charge or expansion valve. Both abnormal at once usually means scale plus a leak.
Does descaling really restore capacity?
Where scale is the cause, yes — typically 10%–25% of capacity comes back within a day. Use a citric or phosphoric acid cleaning at the concentration and temperature in the manual, neutralise and flush thoroughly, and do not leave the acid in the exchanger.
How often should the water-side heat exchanger be cleaned?
Annually in soft water, every six months above 200 mg/L hardness, and quarterly where the water is aggressive or the unit runs continuously. Add a water softener if the hardness is above 300 mg/L; cleaning is the symptom, hardness is the cause.
Why does it only fail in winter?
Capacity falls with ambient temperature, so a system with no margin fails first on the coldest days. That is a sizing or specification issue rather than a fault — see the winter performance guidance and check the capacity table for the unit at the local design temperature.