The demand is time-boxed, not spread
Domestic hot water in a dormitory is consumed in one or two short windows: after evening study, and sometimes after morning exercise. The daily volume is modest; the peak is severe.
| Boarding type | Consumption per student per day | Shower window |
|---|---|---|
| Primary / secondary boarding | 40–60 L at 60 °C | 1.5–2.5 h |
| Senior high, exam periods | 50–70 L | 2–3 h |
| Vocational college | 50–80 L | 2–3 h |
| University dormitory with ensuite | 60–100 L | 3–4 h |
| Sports school / academy | 80–120 L | 2–3 h |
A 1,500-student senior high school at 60 L per student uses 90 m³ per day. That is a large system, and almost all of it is drawn between 21:00 and 23:00.
Peak-hour factor: the number that decides the tank
| Institution | Peak-hour factor | Consequence |
|---|---|---|
| Boarding school, fixed window | 30%–40% of daily | Storage dominates the design |
| College, longer window | 20%–30% | Balanced storage and capacity |
| Day school with sports | 40%–50% of the used volume | Very large storage for a small daily total |
For the 90 m³ school at 35%, the peak hour is 31.5 m³. No practical heat pump bank can produce 31.5 m³ in one hour — it would need more than 1.5 MW. The design answer is storage.
Storage = peak-hour demand − heat pump output in the peak hour
If the heat pumps deliver 5 m³ equivalent in that hour, storage is 26.5 m³ of usable hot water. Add 20% for dead volume and stratification loss, and the specification is around 32 m³ — typically four 8 m³ tanks or a sectional bank.
Sizing the heat pumps on the recovery window
The recovery window is the period between the end of the evening peak and the start of the next one, minus the hours when the plant should not run because of noise.
| Daily demand | Energy at ΔT 45 K | 8 h recovery | 12 h recovery |
|---|---|---|---|
| 30 m³ | 1,570 kWh | 196 kW | 131 kW |
| 60 m³ | 3,140 kWh | 392 kW | 261 kW |
| 90 m³ | 4,709 kWh | 588 kW | 392 kW |
| 120 m³ | 6,279 kWh | 784 kW | 523 kW |
A 12-hour window across the night and midday is usually the better choice: it halves the plant size, and the noise of a large bank running at 22:00 next to a dormitory is itself a problem. Check the local night-time noise limit before choosing the window.
The storage-to-capacity ratio is the key decision
| Ratio (storage ÷ daily demand) | Effect | Comment |
|---|---|---|
| 0.2–0.3 | Small plant, storage-limited | Risk of running cold at peak |
| 0.3–0.5 | Balanced | Normal for colleges |
| 0.5–0.7 | Large storage, small plant | Good for fixed-window schools |
| Above 0.7 | Storage-dominated | Standing loss and capital cost rise |
For a fixed-window boarding school, 0.5–0.6 is the practical range. Beyond that, the extra tank volume costs more than the plant it replaces and adds standing loss every day.
Distribution: risers, floors and pressure
| Item | Requirement |
|---|---|
| Riser size | Sized on the simultaneous flow of the floors served |
| Floor branch | Balance valve on each floor |
| Pressure | 0.15–0.3 MPa at the farthest shower |
| Balancing | Proportional, with a commissioning record |
| Metering | Per floor or per block, for energy accounting |
| Shower heads | Low-flow, 6–9 L/min |
Unbalanced risers are the classic dormitory complaint: the lower floors get scalding water and the top floor gets warm water. A balance valve on every floor branch, set at commissioning, is the fix.
Controls: card readers, timers and holiday mode
| Function | Purpose |
|---|---|
| Card or app activation | Charges per use and reduces waste |
| Time-of-use scheduling | Heat at night on off-peak tariff |
| Holiday mode | Circulate and disinfect weekly, no heating |
| Anti-legionella cycle | Weekly 70 °C, or continuous 60 °C storage |
| Remote monitoring | Alarm to the facilities team |
| Tamper alarm | Detects unauthorised setpoint changes |
Holiday mode matters more than it appears. A system left full of 45 °C water for six weeks is an incubator; a system drained and refilled is a maintenance task nobody does properly. The right answer is a weekly disinfection cycle with the tanks at 60 °C or above.
Water quality and scaling
School water is often hard, and 60 °C storage accelerates scaling.
| Parameter | Target | Action |
|---|---|---|
| Hardness | Below 200 mg/L as CaCO3 | Soften above 250 |
| Chloride | Below 200 mg/L | 316L tanks above |
| pH | 7.0–8.5 | Adjust if outside |
| Scale on heat exchanger | No visible | Annual inspection |
In hard water areas, the condenser of an air-source unit is water-side clean only if the circuit is treated; a scaled heat exchanger loses 5%–10% of capacity within two years.
Noise and siting next to dormitories
| Distance to nearest window | Measure |
|---|---|
| Under 10 m | Acoustic barrier plus spring isolators, or relocate |
| 10–20 m | Spring isolators, night-time scheduling |
| Above 20 m | Standard installation, check at boundary |
| Rooftop above rooms | Floating base, flexible connectors |
A heat pump bank running at 23:00 under a dormitory window will generate complaints regardless of whether it meets the boundary limit. Schedule the heavy heating before 22:00 where possible.
A worked example
A 1,200-student vocational college, 60 L per student, 14-hour recovery window:
| Item | Calculation | Result |
|---|---|---|
| Daily demand | 1,200 × 60 L | 72 m³/d |
| Daily energy | 72,000 × 4.186 × 45 ÷ 3,600 | 3,767 kWh |
| Plant at 14 h | 3,767 ÷ 14 | 269 kW |
| Winter correction | 269 ÷ 0.75 | 359 kW nominal |
| Units | 359 ÷ 30 kW | 12 units of 30 kW |
| Peak hour at 30% | 21.6 m³ | — |
| Storage | 21.6 − 4.3, ×1.2 | about 21 m³, specify 3 × 8 m³ |
Twelve units is a lot of machines; in practice they are arranged in two banks of six, with one bank on duty at night and both during the morning recovery. Staging also gives redundancy: a failed unit costs capacity, not hot water.
Longkang Environmental Equipment Co., Ltd. designs school systems around the shower window rather than the daily total, and issues the storage calculation with the plant selection so the school can see why the tank is the size it is. Phone: +86 400-878-0280 | +86 130-0200-1280
Questions from school projects
How much storage does a 1,000-student school need?
For a fixed evening window, 15–22 m³. The figure comes from the peak-hour demand minus what the plant can produce in that hour, plus a 20% allowance.
Can one heat pump bank serve several dormitory blocks?
Yes, with a ring main and a central plant. Distributed small units per block are also common and reduce distribution losses, but multiply the maintenance points.
What happens during the summer holiday?
Run a weekly disinfection cycle and keep the circulation pump exercising. Do not drain unless the system will be maintained empty; a drained system left open corrodes.
Is a card system worth the cost?
In most Chinese and Asian campuses yes: it reduces consumption by 20%–40% and pays back within two to three years. It also gives the school data on which blocks are using what.
How do we stop students adjusting the temperature?
Put the setpoint behind a password, use thermostatic mixing valves at the shower, and mount the controller in a locked cabinet. Tamper alarms on the controller are also effective.
What if the school wants to add a block later?
Design the plant room and the ring main for the future load at the start. Adding tanks and units later is straightforward; upsizing the main is not.