Clearance is the first specification, not the last
An air-source unit moves a large volume of air — roughly 200 to 350 m³/h per kW of heating capacity at nominal conditions (0.06–0.10 m³/s), because the evaporator has to draw its heat from that air stream. If that air cannot be replaced, the unit recirculates its own cold discharge, the evaporating temperature falls, and capacity drops while defrost frequency rises.
| Item | Minimum | Preferred | Why it matters |
|---|---|---|---|
| Air inlet face to wall or obstruction | 0.3 m | 0.6 m | Starved inlet lowers evaporating temperature |
| Discharge face to wall (horizontal) | 1.5 m | 2.5 m | Short-circuit of cold air back into the coil |
| Discharge upward to overhead slab | 1.0 m | 2.0 m | Rebound of cold plume |
| Service access to electrical box | 0.6 m | 0.8 m | Safe isolation and gauge connection |
| Between two side-by-side units | 0.8 m | 1.0 m | Mutual interference between air streams |
| Above finished ground / roof | 0.2 m | 0.3 m | Snow, splash and defrost water clearance |
Two arrangements cause most of the trouble. The first is a unit pushed into a recess with one open side: the recess acts as a plenum and the unit breathes its own exhaust. The second is an acoustic enclosure built after a noise complaint, with louvres that cut airflow by half. If noise is a known constraint, design the acoustic treatment as part of the airflow design — an offset barrier or a lined duct with the correct free area — rather than as an afterthought.
Base, weight and vibration
A filled 1,000 L tank weighs a tonne before any steel is added, so tank support usually governs the structural check rather than the heat pump. The heat pump itself is lighter but vibrates.
| Capacity class | Typical unit weight (kg) | Base load to allow (kN) | Isolator type |
|---|---|---|---|
| 5–10 kW | 90–150 | 2.0 | 10 mm rubber pad, 4 points |
| 15–25 kW | 180–320 | 4.0 | Spring or rubber-cork, 4–6 points |
| 30–60 kW | 400–750 | 8.0 | Spring isolators, 6 points |
| 60 kW+ / modular bank | 800+ | per manufacturer | Inertia base plus springs |
The base should be level to within 5 mm across the unit footprint, cast on compacted ground or carried on a steel frame tied to the structure. Do not pack under one corner to level a unit: the chassis will distort and the fan will rub. On roofs, check that the frame does not bridge a drainage outlet, and provide a drip tray with a drain to a suitable point if defrost water cannot be allowed to fall freely.
Defrost water has to go somewhere
In heating mode below about 5 °C the outdoor coil runs below freezing and frost forms. During defrost the unit melts that frost, and a 25 kW unit can release several liters in a single cycle. If the base sits directly on a walkway or a roof membrane, that water refreezes into a hazard.
Provide a raised base of at least 200 mm, a sloped drip tray, and a drain route that does not cross a pedestrian path. In cold climates, do not fit a drain trap that can freeze; use an open discharge with a fall of at least 1:50. Where the unit sits above a public area, a heated drain trace or a collection sump is usually required.
Ambient range and frost protection
Standard models are rated for operation down to about −7 °C, low-temperature models to −20 °C or below, with capacity derating at the lower end of the range. The design temperature, not the average winter temperature, is the correct figure to use: a unit selected on the mean will fail during the cold snap that sets the peak demand.
Water-side frost protection is separate from air-side defrost. If the plant can be isolated and left unheated, either drain the water circuit or fill it with an approved antifreeze mixture and re-check pump head and heat transfer, because glycol reduces both. Do not rely on the unit’s antifreeze protection alone if the power supply can be interrupted.
Noise: what can actually be measured
Sound pressure at 1 m from a typical 20–30 kW unit is around 58–65 dB(A); the figure rises at night when background noise falls. What matters at the boundary is the level at the nearest sensitive window, not at the unit.
| Constraint | Practical measure | Watch out for |
|---|---|---|
| Bedroom window within 5 m | Relocate, or fit a barrier with 1.5× the unit height | Barrier must not block the discharge |
| Boundary wall 3 m away | Solid barrier with absorbent face | Reflective facades opposite |
| Rooftop plant near hotel rooms | Spring isolators plus flexible pipe connectors | Structure-borne path through the slab |
| Multiple units | Stagger starts; check cumulative level | Each +3 dB for a doubling of units |
Structure-borne noise travels further than airborne noise in a concrete frame. Flexible connectors on the water pipes and spring isolators under the chassis are more effective than wrapping the compressor.
Hydraulic and electrical interfaces
Pipe sizes are set by flow and allowable pressure drop, not by the unit connection size alone.
| Heating capacity | Design flow (ΔT 5 K) | Minimum DN | Typical connection |
|---|---|---|---|
| 10 kW | 0.48 L/s | DN25 | 1″ |
| 20 kW | 0.96 L/s | DN32 | 1¼” |
| 30 kW | 1.43 L/s | DN40 | 1½” |
| 50 kW | 2.39 L/s | DN50 | 2″ |
Single-phase 220 V models are limited to roughly 3–5 kW output in practice because of supply current; anything larger is normally three-phase 380 V. Confirm the supply capacity, cable size, isolation means and earth resistance before the unit arrives. A neutral missing on a 380 V unit, or a phase sequence reversed on a scroll compressor, will destroy the compressor within seconds of start-up.
Pre-start sign-off
| Check | Acceptance | Record |
|---|---|---|
| Clearances | Equal to or greater than the table above | Photo with tape measure |
| Base level | Within 5 mm across footprint | Straightedge reading |
| Isolators fitted | All points, correct load | Photo |
| Defrost drainage | Falls, no ponding | Water test |
| Pipe pressure test | 1.5× working pressure, 30 min hold | Signed test sheet |
| Insulation | Continuous, joints sealed | Visual |
| Earth resistance | ≤ 4 Ω | Instrument reading |
| Supply voltage and phase | Within ±10%, sequence correct | Meter reading |
Longkang Environmental Equipment Co., Ltd. supplies a siting drawing with each unit showing the required clearances and connection positions, so the base can be set out before delivery. Phone: +86 400-878-0280 | +86 130-0200-1280
Questions contractors ask on site
How much space does a 30 kW unit need?
Allow roughly 1.5 m × 1.0 m for the unit plus 1.5 m clear in front of the discharge and 0.6 m at the service side. A recessed position needs more, not less, because the walls restrict replacement air.
Can the unit be installed indoors?
Yes, if the space is large enough and ventilation is designed — typically 1.5–2 m³/s of air per 100 kW, or a ducted inlet and discharge to outside. A closed plant room without ventilation will not work: the room becomes a cold reservoir and capacity collapses.
Does the unit have to be lower than the tank?
No. A pressurised circuit with a correctly sized pump will work with the unit above or below the tank. What matters is that the pump is on the return (cooler side), the system is fully vented, and the static pressure at the unit stays within its limit.
How far can the unit be from the tank?
Keep the one-way run under about 15 m where possible. Beyond that, pipe heat loss and pump head both rise; if the run cannot be shortened, increase insulation thickness and re-check pump selection rather than accepting the original figure.
Is a concrete plinth always required?
Not always. A proprietary steel frame on adjustable feet is acceptable on a flat roof if the load is spread and the waterproofing is protected. The requirement is a level, rigid, drained base, not concrete as such.
What if the site is at 1,500 m altitude?
Capacity and motor cooling both change. Above about 1,000 m, ask for an altitude correction — typically 2%–3% capacity loss per 300 m — and confirm the fan motor is rated for the lower air density.