Water Chiller Product Series: A Complete Selection Overview

Classification, four ways

Every chiller sits at the intersection of four choices. Getting those four right narrows the catalog to a handful of models; arguing about model numbers before that is wasted effort.

Classification Options What it decides
Compressor Scroll, screw, centrifugal, magnetic bearing centrifugal Capacity range, part-load behavior, maintenance
Heat rejection Air-cooled, water-cooled, evaporative Plant room space, water availability, COP
Refrigerant R410A, R32, R134a, R513A, R1234ze GWP compliance, pressure, charge limit
Duty Comfort cooling, process cooling, low temperature Leaving water temperature, control precision

The series map

Series type Capacity range Typical COP Where it fits
Air-cooled scroll 3–60 kW 2.8–3.2 Small commercial, no plant room, no cooling tower
Air-cooled screw 60–500 kW 3.0–3.4 Mid-size buildings, rooftop or compound siting
Water-cooled scroll 10–80 kW 4.5–5.2 Plant rooms with a tower, small process loads
Water-cooled screw 100–1,000 kW 5.2–6.0 Offices, hotels, factories, district cooling
Water-cooled centrifugal 300–3,000 kW 5.8–6.6 Large commercial, airports, campuses
Magnetic bearing centrifugal 200–2,000 kW 6.2–7.0 at full load, better part load Data centers, hospitals, low-noise sites
Low-temperature process 5–500 kW 2.0–3.0 Below 5 °C leaving water, brine or glycol
Heat recovery 50–1,000 kW — Simultaneous cooling and hot water demand

Capacity is quoted in kW or in refrigeration tons, where 1 RT = 3.517 kW. A “500 RT” machine is 1,759 kW, and a quotation that mixes the two units without saying so is a warning sign.

Decoding a model number

Manufacturers use their own schemes, but most follow a pattern of compressor code, nominal capacity, refrigerant and variant. A typical designation might read LSBLG-500M/R134a, which decodes as screw (L), water-cooled (S), flooded evaporator, 500 kW nominal, M variant, R134a.

Field Common codes Meaning
Compressor W / L / X / C Scroll, screw, centrifugal, magnetic bearing
Condenser F / S Air-cooled (fan), water-cooled
Evaporator G / B Shell-and-tube, plate
Capacity Number kW nominal, occasionally RT
Variant A / M / H Revision, high-ambient, heat recovery

The number in the model is nominal capacity at rating conditions, not at site conditions. A 500 kW machine at 7 °C leaving water and 30 °C entering condenser water delivers far less at 2 °C leaving water, or with 35 °C condenser water in August.

The rating conditions behind the catalog figures

Two rating frameworks dominate, and they are close but not identical.

Parameter GB/T 18430.1 AHRI 550/590
Chilled water leaving 7 °C 6.7 °C (44 °F)
Chilled water flow 0.172 m³/(h·kW) 2.4 gpm/ton
Condenser water entering 30 °C 29.4 °C (85 °F)
Condenser water flow 0.215 m³/(h·kW) 3.0 gpm/ton
Fouling factor 0.000086 m²·K/W 0.0001 m²·K/W

A chiller rated COP 6.0 at these conditions will deliver about 5.4 if the condenser water arrives at 32 °C instead of 30 °C — a 5%–8% loss per 2 K, which matters in a tropical summer. Always ask for the correction table.

Selection matrix by application

Application First choice Alternative Key constraint
Office 5,000–20,000 m² Water-cooled screw Air-cooled screw Plant room and tower space
Hotel Water-cooled screw with heat recovery Air-cooled screw Simultaneous hot water demand
Factory process cooling Water-cooled screw, plate exchanger Air-cooled screw Water quality, 24/7 duty
Data center Magnetic bearing centrifugal or screw Water-cooled screw Part-load efficiency, redundancy
Hospital Screw with N+1 Magnetic bearing Noise, infection control areas
Small retail or restaurant Air-cooled scroll — No plant room, no tower
Chemical reactor cooling Low-temperature screw, brine Plate chiller + tower Corrosion, explosion protection
Cold store pre-cooling Low-temperature screw — Glycol, low evaporating temperature

Three of these deserve a note. Hotels need heat recovery because the chiller rejects heat all day into a building that also heats water all day; the recovered heat can supply 60%–80% of the domestic hot water load in summer. Data centers need part-load performance, not full-load, because a 2N plant runs at 25%–40% for most of its life. Chemical plants need the wetted materials decided by the process fluid, not by the catalog.

Refrigerant choice in 2026

Refrigerant GWP (AR4) Pressure Status
R22 1,810 Medium Phase-out under the Montreal Protocol; no new equipment
R410A 2,088 High Still common, being displaced
R32 675 High Growing share in small and mid-size
R134a 1,430 Low Common in centrifugal and screw
R513A 631 Low Drop-in for R134a
R1234ze under 10 Low New centrifugal machines

Ask for the charge in kilograms, not just the refrigerant type. A 1,000 kW centrifugal with 400 kg of R134a is a different compliance question from one with 250 kg of R1234ze, and some jurisdictions set charge thresholds that trigger leak detection and reporting.

Capacity control and part-load

The compressor type decides how the machine behaves below full load, and that is where most of the annual energy is spent.

Compressor Capacity control Part-load behavior
Scroll On/off stages or inverter Inverter scroll holds 10%–100% smoothly
Screw Slide valve, 25%–100% Good, but efficiency falls below 40%
Centrifugal Inlet guide vanes, 10%–100% Excellent at high load, surge risk at low load
Magnetic bearing Variable speed, 5%–100% Flattest part-load curve, no oil system

For a plant that spends its life between 30% and 60% load, a machine with a flat curve at part load beats one with a higher nominal COP. That is the argument for IPLV or integrated part-load value as the selection metric, and it is set out in our comparison of COP and IPLV.

Configuration: how many machines

Plant size Usual configuration Reason
Under 300 kW 1 machine + 1 standby, or 2 at 60% Redundancy without complexity
300–1,000 kW 2–3 machines Staging, maintenance without shutdown
1,000–3,000 kW 3–4 machines, mixed sizes Wide efficient band
Above 3,000 kW 4+ machines or centrifugal train Redundancy, staged investment

Mixed sizes — one large and one small — widen the band over which at least one machine runs near full load. Three equal machines give better redundancy but a poorer part-load curve in the 10%–30% range, where a single small machine would be ideal.

Longkang Environmental Equipment Co., Ltd. supplies air-cooled and water-cooled screw chillers from 60 to 1,000 kW with R134a or R513A, and provides capacity correction tables for condenser water temperatures from 25 °C to 40 °C with each quotation. Phone: +86 400-878-0280 | +86 130-0200-1280

Questions buyers ask

Is an air-cooled chiller less efficient than a water-cooled one?

Yes, typically 20%–30% at full load, because the air-cooled condenser works against a dry-bulb temperature of 35 °C rather than a wet-bulb-driven cooling tower at 30 °C. Air-cooled units win on installation cost, water use and plant room space, not on COP.

What does a “low-temperature” chiller mean?

Usually leaving water between −5 °C and +5 °C, using glycol or brine. Below 0 °C the evaporator must be rated for the mixture and the compressor for a higher pressure ratio; a comfort-cooling chiller cannot simply have its setpoint lowered.

How do I compare two quotations with different capacities?

Convert both to the same conditions: same leaving water temperature, same condenser water entering temperature, same flow, same fouling factor. Then compare kW per kW of cooling and check the part-load figures at 50% and 25%.

Does the number in the model equal the kW?

Usually the nominal kW at rating conditions, but some manufacturers use RT or a nominal horsepower. Confirm on the datasheet, and check the capacity table rather than the model number.

How much space does a 500 kW water-cooled chiller need?

Roughly 3.5 × 1.6 m in plan plus 1.0–1.2 m clear at the tube ends for cleaning, and space above for lifting the compressor. Allow a further 30%–40% for pumps, headers and the control panel.

Is heat recovery worth specifying?

If the building has a year-round hot water load — hotel, hospital, swimming pool — yes. A heat recovery chiller can deliver 60%–80% of the summer hot water demand at a marginal cost of 5%–10% on the chiller, and it removes that load from the boilers.

Related reading