“Solar heat pump, zero-carbon hot water” is an attractive slogan, but it hides the central problem: a PV array generates most of its electricity around noon, while a hotel, dormitory or canteen uses most of its hot water in the morning and evening. The two curves do not match. The economic result depends on how much of the PV output is used on site rather than exported at a low price.
This article explains the three coupling options, calculates the storage and array size for a 100-room hotel, and gives a three-stage control sequence that raises self-consumption without a battery.
Prices and irradiance are illustrative. Use the site’s tariff, roof yield and measured hot-water profile.
1. The mismatch is the design problem
A 100-room hotel uses 12 m³/d of hot water at 55 °C, with makeup at 15 °C. Daily heat = 12,000 × 4.187 × 40 ÷ 3,600 = 558 kW·h. At an annual average COP of 3.6, electricity = 155 kW·h/day.
With simple “heat when the tank falls below setpoint” control, the heat pump runs from morning to night, following the draw. PV output peaks between 09:00 and 15:00. The overlap is partial, and the evening peak is served by grid electricity.
The design lever is the tank: heat during the PV peak, store at 60 °C, and draw down in the evening. The tank converts daytime electricity into evening hot water.
2. Three coupling options
AC-coupled. The PV inverter feeds the site distribution board; the heat pump draws from the board. The source of electrons is not distinguishable, but metering and scheduling can prioritize PV. This is the most common retrofittable option, and the PV can be metered separately.
DC-coupled. The PV array feeds a DC bus that drives the heat pump’s variable-frequency drive. It avoids one conversion step and can be 2–3 percentage points more efficient, but few heat-pump drives accept the wide DC voltage range, and the equipment choice is limited.
Off-grid with battery. Only for sites without a reliable grid. A battery added solely to raise self-consumption usually has a payback longer than the control measures. Do not specify a battery by habit.
3. Tank size: 40–60% of daily demand
For 12 m³/d, a tank of 5–7 m³ is a practical range. The tank must store the heat that can be moved from noon to evening, not the entire daily demand.
Usable energy in 5 m³ over a 40 K rise from 15 °C to 55 °C is 5,000 × 4.187 × 40 ÷ 3,600 = 233 kW·h. That is the heat content of a full tank heated from cold; the useful drawdown at 55 °C to 45 °C is only 5,000 × 4.187 × 10 ÷ 3,600 = 58 kW·h. The first figure is the storage capacity; the second is the control buffer. Do not mix them.
If the tank is 7 m³, the full-tank heat is about 326 kW·h, and the 10 K drawdown is about 81 kW·h. The tank also adds standing loss; insulate to 50–80 mm and keep the surface area low.
| Item | Value | Basis |
|---|---|---|
| Daily demand | 12 m³/d | 100 rooms |
| Daily heat | 558 kW·h | 40 K rise |
| Daily electricity | 155 kW·h | COP 3.6 |
| Tank | 5–7 m³ | 40–60% of daily demand |
| Full-tank heat at 7 m³ | 326 kW·h | 15→55 °C |
| 10 K drawdown at 7 m³ | 81 kW·h | 55→45 °C |
4. Size the array by daytime consumption, not annual energy
If the tank can move 58% of the daily heat into the daytime, the daytime electricity demand is 155 × 0.58 = 90 kW·h. At 3.8 peak-sun hours and a system efficiency of 0.80, the array size is 90 ÷ (3.8 × 0.80) = 29.6 kWp. A 30 kWp array is a reasonable match.
Annual generation = 30 × 3.8 × 0.80 × 365 = 33,300 kW·h. Annual heat-pump electricity = 155 × 365 = 56,600 kW·h. The array generates the equivalent of about 59% of the heat pump’s annual electricity, but under the dispatch assumptions only 19,000 kW·h — about 34% of the heat-pump demand — is used on site; the rest is exported.
Do not size the array to equal the annual electricity consumption. That would require about 51 kWp and produce a large export stream at a low tariff, with a long payback. Size for self-consumption first; export is a by-product.
5. Three-stage control
Stage 1 — PV priority, 09:00–15:00. When PV output exceeds the heat-pump demand, raise the tank setpoint by 5 K (for example to 60 °C) and run the heat pump to the upper limit. If PV still exceeds demand, export the surplus.
Stage 2 — normal, 15:00–22:00. Return the setpoint to 55 °C. The heat pump runs only if the tank temperature falls below the lower limit. The stored hot water serves the evening peak.
Stage 3 — off-peak fallback, 23:00–06:00. If the tank is below 50 °C, heat with off-peak electricity. This stage should rarely operate if the tank and array are correctly sized.
The PV signal can come from the inverter’s Modbus output or an irradiance sensor. A small PLC or energy manager reads the signal and writes the setpoint. Retrofits usually use an external controller because the heat-pump panel may not accept a dynamic setpoint.
6. Economics
Assume 30 kWp PV at CNY 3.5/Wp = CNY 105,000, plus CNY 15,000 for the control retrofit, total CNY 120,000 (about USD 16,700 at CNY 7.2/USD).
Annual generation 33,300 kW·h; self-consumed 19,000 kW·h; exported 14,300 kW·h. Self-consumption at CNY 0.70/kWh and export at CNY 0.35/kWh gives annual benefit = 19,000 × 0.70 + 14,300 × 0.35 = CNY 13,300 + 5,000 = CNY 18,300 (about USD 2,540). Simple payback = 120,000 ÷ 18,300 = 6.6 years.
Without the control retrofit, self-consumption may fall to 30%: 10,000 kW·h self-used and 23,300 exported. Benefit = 7,000 + 8,155 = CNY 15,155 (about USD 2,100); payback = 7.9 years. The control retrofit costs CNY 15,000 and shortens the payback by about 1.3 years.
| Case | Self-consumption | Annual benefit | Payback |
|---|---|---|---|
| With dispatch control | 58% | CNY 18,300 | 6.6 years |
| Without control | 30% | CNY 15,155 | 7.9 years |
A battery would add CNY 65,000 for 20 kW·h and extend the payback unless there is a subsidy or a firm green-electricity requirement. Control and thermal storage are usually cheaper than electrochemical storage for this duty.
7. Boundaries
Roof area. A 30 kWp array needs about 200 m² of usable roof. Tanks, air-conditioning units and shading can cut the practical area.
Grid limit. Some distribution networks cap export capacity. Check the interconnection limit before sizing; a larger array may require an upgrade and a longer approval.
Continuous demand. A swimming pool or a laundry with steady all-day demand can self-consume 80% or more. The same array and tank would perform differently; recalculate.
Tariff structure. If off-peak electricity is cheaper than the PV export tariff, heating at night may be more economic than shifting to noon. The dispatch sequence must follow the local prices, not a generic rule.
Frequently asked questions
Why does PV output not match hot-water demand?
PV peaks around noon, while domestic hot water peaks in the morning and evening. Without storage, most generation is exported at a low price and the heat pump runs at night. A tank shifts the noon generation to the demand period.
How much storage is needed?
Size the tank for the evening and morning draw, minus the heat pump output during those hours. A useful check is the noon surplus energy divided by the usable temperature rise. Then confirm the tank recovers before the next peak.
How is self-consumption sized?
Start with the load profile, not the array size. Match array and heat-pump capacity so midday generation is absorbed by the tank and the heat pump, and limit export. Oversizing the array without storage lowers self-consumption.
What is three-stage control?
Stage 1: run the heat pump on PV surplus. Stage 2: charge the tank to a higher setpoint when surplus persists. Stage 3: block or limit grid charging during peak tariffs. The stages should have hysteresis so the unit does not hunt.
Can the heat pump follow PV output?
Some inverters and heat pumps support a PV signal or Modbus control. The heat pump can raise its setpoint or start when surplus exceeds a threshold. Do not force rapid modulation; compressors prefer stable operation.
What happens in winter or cloudy weather?
PV yield falls and hot-water demand rises. Use the grid or a backup heater, and keep the tank at a safe temperature. Size the heat pump for the winter load, not the sunny-day surplus.
How is payback calculated?
Value self-consumed energy at the retail tariff and exported energy at the feed-in tariff. Add the tank and control cost. A system that exports most generation has a much longer payback than the self-consumption ratio suggests.
What should be metered?
PV generation, export, heat-pump power, tank temperatures and hot-water draw. Without separate metering, self-consumption and savings cannot be verified.
Related reading
Heat pump vs gas boiler cost · Inverter part-load efficiency · Coal-to-electric heat-pump retrofit