Retrofitting a farm with a heat pump by copying a domestic hot-water package is a common failure. The drinking line needs a continuous, small flow at a low temperature; the washing line needs a large batch at 45 °C; the staff shower is an ordinary domestic load. Added together, they do not resemble a dormitory or a hotel, and a single unit sized on the wrong load will either freeze the drinkers or run out of water halfway through washing.

The design rule is to split the loads first, then size the plant. Water demand is calculated from stock numbers and daily allowances, not from floor area. The washing load is moved into storage and preheated over 24 hours, not matched at its peak. The unit is installed outside the shed, with a coated coil and a filtered air path.

1. Three circuits, three different duties

Drinking water. In winter, groundwater at 5 °C reduces intake and feed consumption. The practical target is 15–20 °C for finishers and sows, and 20–25 °C for nursery piglets. The circuit runs all day at a small flow with a 10–17 K rise. A small unit and a 2–3 m³ buffer are enough; stability matters more than recovery speed.

Washing water. After a batch leaves, the shed is washed and disinfected with 45 °C water and a high-pressure gun. A 10,000-head site may use 18 m³ per batch across about 200 pens. The instantaneous power is large, but the event occurs only a dozen times a year. Sizing the unit for that peak triples the capital cost for a few hours of use.

Staff showers. For 20–40 staff, demand is 1–2 m³/d at 50 °C, similar to a small dormitory. This load can share the buffer tank and be heated at night.

2. Size by head, not by floor area

Farm demand is quoted per head per day. The following table is a planning guide; actual projects should be checked against the site’s water meter and the coldest-month groundwater temperature.

Use Typical scale Daily water Inlet → outlet Daily heat
Finisher drinking 1,000 head 8 m³ 5 → 20 °C 140 kW·h
Nursery drinking 1,000 head 3 m³ 5 → 22 °C 59 kW·h
Layer drinking 10,000 birds 2.5 m³ 5 → 18 °C 38 kW·h
Shed washing 200 pens/batch 18 m³ 5 → 45 °C 837 kW·h
Staff showers 30 people 1.5 m³ 5 → 50 °C 79 kW·h

The heat formula is the same for every row: liters × 4.187 × rise ÷ 3,600. The 8 m³ finisher row, for example, is 8,000 × 4.187 × 15 ÷ 3,600 = 139.6 kW·h, rounded to 140 kW·h.

These are winter figures. In summer, pigs drink 30–50% more, but the inlet temperature rises above 20 °C, so the rise and the heat demand fall. Size the plant on winter; calculate annual electricity on an annual weighted basis.

3. A 1,000-head example

Take 1,000 finishers, groundwater at 5 °C, drinking water at 20 °C, 8 m³/d, 30 staff showers and a winter design temperature of −5 °C. Drinking and showers together require 140 + 79 = 219 kW·h/d. Over a 10 h heating window, the average is 21.9 kW. At −5 °C, apply a capacity correction of 0.72: 21.9 ÷ 0.72 = 30.4 kW. Select two 16 kW units, or one 32 kW unit with a backup electric heater.

For washing, 4 m³ per batch for a 1,000-head barn requires 186 kW·h. With a 4 m³ insulated tank and the same 32 kW plant, preheating takes 186 ÷ 32 = 5.8 h. For a 10,000-head site with 18 m³ per batch, the demand is 837 kW·h; a 20 kW unit needs about 42 h, so start preheating two days before the batch leaves. A 10 m³ washing tank costs far less than enlarging the unit to 140 kW.

The principle is the same at both scales: washing is a storage problem, not a capacity problem.

4. Three site failures: ammonia, dust and hardness

Ammonia corrosion. Ammonia in the shed air combines with condensate on copper and aluminum to form ammonium salts. The first sign is a white powder on the coil, followed by a slow refrigerant leak within two years. Cleaning does not reverse it. Use an epoxy-coated or hydrophilic-coated coil, install the unit outside the shed and upwind of the exhaust, at least 10 m away, or place it in a separate mechanical room with filtered inlet air.

Feed dust. Dust sticks to the coil and reduces airflow. The unit does not stop; capacity falls quietly. A normal coil has a 3–5 K air-side difference; a blocked coil reaches 8 K or more, with a rising discharge temperature. Add a coarse inlet filter and blow the coil down every two weeks.

Hard groundwater. Above 300 mg/L hardness, scale forms faster at 60 °C and above. The symptom is slower temperature recovery and more frequent high-pressure trips. Add a softener, or plan quarterly acid cleaning. Above 500 mg/L, softener is not optional.

Defrost water. Fit a drain pan heater and a drain pipe with at least 2% slope to a drainage ditch. In the north, insulate the drain; if it freezes overnight, the next defrost floods the base and can damage the fan.

5. Where the approach does not fit

Open or semi-open sheds below −10 °C. Capacity falls below half of nominal. Drinking water can still be maintained, but space heating cannot; use a separate heater or electric trace.

Washing demand above 40 m³/d. The storage tank becomes 20 m³ or more, and the footprint and capital cost are no longer attractive. A gas or biomass boiler may carry the washing load, with the heat pump serving drinking and showers.

Hardness above 500 mg/L without softening. Efficiency falls by more than 20% within two years, erasing the running-cost advantage.

Unstable voltage. Compressors are sensitive to low voltage at the end of a rural feeder. Fix the supply before selecting the unit.

Sizing table by head and use

The three loads do not scale together. Drinking water follows head count, washing follows pens or batches, and showers follow staff. The table gives a starting point for a farm with 5–20 °C inlet and 45–55 °C outlet; it is not a substitute for a site water survey.

Case Daily water Buffer tank Nominal unit Main check
300-head finisher 2.4 m³/d 1 m³ 8 kW Peak hour after washing
1,000-head finisher 8 m³/d 3 m³ 20 kW Winter ambient and recovery
2,000-head finisher 16 m³/d 5 m³ 35 kW Two circuits or one plant
10,000 layers 2.5 m³/d 1.5 m³ 10 kW Drinking line only
200 sows 6 m³/d 3 m³ 18 kW Farrowing and service separately

The nominal output is at a mild ambient. At −12 °C, a unit selected on the table may deliver only 60–70% of its nominal output, so the winter case must be checked separately. Keep the unit outside the shed, draw air from a clean side, and protect the coil from ammonia and dust. A buffer tank of 1–3 m³ is not only storage: it lets the unit run at a stable return temperature and keeps the drinking line from cycling.

For a 1,000-head finisher, drinking is about 8 m³/day and 140 kWh/day; washing and showers can be larger than drinking. Do not size on drinking water alone. If the farm has a farrowing room, supply it separately from the finisher line so a drop in one circuit does not change the other. Use the table to bound the plant, then measure the actual daily draw for a week. The buffer volume should cover the difference between the peak hour and the unit’s recovery rate, not the whole daily volume. You can compare farm packages on the air-source heat pump page.

Common questions

What drinking-water temperature is right?

15–20 °C for finishers and sows, 20–25 °C for nursery piglets. Below 15 °C intake falls; above 25 °C there is no benefit and the energy is wasted. Control at the buffer outlet with a mixing valve.

Can one heat pump also handle washing water?

Yes, with storage. A 10,000-head site may need 18 m³ at 45 °C, or 837 kW·h. A 20 kW unit can preheat it in about 42 h; sizing for a 6 h wash would need 140 kW and is not economic.

Can the unit be installed inside the shed?

Not recommended. Ammonia and dust accelerate coil corrosion, and a leak may appear within two years. Install outside, upwind, with a coated coil and a coarse filter. If it is already inside, duct the inlet from outside.

How should defrost water be handled?

A heated drain pan, a pipe slope of at least 2%, and a drain to a ditch. In cold regions, insulate the pipe; otherwise ice blocks it and water overflows the base.

Is a softener needed for hard groundwater?

Above 300 mg/L, yes. At 0.3 mm scale, capacity falls by 5–8% and the outlet takes longer to recover. A small softener costs less than two acid cleanings a year.

What does the system cost to run?

For 1,000 finishers, drinking and showers are about 219 kW·h/d in winter, roughly 55,000 kW·h of heat per year with seasonal weighting. At a system COP of 2.8, electricity is about 19,600 kW·h; at 0.65 CNY/kWh, about 12,800 CNY/year. Washing adds about 2,200 kW·h of heat per year at 12 batches, or roughly 500 CNY.

What three loads?

Drinking water, washing and staff showers. Each has a different temperature and schedule. Size by the peak head, not the herd count alone.

Why keep the unit outside?

Ammonia, dust and humidity corrode the coil and the electronics. Keep the unit outside the shed and protect the intake. Service access matters more than a compact footprint.