Humidity Cycle: The Coil That Sets Dryer Capacity

A heat-pump sludge dryer is often described as two cycles: a refrigerant cycle that moves heat and a humidity cycle that moves water. The refrigerant cycle is familiar. The humidity cycle is the one that decides the dryer’s capacity, because it is the coil that condenses the water, not the compressor.

This article follows the humidity cycle from the wet sludge to the condensate drain. It explains the dew point, the coil, the airflow and the coupling that makes the two cycles one machine.

The humidity cycle

Air at 40 °C and 60% relative humidity carries about 0.028 kg water per kg dry air. Air at 20 °C and saturation carries about 0.015 kg/kg. The difference, 0.013 kg/kg, is the water the coil can remove. Multiply by the dry-air mass flow to get the condensation rate.

At 15,000 m³/h, the dry-air mass flow is about 18,000 kg/h. At 0.013 kg/kg, the coil removes about 234 kg/h. That is the nominal dehumidification capacity. The sludge evaporation must not exceed it, or the humidity in the chamber rises and the drying rate falls.

Point Dry-bulb RH Moisture
Chamber air 40 °C 60% 0.028 kg/kg
After coil 20 °C 100% 0.015 kg/kg
Removed — — 0.013 kg/kg
Airflow 15,000 m³/h — 18,000 kg dry air/h

The coil is the capacity

The evaporator coil has two jobs: cool the air below its dew point and remove the latent heat. The latent load is 234 kg/h × 0.667 kWh/kg = 156 kW. The sensible load to cool the air from 40 to 20 °C is 18,000 × 1.005 × 20 ÷ 3,600 = 100 kW. The coil load is about 256 kW.

The compressor must remove that heat at the condenser, plus its own power. If the compressor draws 90 kW, the condenser rejects about 346 kW. That heat returns to the chamber air. The energy is not lost; it is re-used to heat the air and evaporate more water. That is why a heat-pump dryer can reach 0.25–0.45 kWh/kg water.

Load Value Basis
Latent 156 kW 234 kg/h × 0.667
Sensible 100 kW 18,000 kg/h × 20 K
Coil 256 kW Sum
Compressor 90 kW Indicative
Condenser 346 kW Coil + compressor

The coil surface must be large enough to reach the dew point without a high air-side pressure drop. A coil with a face velocity above 2.5 m/s may carry condensate into the fan. A fin spacing below 2 mm may block with dust and fiber. A coil that is too small passes the air through without enough contact, and the chamber humidity rises.

The coupling

The two cycles meet at the coil and the condenser. The coil removes heat from the air and water; the condenser adds heat back. The balance is: condenser heat = coil heat + compressor power. If the condenser is undersized, the head pressure rises and the compressor power increases. If the coil is undersized, the air leaves wet and the chamber humidity rises.

The control loop should use the chamber humidity, not the air temperature alone. A dryer held at 60 °C but 80% RH is not drying; it is cooking. A dryer at 50 °C and 40% RH may dry faster with less energy. The set point should be a humidity ratio or a dew point, not a dry-bulb temperature.

Airflow and pressure

The airflow must pass through the sludge bed, not around it. A bed that is too thick, or a belt that is overloaded, creates a path of least resistance around the sludge. The air bypasses the wet material and the coil sees less water. That is a capacity loss that looks like a refrigeration fault.

Measure the pressure drop across the coil and the bed. A coil ΔP above 30% of the clean value indicates fouling. A bed ΔP that is too low indicates channelling; too high indicates compaction. Both change the humidity cycle.

Condensate and reheat

The condensate is not pure water. It carries dust, ammonia and odor. It must go to a drain with a trap, not back to the sludge. A dry trap allows chamber air to escape and worsens the odor. A trap that is too shallow cannot overcome the fan pressure.

The air leaving the coil is cold and saturated. It must be reheated before it returns to the chamber, or it will condense on the walls and the sludge. The condenser provides that reheat. If the condenser is bypassed, the air arrives cold and the drying rate falls.

Control and set points

A heat-pump dryer should control on chamber dew point or humidity ratio, with a temperature limit. A fixed 60 °C set point ignores the humidity and can over-dry the surface while the core stays wet. A dew-point set point of 25–30 °C at 50 °C dry-bulb is a practical target for 30% product; the exact value depends on the sludge and the residence time.

The control should also watch the coil ΔP and the condensate flow. A falling condensate flow with a stable feed is an early sign of coil fouling or a bypass. A rising ΔP with a stable flow is a sign of dust. Both are easier to fix before the product moisture rises.

Boundary

This article covers the air-side humidity cycle of a heat-pump dryer. It does not cover the refrigerant charge, the compressor selection or the sludge chemistry. A dryer with the right airflow but the wrong sludge thickness will still fail; the humidity cycle is a system, not a coil alone.

Common questions

What are the two cycles?

A refrigerant cycle moves heat, and a humidity cycle moves water. The coil condenses the water; the condenser reheats the air. They meet at the coil and condenser.

How much water can the coil remove?

At 15,000 m³/h, 40 °C/60% RH to 20 °C saturated, about 234 kg/h. The exact value depends on the airflow and the coil temperature.

Why is chamber RH important?

A dryer at 60 °C and 80% RH is not drying. Control on humidity ratio or dew point, not dry-bulb temperature alone.

What coil pressure drop is too high?

Above 30% of the clean value suggests fouling. Clean the coil and check the filter before adding refrigerant.

Why does the air need reheat?

Air leaving the coil is cold and saturated. Without reheat it condenses on the walls and the sludge. The condenser provides the reheat.

Can condensate go back to the sludge?

No. It carries dust, ammonia and odor. Drain it through a trap to the sewer or a treatment point.

What sets capacity?

The coil’s dew point and airflow, not the compressor alone. A cold coil below dew point removes water; a warm coil only moves heat.

How do I check the coil?

Measure air before and after, the coil surface temperature and the condensate. Fouling shows as a higher approach and less water.