Sludge Drying: The Two Coupled Cycles

Most operating faults in a heat-pump sludge dryer can be assigned to one of two circuits: the refrigerant loop is not holding the correct high and low pressures, or the air loop cannot bring humidity down. Separating the two, then finding their coupling point, gives a logical troubleshooting sequence instead of an immediate suspicion that the machine is undersized.

This article first defines the criteria for each closed loop, then explains the heat balance where they meet, and finally uses a 10 t/d example to reconcile air flow, heat load and energy. The values are typical for a closed heat-pump dryer; a specific project must use the nameplate and site measurements.

The refrigerant loop moves heat from a low-temperature source to a high-temperature sink

The four components are the compressor, condenser, expansion valve and evaporator. The compressor raises low-pressure vapor to high-pressure, high-temperature gas; the condenser rejects heat and condenses it to liquid; the expansion valve throttles it to low pressure and low temperature; the evaporator absorbs heat and returns vapor to the compressor.

In a dryer, the two heat exchangers have distinct duties. The condenser is the heat source, raising air from about 30 °C to 60–70 °C. The evaporator is the cold source, cooling the humid return air below its dew point so that water condenses out. The difference from a comfort air-conditioner is the temperature band: an air-conditioner evaporates near 5 °C, while a sludge dryer commonly evaporates at 30–38 °C and condenses at 58–68 °C, with a pressure ratio of 2.0–3.0.

Why raise evaporating temperature above 30 °C? Because the heat-transfer surface must be below the air dew point to condense water, and the return air from the drying chamber commonly has a dew point of 30–35 °C. Evaporating at 10 °C would also dehumidify, but the pressure ratio rises, efficiency falls and the coil quickly becomes covered with sludge dust. At about 30 °C, dehumidification is sufficient and efficiency remains reasonable.

Parameter Typical range Consequence of deviation
Evaporating temperature 30–38 °C Below 25 °C: over-dehumidification and high energy; above 40 °C: insufficient dehumidification
Condensing temperature 58–68 °C Above 70 °C: high-pressure protection, high discharge temperature
Pressure ratio 2.0–3.0 Above 3.2: discharge temperature and shaft power rise together
Superheat 3–6 K Too low: liquid return; too high: poor evaporator utilization
Subcooling 3–8 K Too low: flashing before the expansion valve, reduced capacity

The air loop moves water from the sludge to the evaporator

The air loop is also closed: humid return air leaves the drying chamber, passes the evaporator where it is cooled and dehumidified, then passes the condenser where it is reheated, and is delivered back to the chamber by the supply fan. It passes through the sludge bed, picks up water, and repeats.

The transport capacity of this loop is set by two numbers: air flow and the humidity difference between supply and return. Air flow determines how much air is moved; the humidity difference determines how much water each kilogram of air carries. Their product is the hourly dehumidification rate, the first calculation in selection.

Three criteria apply: supply air at 60–70 °C, because drying rate falls noticeably below 55 °C and odor volatilization accelerates above 75 °C; return air at 80–90% relative humidity, because near saturation means the dehumidification capacity is exhausted; and a slight negative pressure of 20–50 Pa in the drying chamber, to prevent odor escape without excessive infiltration.

A distinction is needed between the “temperature cycle” and the “humidity cycle”. The temperature cycle is the heating and cooling of air between condenser and chamber, and it sets drying rate. The humidity cycle is the path of water through sludge, air, evaporator and condensate, and it sets dehumidification capacity. Both run in the same air path, but they are controlled by different variables: temperature by condenser heat and exhaust ratio, humidity by evaporating temperature and air flow.

The coupling point: condenser heat equals evaporator heat plus compression work

The two loops meet at the evaporator and condenser. In a closed loop, condenser heat equals evaporator heat plus compressor input power. The evaporator absorbs the latent heat of the water evaporated from the sludge, and the condenser returns that heat to the drying chamber. In an ideal case, the net energy for evaporating one metric ton of water is only the compression work plus losses.

This is why heat-pump drying is more efficient than hot-air drying, and also where site errors occur. The compression work is a net heat input that must be rejected. For a 10 t/d machine, compression work is about 70 kW and fan power about 8 kW, a total of 78 kW. If this surplus cannot be rejected, the chamber temperature climbs, the product becomes drier than target but too hot, and condensing pressure rises until the compressor derates.

There are two rejection paths. Exhaust air can remove heat; at an enthalpy difference of 90 kJ/kg dry air, 3,000 m³/h removes about 68 kW. An auxiliary air-cooled radiator after the condenser and before the supply fan provides the rest. In humid southern summer, exhaust air carries moisture well but heat less effectively, so an auxiliary radiator is more reliable. In northern winter, the opposite applies and supplementary heat may be needed.

More exhaust is not always better. An exhaust of 3,000 m³/h requires 3,000 m³/h of make-up air; in winter that cold air must be heated, and in summer its moisture must be removed. Design exhaust at 10–15% of circulation flow, with feedback from chamber humidity.

A 10 t/d example: air side and heat side

Feed 10 t/d at 80% moisture, discharge at 60%, 20 hours per day. Dry solids are 10 × 0.2 = 2 t/d. Discharge is 2 ÷ 0.4 = 5 t/d. Evaporated water is 5 t/d, or 250 kg/h.

Take return air at 50 °C and 55 g/kg, supply at 65 °C and 30 g/kg, a humidity difference of 25 g/kg. Dry air required is 250 ÷ 0.025 = 10,000 kg/h. At 50 °C and 1.09 kg/m³, that is about 9,200 m³/h; with 10% margin, select 10,000 m³/h.

On the heat side, latent heat at 2,380 kJ/kg for 250 kg/h is 165 kW. Sensible heat to raise sludge from 20 to 60 °C is about 16 kW, and shell and pipe losses about 12 kW, giving about 193 kW that the condenser must supply. The return air cooling from 50 to 32 °C releases about 54 kW sensible, which together with latent heat gives an evaporator load of about 219 kW. The difference, 26 kW, is of the same order as compression work; in operation the compressor capacity modulates to balance it.

Energy: at a specific dehumidification rate of 2.8 kg/kWh, 5,000 kg/d ÷ 2.8 = 1,786 kWh/d, or 357 kWh/t water. At 0.7 CNY/kWh, daily electricity is 1,250 CNY, or 125 CNY per metric ton of wet sludge.

Item Value Basis
Feed 10 t/d at 80% Design input
Dry solids 2 t/d 10 × 0.2
Discharge 5 t/d at 60% 2 ÷ 0.4
Evaporated water 5 t/d, 250 kg/h 10 − 5 over 20 h
Circulation air 10,000 m³/h 250 ÷ 0.025 ÷ 1.09, plus 10%
Latent load 165 kW 250 × 2,380 ÷ 3,600
Condenser heat About 193 kW Latent + sensible + losses
Compression work About 70 kW From specific dehumidification
Surplus heat to reject About 78 kW Compressor + fan
Specific energy 357 kWh/t water 1,786 ÷ 5

Field diagnosis: dew point, pressure ratio, air flow, condensate

When chamber humidity rises and discharge moisture will not come down, check in this order. First, compare return-air dew point with evaporating temperature. If dew point is 33 °C and evaporating temperature 36 °C, the heat-transfer surface is above the dew point, no water can condense and dehumidification is zero. The cause is usually fouled evaporator fins or low refrigerant charge, not an undersized machine.

Second, check pressure ratio and discharge temperature. A ratio above 3.2 and discharge above 105 °C usually means insufficient condenser-side heat rejection: exhaust damper not open enough, auxiliary radiator fan failed, or fins blocked with dust. The machine derates and dehumidification falls, which appears as “the hotter it gets, the less it dries”.

Third, check air flow and leakage. Traverse the supply duct with an anemometer and compare with design. Measure oxygen in the chamber; above 20.5% indicates leakage. Leakage carries away heat and brings in moisture, a common cause of high summer energy.

Fourth, check condensate drainage. A failed trap allows humid air to return through the drain, silently reducing dehumidification. It is the lowest-cost check and the easiest to forget.

Boundaries where the model does not hold

Below 5 °C ambient without supplementary heat, the closed loop loses too much heat through the shell, supply temperature cannot be maintained and drying rate falls by more than 30%. Electric or hot-air supplementary heat is needed. Above 85% feed moisture, the evaporation load rises; 85% feed evaporates about 2.4 t/d more than 80% feed, and the same machine’s residence time is insufficient. Mechanical dewatering should come first. Sludge containing oil or solvent forms a film on the evaporator fins and creates an explosion risk; that requires an open hot-air system or nitrogen protection, not the closed loop described here.

Increasing compressor size without increasing heat-exchanger area is another false economy. Capacity rises, but the evaporator and condenser areas do not; evaporating temperature is depressed, condensing temperature is raised, pressure ratio increases, and actual dehumidification improves only marginally while power rises sharply.

Common questions

Why does a closed dryer still need exhaust?

Because compression work is a net heat input, about 70 kW on a 10 t/d machine. Without exhaust or an auxiliary radiator, chamber temperature climbs. Exhaust is normally 10–15% of circulation flow; at 90 kJ/kg enthalpy difference, 3,000 m³/h removes about 68 kW.

Is a higher evaporating temperature always more efficient?

At the same condensing temperature, each 1 K rise in evaporating temperature improves COP by about 2–3%. But evaporating temperature is constrained by the return-air dew point; above the dew point, no water condenses and dehumidification is zero. A practical value is 3–5 K below the return dew point.

Why is discharge moisture higher in summer?

Humid ambient air reduces the moisture-carrying ability of the same exhaust volume, while make-up air brings more moisture into the loop. Increase exhaust ratio, raise evaporator heat-transfer capacity, or temporarily reduce throughput.

Is 357 kWh/t water a good figure?

It corresponds to 2.8 kg/kWh, a mid-range value for a conventional closed machine. A well-maintained machine with stable sludge can reach 3.2–3.5 kg/kWh, or 285–310 kWh/t; fouled coils and leakage can drop below 2.0 kg/kWh.

Which loop fails more often?

In the first three years, about 70% of faults are in the air loop: leakage, condensate drainage, fin dust. After three years, refrigerant leaks and compressor wear increase. Check the air side first because it is cheaper and faster.

Why does the chamber need slight negative pressure?

A negative pressure of 20–50 Pa prevents odor escaping through inspection doors and discharge points and supports the uncontrolled-emission requirements of GB 37822-2019. Excessive negative pressure increases infiltration and supplementary heat, so it should not exceed 50 Pa.

What are the two cycles?

The air cycle and the water cycle. The air carries vapor; the water moves through the sludge and evaporates. Both must balance, or the dryer stalls.

Which cycle limits capacity?

Whichever is slower: the coil’s water removal or the sludge’s water migration. Adding heat to the wrong cycle wastes energy.