Coil Bypass Factor: The Latent Capacity You Lose

A heat-pump sludge dryer is a dehumidifier before it is a heater. The coil cools the moist return air below its dew point, water condenses, and the dry air is reheated to absorb more water. If part of the air bypasses the coil without touching the fins, that air never reaches dew point. The machine still runs, but the water removal falls short of the design.

The bypass factor is the fraction of air that passes through the coil without being cooled to the apparatus dew point. It is not a theoretical detail; it is the difference between a 30% product and a 38% product.

Four state points

Point Temperature Relative humidity Moisture content
1. Entering the drying chamber 55 °C 18% 20 g/kg
2. Leaving the drying chamber 42 °C 69% 38 g/kg
3. Leaving the evaporator 18 °C 95% 12.5 g/kg
4. Leaving the condenser 55 °C 11% 12.5 g/kg

From point 2 to point 3, the moisture content falls from 38 to 12.5 g/kg, so every kilogram of dry air removes 25.5 g of water. Heating from 3 to 4 does not change the moisture content; it only lowers the relative humidity and prepares the air to absorb again.

The bypass factor

Bypass factor BF is defined as:

BF = (Tout − TADP) ÷ (Tin − TADP),

where TADP is the apparatus dew point, the effective coil surface temperature. A BF of 0.1 means 90% of the air is cooled to the ADP; a BF of 0.3 means 30% slips through. A deep coil with 6–8 rows can achieve 0.1–0.2; a shallow 3-row coil may be 0.3–0.4.

The ADP is not the chilled-water temperature. It depends on the coil surface, the refrigerant temperature and the air-side heat transfer. A lower ADP removes more water but risks frost on the coil. The practical range for sludge drying is an ADP of 8–12 °C, with an air-off temperature of 15–20 °C.

Face velocity sets the limit

Air velocity through the coil is typically 2–2.5 m/s. Above 2.5 m/s, the air has less contact time, the BF rises and the coil may carry condensate into the duct. Below 1.5 m/s, the coil is oversized and the air-side heat transfer is poor.

A 30,000 m³/h loop with a 2.2 m/s face velocity needs about 3.8 m² of coil face area. If the coil is only 2.5 m², the velocity is 3.3 m/s and the BF rises. The fan may be able to push the air, but the water removal falls.

A 30,000 m³/h calculation

Air density at 42 °C is about 1.1 kg/m³. The dry-air mass flow is 30,000 × 1.1 ÷ (1 + 0.038) = 31,793 kg/h. With a moisture difference of 25.1 g/kg, the water removal is 31,793 × 25.1 ÷ 1,000 = 798 kg/h.

At a latent heat of 0.69 kWh/kg, the coil duty is 798 × 0.69 = 551 kW. At a system COP of 3.8, the compressor power is 551 ÷ 3.8 = 145 kW. The fans add 30–45 kW, so the total is about 195 kW and the overall dehumidification ratio is 798 ÷ 195 = 4.1 kg/kWh.

Item Formula Result
Dry-air mass flow 30,000 × 1.1 ÷ 1.038 31,793 kg/h
Moisture difference 38 − 12.9 25.1 g/kg
Water removal 31,793 × 25.1 ÷ 1,000 798 kg/h
Coil duty 798 × 0.69 551 kW
Compressor power 551 ÷ 3.8 145 kW
Total power 145 + 45 + 5 195 kW
Dehumidification ratio 798 ÷ 195 4.1 kg/kWh

The 4.1 figure is optimistic because the entering air is at 38 g/kg and the leaving coil is at 18 °C saturated. Field units usually achieve 2.8–3.6 kg/kWh. The difference is the bypass factor, coil fouling and condensate re-evaporation.

Why 50–60 °C, not 70

A higher air temperature increases the moisture-carrying capacity, but it also raises the coil load and the compressor lift. At 70 °C, the return air may be 50–55 °C; the evaporator still has to cool it to 18 °C, so the compressor does more work. The gain in moisture content is smaller than the gain in energy. The practical range for sludge is 50–60 °C, with a 10–15 K temperature drop across the drying chamber.

What goes wrong on site

Low refrigerant charge. The evaporator pressure rises, the coil temperature rises, and the air leaves above dew point. The dryer looks like it is running but removes less water. Check superheat and subcooling before adding gas.

Fouled coil. Dust and biofilm reduce the air-side heat transfer. The BF rises and the coil may freeze unevenly. Clean the coil and check the drain pan.

Condensate re-evaporation. If the pan holds water and the air passes over it, the water returns to the air. The drain must be trapped and sloped; the pan should not be a sump.

High face velocity. A coil that is too small for the airflow throws condensate into the duct. The water leaves the machine as droplets, not as a drain flow. Check the coil face area and the air velocity.

Common questions

What is coil bypass factor?

The fraction of air that passes through the coil without being cooled to the apparatus dew point. A BF of 0.2 means 20% of the air bypasses the effective coil surface and removes little water.

Why does a higher air temperature not always dry more?

It raises the moisture-carrying capacity, but it also raises the coil load and the compressor lift. Above 60 °C the energy penalty usually outweighs the moisture gain.

How many coil rows are needed?

For sludge drying, 6–8 rows are common to reach a BF of 0.1–0.2. A 3-row coil may be adequate for a small unit but will have a higher bypass factor.

Can I increase water removal by increasing airflow?

Only up to the coil’s face velocity limit. Above 2.5 m/s the contact time falls, the BF rises and condensate can be carried into the duct. Increase coil area before airflow.

Why does the product stay wet when the machine runs?

Check the coil temperature, refrigerant charge, coil fouling and drain. The machine may be moving air without reaching dew point, or the condensate may be re-evaporating in the pan.

What dehumidification ratio is realistic?

Field units typically achieve 2.8–3.6 kg water per kWh of total power. A calculation that gives 4.1 is based on ideal entering air and a clean coil.

How do I measure bypass factor?

Measure the entering and leaving air dry-bulb and dew point, and the coil surface temperature. The bypass factor is the fraction of air that passes without contacting the coil. It falls as coil depth or face velocity falls.

How does coil depth affect it?

A deeper coil has more surface and a lower bypass factor, but it adds air pressure drop. A shallow coil at high face velocity lets more air bypass and loses latent capacity. Balance depth against fan energy.

Further technical reading

For the psychrometrics, see Sludge Dehumidification Drying: Psychrometrics of the Loop. For the dehumidification ratio, see Sludge Dryer Dehumidification Ratio. For the two cycles, see Sludge Drying: The Two Coupled Cycles. For drying temperature, see Sludge Dryer Drying Temperature.