A sludge dryer is often described by its evaporative capacity: 500 kg/h, 1,000 kg/h. That number is a water balance, not an energy balance. The machine can only evaporate that water if the heat reaches it, and the heat has to come from somewhere.
This article follows the heat through a low-temperature heat-pump dryer. It uses a 1 t/h feed at 80% moisture and 30% product to keep the numbers concrete.
Two loops, one balance
The dryer has two coupled loops. The refrigerant loop moves heat from the evaporator to the condenser. The air loop carries that heat to the sludge and carries the moisture back to the evaporator. The two loops meet at the evaporator and the condenser, and the energy balance is the bridge between them.
The refrigerant loop is a heat pump: the compressor lifts the temperature from the evaporator to the condenser. The air loop is a humidity loop: the air picks up water in the drying chamber, the evaporator condenses it out, and the condenser reheats the dry air. Neither loop works alone.
The four air states
| State | Location | Temperature | Relative humidity | What it means |
|---|---|---|---|---|
| 1 | Chamber outlet | 40–50 °C | 70–90% | Air has taken water from the sludge |
| 2 | Evaporator outlet | 15–25 °C | Near saturation | Water has condensed out |
| 3 | Condenser outlet | 50–70 °C | 20–40% | Air is dry and hot again |
| 4 | Chamber inlet | 50–70 °C | 20–40% | Air is ready to absorb water |
The mass of water removed per kilogram of air is the humidity difference between state 1 and state 2, not the relative humidity. Air at state 2 may be at 95% RH, but its absolute humidity is lower than at state 1. That difference is the drying capacity.
Mass balance first
For 1,000 kg/h of 80% cake: dry solids = 1,000 × 0.20 = 200 kg/h. Product at 30% = 200 / 0.70 = 285.7 kg/h. Water evaporated = 1,000 – 285.7 = 714.3 kg/h. The condensate is about 714 kg/h; in a closed loop, the water has nowhere else to go.
If the product is 40%, the mass is 333.3 kg/h and the evaporation is 666.7 kg/h. If the feed is 85%, the dry solids are 150 kg/h, the product at 30% is 214.3 kg/h and the evaporation is 785.7 kg/h. The same machine sees a 10% higher load when the feed is 5 points wetter.
Energy balance second
The heat required has three parts: heating the feed and the water to the drying temperature, evaporating the water, and making up the losses. The latent heat is about 2,260 kJ/kg at 60 °C; the sensible heat for the feed and the water is smaller but not negligible.
At 714 kg/h evaporation, the latent load is 714 × 2,260 = 1.61 million kJ/h, or about 448 kW. Add 10–15% for sensible heat and losses, and the dryer needs about 500–515 kW of heat at the air side. If the heat pump delivers 3.5 kW heat per kW electricity, the compressor draw is about 143–147 kW. A unit with a lower COP needs more.
| Item | Value | Basis |
|---|---|---|
| Evaporation | 714 kg/h | 1 t/h, 80% to 30% |
| Latent heat | 2,260 kJ/kg | At about 60 °C |
| Latent load | 448 kW | 714 × 2,260 / 3,600 |
| With losses | 500–515 kW | +10–15% |
| Compressor draw | 143–147 kW | At COP 3.5 |
This is the number that should match the nameplate. A machine rated 500 kg/h evaporation with a 90 kW compressor is claiming a COP above 5.5 at 60 °C, which is not credible for a standard low-temperature dryer. Ask for the heat balance, not only the water capacity.
What the balance tells you
First, it separates the water capacity from the heat capacity. A dryer can be water-rich and heat-poor, or the reverse. The balance tells you which is the limit.
Second, it shows the effect of the target moisture. Going from 30% to 20% adds only 0.36 t/d of water in the 10 t/d example, but it also lowers the product temperature and may need a longer residence time. The energy per metric ton of product rises.
Third, it shows the value of pre-dewatering. If the press can deliver 78% instead of 80%, the evaporation falls from 714 to 673 kg/h, about 6%. That is a smaller machine or a lower bill for the same product.
Three checks on site
Check the condensate. The condensate flow should match the calculated evaporation within 5–10%. A lower flow means water is accumulating in the chamber or leaking; a higher flow means the feed is wetter than assumed.
Check the air temperature rise across the condenser. The rise should match the heat delivered; a low rise with a high compressor current suggests a low air flow or a fouled coil.
Check the specific energy. Divide the compressor kWh by the water evaporated. A low-temperature dryer is typically 0.25–0.45 kWh/kg water. A number below 0.20 is suspicious; a number above 0.50 means the machine is working outside its design point.
Where the losses hide
The largest loss is the gap between the condenser heat and the air heat: duct loss, fan heat and casing loss. The second is the evaporator defrost or the coil fouling, which reduces the dehumidification. The third is the reheat of the condensate and the product, which leaves the system with sensible heat.
A well-insulated chamber and a well-sealed air loop recover most of these. An open chamber or a leaky duct can lose 10–20% of the heat, which appears as a higher specific energy and a lower condensate flow.
Boundary
This balance is for a closed-loop heat-pump dryer at 50–80 °C. A high-temperature dryer has a different latent heat and a different air flow. A dryer with a heat exchanger or a heat recovery unit has additional terms; the method is the same, the numbers are not.
Common questions
Why is the water capacity not the same as the heat capacity?
Because evaporation needs latent heat. A machine can be rated for water but lack the heat to evaporate it. The heat balance, not the water number, sets the real capacity.
How much heat to evaporate 1 kg water?
About 2,260 kJ/kg at 60 °C, plus sensible heat and losses. A practical estimate is 2,500–2,600 kJ/kg in a low-temperature dryer.
What is a normal specific energy?
0.25–0.45 kWh/kg water for a low-temperature heat-pump dryer. Below 0.20 is suspicious; above 0.50 means the machine is off its design point.
Why does 80% to 30% evaporate 714 kg/h?
Dry solids are 200 kg/h. At 30% product, the mass is 200/0.70 = 285.7 kg/h, so 714.3 kg/h is evaporated. The dry solids are conserved.
Does a wetter feed change the machine size?
Yes. At 85% feed, the evaporation is 786 kg/h for the same dry solids, about 10% more than at 80%. Size on the wettest expected feed, not the average.
How do I check the balance on site?
Compare condensate flow with calculated evaporation, air temperature rise with condenser heat, and kWh/kg with the design specific energy.
How do I build the heat balance?
Measure the electricity input, the water evaporated, the product and condensate mass, and the heat lost from the casing. The latent heat of evaporation is the useful output. The balance should close within a few percent.
What loss is acceptable?
Casing, condensate and air losses vary by design, but a large unexplained gap means the measurement or the claim is wrong. Compare the heat balance with the measured evaporation, not the nameplate.