Heat pumps · Chillers · Sludge drying systems
Heat pump · Hot water · Heating · Cooling

Air-Source Heat Pumps: Questions That Decide a Project

A heat-pump hot-water project rarely fails because the machine is badly built. It fails because the load was estimated from a rule of thumb, the cylinder was sized to the daily total rather than the peak, or the unit was installed where it could not breathe. The questions below are the ones that decide the project before a model number is chosen.

Each answer carries a number, a condition or a test, so it can be checked against a real site rather than accepted as a general assurance.

Start with the load, not the label

For a staff facility with 100 people, a common design value is 50 liters per person per day. That gives 5 m³/day. With a 40 K rise, the daily heat is about 232.6 kWh. If the plant is allowed 12 hours to recover, the average output is about 19.4 kW; two 10 kW units and a 5 m³ cylinder cover the duty with a realistic margin.

The rule of thumb is only a starting point. A dormitory with concentrated shower peaks needs the upper end of the range; a factory with shift-based washing may use less. The daily energy is the same arithmetic, but the peak hour decides the cylinder and the number of units.

What COP does and does not promise

A heat pump moves heat; it does not convert one kWh of electricity into four kWh of new heat. At a nominal COP of 4.0, one kWh of electricity moves about three kWh from the air and adds one kWh of compressor work. The four kWh at the condenser is useful heat, but three of them were already in the air.

The nominal figure is a laboratory point. At 20 °C ambient and 55 °C delivery, a good unit may reach 3.5–4.0. At 7 °C it may fall to 2.5–2.8; at -7 °C to about 2.0. A standard scroll unit loses capacity faster than an enhanced-vapor-injection (EVI) unit, which can hold heating output at -15 °C and is the right choice for a cold-climate site.

Use the seasonal average, not the badge COP, for the energy bill. A unit rated 4.0 at nominal conditions often averages 3.0–3.4 across a year. A quote that promises an annual COP equal to the nominal figure is not a forecast; it is a brochure.

Sizing the cylinder and the machine together

The cylinder is usually 0.8–1.0 times the daily demand. Concentrated shower use takes the upper end; distributed washbasins take the lower end. A cylinder that is too small empties at the peak and forces the compressor to cycle; one that is too large costs more and loses more standing heat.

Several smaller units are usually more flexible than one large unit. They can rotate, provide standby and run at a better part-load efficiency. Above three units, check the starting current: sequence the starts or use soft starters so the supply does not see the full inrush at once.

Question Design value What it changes
Daily demand 40–150 L per person Energy and cylinder volume
Recovery window 8–16 h Unit output and number of units
Cylinder ratio 0.8–1.0 of daily demand Peak availability and cycling
Lowest ambient Coldest month, not annual average Model and defrost strategy

Installation: air, noise and the return line

The unit needs a clear air path. Leave about 1.5 m at the service face and 1 m at the air inlet; do not place it in a closed recess or against a wall that returns its own exhaust. A unit that recirculates hot air loses capacity and defrosts badly, even if the model is correct.

Operating sound is commonly 60–70 dB(A). On a residential site, face the unit away from bedrooms and fit anti-vibration pads under the base to reduce structure-borne noise. A low-noise model or a barrier is cheaper at the design stage than after a complaint.

Fit a return loop when the farthest outlet is more than 15–20 m from the cylinder. Without it, the user runs the tap and waits for the line to clear. Control the pump on return temperature, not a 24-hour timer; a continuously running loop can double the circulation loss.

Water quality and the service interval

Scale is the quiet killer. At the same flow, a rise in the water-side temperature difference of 2 K above the commissioning value is a signal to clean. Hard water above 200 mg/L as CaCO3 needs attention; above 300 mg/L, fit a softener rather than plan to descale every year.

A practical service schedule is monthly coil cleaning and electrical inspection, quarterly water and temperature-difference checks, and an annual refrigerant and compressor audit. A dusty site or a hard-water site shortens the interval. The annual audit should include the compressor insulation, the refrigerant charge and the safety controls, not only a visual look.

The money question

A heat pump costs more than an electric heater or a gas boiler at the outset and less to run. For a project using 500 kWh of heat per day, an air-source plant may cost about CNY 33,000 a year in electricity; direct electric heating about CNY 128,000; gas about CNY 57,000. The gap pays back the extra capital over a few years, but the exact payback depends on the local tariff and the seasonal COP.

The machine is usually designed for 10–15 years, the cylinder for 8–12. Water quality, running hours and maintenance decide whether the upper end is reached. The compressor and the controller are the expensive parts; check the warranty and the local spare-parts route before comparing prices.

Key parameters at a glance

The five question groups above reduce to a short cross-check table. Use it to challenge a quotation, not to replace the load calculation.

Item Typical value What it changes
Nominal COP 3.0–4.0; seasonal 3.0–3.4 Running cost, not the badge number
Cold-weather capacity At 7 °C, 0.75–0.82 of nominal; at −7 °C, COP about 2.0 Unit size and defrost strategy
Water demand 40–150 L per person per day Daily heat and cylinder volume
Cylinder ratio 0.8–1.0 times daily demand Peak availability and compressor cycling
Recovery window 8–16 hours Unit output and number of units
Operating sound 60–70 dB(A) Setback distance, low-noise model or barrier
Service life Host 10–15 years; cylinder 8–12 years Warranty, spare-parts route and lifecycle cost

If two numbers conflict, fix the load and the design ambient first. A nominal COP cannot settle a cold-climate sizing question, and a cylinder ratio cannot compensate for a unit that cannot breathe. The table is a checklist for the next question, not a substitute for the site survey.

The same discipline applies to installation. A unit selected on the table but placed in a recess with a blocked return will lose capacity and defrost badly; a cylinder sized at the upper ratio but fed by a long, uninsulated line will deliver a lower usable temperature at the tap. Check air path, pipe run and power capacity before signing the order. Longcom’s air-source heat pump page gives the model ranges and the installation envelope behind these figures.

Common questions

Does a COP of 4 mean four units of heat per unit of electricity?

It means four units of useful heat at the condenser for one unit of electrical input, but three of those units are moved from the air. The nominal COP is a test-point value, not a year-round average.

Can a heat pump work at -15 °C?

A standard scroll unit loses much of its output; an EVI unit can hold heating at -15 °C. Size on the coldest month and include defrost losses, not on the annual average.

How big should the cylinder be?

About 0.8–1.0 times the daily demand. Take the upper end for concentrated showers and the lower end for distributed washbasins; check the peak hour, not only the daily total.

How far can the hot-water line run without a return loop?

Beyond 15–20 m to the farthest outlet, fit a return loop. Control the pump on temperature; a 24-hour loop wastes heat and pump energy.

What is the first sign that the heat exchanger needs cleaning?

The water-side temperature difference rises by 2 K above the commissioning value at the same flow. Clean and check the water treatment before the COP falls further.

How long does a heat-pump water heater last?

The unit is typically designed for 10–15 years and the cylinder for 8–12. Hard water, long running hours and skipped coil cleaning move the life toward the lower end.

What is the first question to ask when sizing a heat pump?

How much hot water is drawn at the peak hour, not the daily total. The peak hour sizes the plant; the daily total only sets the tank. Get the fixture count and the draw profile.

What load data?

Headcount, shift pattern, fixture flow and simultaneity. A daily average hides the morning peak.

Further technical reading

For the full working principle, see What Is an Air-Source Heat Pump Water Heater?. For COP bands, see How to Read a Heat Pump COP. For common selection errors, see Heat-Pump Selection Mistakes. For the service plan, see Air-Source Heat Pump Maintenance Schedule.

Related reading

Heat Pump Project Questions · Heat Pump Price Factors · Heat Pump Tender Technical Response