Six Inputs Before a Heat-Pump Quote

A heat-pump quotation is often built from a daily water volume and a per-person liter figure. That is enough for a first estimate, not enough for a purchase order. Six inputs decide whether the unit will hold temperature in the worst week, not the average week.

This article lists the six inputs, the calculation for each and the questions to ask before signing. The example is a 100-person dormitory with 6 m³/day at 55 °C.

1. Daily draw, not occupancy

Use liters per person at 55 °C, not the tank volume. A dormitory may use 60 L/person; a hotel 80–100 L; a factory canteen a different pattern. The draw also includes cleaning and process use. If the site has a water meter, use 12 months of data.

For 100 people at 60 L, the daily draw is 6 m³. At 15 °C mains and 55 °C supply, the temperature rise is 40 K. The daily heat is 6,000 × 4.18 × 40 ÷ 3,600 = 279 kWh.

2. Winter ambient, not laboratory 7 °C

The nominal capacity is measured at 7 °C air. The winter design may be -5 °C or -15 °C. Ask for the capacity at the site’s winter ambient and the leaving-water temperature. A 39 kW nominal unit may deliver 27 kW at -5 °C, a 30% reduction.

If the winter capacity is 70% of nominal, one 39 kW unit gives about 27 kW. Running 10 hours, it delivers 270 kWh, close to the 279 kWh daily demand. That is one unit at full load for 10 hours, with no margin for a cold snap or a defrost cycle.

Input Example Why it matters
Daily draw 6 m³/day at 55 °C Sets the energy
Winter ambient -5 °C Sets the real capacity
incoming water temperature 15 °C Sets the temperature rise
Peak profile 60% in 2 hours Sets the tank and peak kW
Tank volume 3–4 m³ Bridges the peak
Electrical supply 380 V, 3-phase Sets the unit size

3. Supply temperature, not just “hot water”

55 °C, 60 °C and 65 °C are different products. A 5 K higher supply temperature lowers the COP by roughly 8–12% and increases standing loss. For most dormitory and hotel use, 55 °C at the tank with a 50 °C return is enough; a kitchen or a hospital may need 60–65 °C and a mixing valve.

State the supply temperature, the return temperature and the mixed delivery temperature. A system designed for 55 °C but set to 60 °C to “be safe” will consume more and scale faster.

4. Peak profile, not daily average

The tank is sized by the peak, not the daily total. At that profile, 3.6 m³ falls inside the two-hour window, so the draw rate is 1.8 m³/h. Lifting that flow by 40 K needs 83.7 kW. One 39 kW unit supplies less than half the peak, so the tank must cover the deficit while the compressor keeps charging.

A 3 m³ tank at 55 °C holds roughly 140 kWh of useful heat above incoming water temperature. That buffer can carry a 1.8 m³/h draw for under two hours, provided it is full at 06:00. The recovery timer should therefore start at 22:00, not when the first shower opens.

5. Tank and electrical room

Tank volume is 30–60% of the daily draw for a normal profile; 50–70% for a school or factory with a sharp peak. A 6 m³/day dormitory may need 3–4 m³, not 6 m³. A tank that is too large wastes standing heat; too small shifts the load to the compressor at the worst time.

Check the electrical supply before choosing the unit. A 10 HP unit may need 380 V three-phase and a dedicated breaker. A building with a 100 A service may not accept two units starting at once. A soft starter or a staggered start may be needed.

6. Water quality

Hardness, chloride, iron and suspended solids decide the condenser type and the water treatment. A brazed plate condenser in hard water scales; a shell-and-tube tolerates it better. A site with chloride above the manufacturer’s limit needs a different material or a secondary loop.

Ask for a water analysis before the quote. A softener, a strainer or a closed secondary loop may add 5–15% to the project, but it is cheaper than a condenser replacement in year three.

The quote checklist

Ask the supplier to state: the winter capacity at the site ambient, the COP at that condition, the daily energy at the design draw, the tank volume and the peak kW, the electrical demand, the condenser material and the water-quality limit. A quote that gives only the nominal capacity and the tank volume is a budget quote, not a design.

Also ask for the defrost strategy and the low-temperature cut-out. A unit that defrosts every 30 minutes in a humid winter spends a lot of energy melting ice; a unit that never defrosts in a coastal climate will ice the coil.

Boundary

This six-input method is for a single building with a known draw. A district or a resort with several buildings needs a load profile per building and a central plant model. A process with a simultaneous hot and cold demand needs a different machine, not a larger tank.

Common questions

Is 60 liters per person enough?

For a dormitory, 50–60 L at 55 °C is a common planning figure. A hotel may need 80–100 L; a factory canteen has a different peak. Use metered data if available.

Why is winter capacity lower?

The evaporator extracts heat from colder air, so the lift is higher and the capacity falls. A 39 kW nominal unit may deliver 27 kW at -5 °C. Size on the winter number.

How big should the tank be?

30–60% of daily draw for a normal profile; 50–70% for a school or factory with a sharp peak. A 6 m³/day dormitory may need 3–4 m³, not 6 m³.

Can one 10 HP unit serve 100 people?

It can cover the daily energy in a mild climate, but not a 1.8 m³/h morning peak. The tank must carry the peak or a second unit must start before the draw.

Do I need a softener?

If the hardness is above the manufacturer’s limit, yes. A brazed plate condenser scales faster than a shell-and-tube. Test the water before choosing the condenser.

What should a quote state?

Winter capacity at site ambient, COP at that condition, daily energy, tank volume, peak kW, electrical demand, condenser material and water-quality limit. Nominal capacity alone is not a design.

What six inputs are essential?

Daily volume, winter ambient, peak draw, supply temperature, tank volume and electrical capacity. Add water quality and site altitude. Without these, the quote is a catalog selection, not a design.

How do I compare quotes with different scope?

Normalize the tank, controls, installation, commissioning and warranty. Compare delivered cost and guaranteed performance at the same winter condition. A low price with a smaller tank may not meet the peak.

Further technical reading

For selection mistakes, see Heat Pump Selection Mistakes That Cost Money After Handover. For hotel design, see Hotel Hot Water by Air-Source Heat Pump. For COP, see How to Read a Heat Pump COP. For installation, see Heat-Pump Installation: Six Stages, Three Inspections.