A heat-pump that will not heat is not necessarily short of refrigerant. More often, one of four state points has moved and the control is still working to a set point it cannot reach. The four points are the suction, the discharge, the condenser outlet and the expansion-valve inlet. Each can be read with a gauge and a contact thermometer.
This article turns the heating cycle into four readings and a fault table. The reference condition is 20 °C ambient, 15 °C inlet water and 55 °C outlet water with R410A.
Four readings, four state points
| Point | Where | Normal reading | What it proves |
|---|---|---|---|
| Suction | Compressor inlet | 2–5 °C evaporating, 3–5 K superheat | Air side is loading the coil |
| Discharge | Compressor outlet | 75–85 °C at 20 °C ambient | Compression ratio is sane |
| Condenser outlet | Liquid line | 3–8 K subcooling | Water side is taking the heat |
| Valve inlet | Before expansion valve | Liquid, no flash gas | Charge and subcooling are adequate |
At the standard point, R410A sits at about 0.93 MPa on the low side and 3.83 MPa on the high side, a pressure ratio of 4.1. The exact values move with the refrigerant and the manufacturer’s setting, but the relationship does not: a low-side reading converts to an evaporating temperature, and a high-side reading converts to a condensing temperature.
Reading 1: suction pressure gives the evaporating temperature
Connect a manifold gauge to the suction service valve and convert the pressure with a saturated-temperature table. In the standard condition the evaporating temperature should be 2–5 °C, about 7–10 K below the ambient. If the ambient is 15 °C and the low side reads 0.5 MPa, the evaporating temperature is about -13 °C, a 28 K difference. That is not a normal operating point; the coil is starved, blocked or short of air.
Check the air path before the charge. A dirty coil, a blocked filter, a reversed fan or a failed fan capacitor can cut airflow by 20–30%, lower the evaporating temperature by 2–4 K and cut heating output by 8–15%. A 0.3 mm dust layer is enough to start that chain. The gauge tells you the coil is starved; the air-side inspection tells you why.
Reading 2: discharge temperature gives the compression ratio
Discharge temperature is the most sensitive signal on the high side. At 20 °C ambient, 75–85 °C is normal. At a pressure ratio of 7, 95–105 °C is common. Above 110 °C, the oil begins to coke and the discharge valve life falls sharply. Most commercial units protect at 110–120 °C; a trip at that level is a symptom, not a reset problem.
Pressure ratio is calculated on absolute pressure. A ratio of 4 gives a scroll volumetric efficiency of about 0.85–0.90; a ratio of 7 gives 0.78–0.82; a ratio above 10 gives 0.65–0.75. The lost volumetric efficiency looks like a loss of charge, so the temptation is to add refrigerant. Adding charge raises the condensing pressure and the ratio further, which makes the real problem worse.
Before adding gas, read the suction pressure and the superheat. A low suction pressure with a high superheat points to a starved evaporator or an undersized valve opening. A normal suction pressure with a high discharge temperature points to a high condensing pressure or a compressor problem. The two are different repairs.
Reading 3: condensing approach gives the water side
The condensing approach is the condensing temperature minus the leaving-water temperature. For a brazed-plate condenser, 3–5 K is normal; for a coaxial condenser, 4–6 K. At 55 °C outlet water, the condensing temperature should be 58–62 °C, corresponding to 3.6–3.9 MPa on R410A.
An approach that grows from 4 K to 7 K is a water-side warning. The causes are scale, low flow, air in the loop or an overcharge. A 40 kW unit with 50/55 °C water and a 5 K rise needs about 6.9 m³/h. If the actual flow is 5 m³/h, the same heat is carried by a 6.9 K rise, the average condensing temperature rises 1–2 K and the COP falls 3–5%.
A 0.5 mm scale layer adds a resistance of about 0.0002–0.0004 m²·K/W, roughly the same effect as the low flow. The gauge sees the pressure; the flow meter and the water analysis see the cause.
Reading 4: subcooling gives the liquid line
Subcooling is the condensing temperature minus the liquid-line temperature at the condenser outlet. Normal is 3–8 K. It keeps the expansion valve inlet full of liquid. Each additional 1 K of subcooling raises the unit heating capacity by about 0.8% and the COP by 0.5–0.7%, which is why a unit with a subcooler can beat a simpler unit by several points.
Low subcooling shows as a liquid line close to the condensing temperature, frost at the valve body and an intermittent flow sound at the valve. High subcooling, above 12 K, often means the condenser is flooded or the charge is excessive; the high pressure and current rise, but the heating capacity does not.
Winter moves one point, not four
In winter the condensing temperature is held by the leaving-water set point, so the high side stays near 3.6–3.9 MPa. The low side is the point that moves. At -5 °C ambient, the evaporating temperature may fall to -12 °C, the suction pressure to about 0.53 MPa, and the pressure ratio to about 7.2.
| Ambient | Evaporating | Suction | Ratio | Capacity factor |
|---|---|---|---|---|
| 20 °C | 3 °C | 0.86 MPa | 4.4 | 1.00 |
| 7 °C | -3 °C | 0.72 MPa | 5.3 | 0.78–0.82 |
| -5 °C | -12 °C | 0.53 MPa | 7.2 | 0.55–0.62 |
| -15 °C | -22 °C | 0.36 MPa | 10.6 | 0.42–0.50 |
The capacity factor is not one loss. It is the product of a larger suction specific volume and a lower volumetric efficiency. At -12 °C, the specific volume is about 1.6 times the 3 °C value, so the mass flow falls to 0.62. The volumetric efficiency falls from 0.88 to 0.78, a factor of 0.886. The product is 0.55, which is why a 40 kW unit delivers about 22 kW before defrost time is deducted.
Fault table
| Reading | Fault family | First check |
|---|---|---|
| Low suction, high superheat | Evaporator starved | Airflow, filter, fan, valve opening |
| Low suction, low superheat | Liquid return | Charge, valve setting, sensor |
| High discharge, normal suction | High condensing or compression | Water flow, scale, charge |
| High condensing approach | Water side | Flow, strainer, scale, air |
| Low subcooling | Liquid line | Charge, condenser, valve |
Read all four before touching the charge. A single reading can send you to the wrong component, and the most expensive component is usually the last place the evidence points.
Boundary
These readings are for a single-stage R410A packaged water heater. A cascade, a CO2 unit or a variable-refrigerant system has different pressures and different normal bands. Use the manufacturer’s table for the refrigerant in the unit; the method of four points still applies.
Common questions
What does 0.5 MPa suction mean on R410A?
About -13 °C evaporating temperature. If the ambient is 15 °C, that is far below normal and points to a blocked coil, low airflow or a starved valve, not simply low charge.
Can I keep running at 105 °C discharge?
Briefly, but it is already in the oil-degradation band. Check suction pressure and superheat first. A low suction with high superheat suggests a starved evaporator; a normal suction suggests high condensing pressure.
What is normal subcooling?
3–8 K at the condenser outlet. Below 3 K risks flash gas at the valve; above 12 K suggests flooding or overcharge, with high pressure and current but no extra capacity.
Why does a 40 kW unit give only 22 kW in winter?
At -5 °C the evaporating temperature falls to about -12 °C. The suction specific volume rises 1.6 times and the volumetric efficiency falls to about 0.78; the product is about 0.55, so 40 kW becomes 22 kW before defrost losses.
Does low suction always mean low refrigerant?
No. A dirty coil, a blocked filter or a failed fan can starve the evaporator with a full charge. Check airflow and superheat before adding gas.
Which reading is most often ignored?
Subcooling. A liquid line that is close to condensing temperature looks normal to a touch, but it means the valve is seeing flash gas and the evaporator is not fully fed.
Which reading first?
Suction pressure and superheat first, then discharge and subcooling. The first reading narrows the fault; the rest confirm it. Do not add refrigerant before reading all four.
What does subcooling tell me?
Low subcooling suggests undercharge or a restriction; high subcooling suggests overcharge or a blocked condenser. Read it with the other three.
Further technical reading