A hot-spring resort is a hotel with a chemistry problem. The rooms need domestic hot water, the pools need continuous heat, and the source water may carry chloride, sulphide, silica and hardness at levels that will perforate a stainless-steel exchanger in two years.
This article uses a published design basis for an 80-room resort with three indoor pools (210 m²), two outdoor pools (90 m²) and 260 guests/day. The numbers are a design example, not a site record.
Split the load into three
The pool load has three parts: surface evaporation, wall and floor loss, and makeup water heating. Evaporation is the largest, often 70% or more.
| Load | Basis | Value |
|---|---|---|
| Indoor pool surface | 210 m² × 180 W/m² | 37.8 kW |
| Outdoor pool surface | 90 m² × 240 W/m² | 21.6 kW |
| Wall and pipe loss | 12% of surface | 7.1 kW |
| Makeup water | 32 m³/day, 25 K | 38.8 kW |
| Pool total | — | 105.3 kW |
| Guest hot water | 24 m³/day, 40 K | 93.0 kW |
| Combined design | 1.0 × sum + 15% | 230 kW |
The pool load is continuous; the guest load peaks in the morning and evening. They are not simultaneous at full value, so the plant is sized at the sum plus a 15% margin, not at the sum of both peaks. A resort that adds a spa, a laundry or a snow-melt load must add those separately.
Source water: the design driver
Hot-spring water is not domestic water. A typical analysis may show total dissolved solids 1,500–4,000 mg/L, chloride 300–1,200 mg/L, sulphide 1–10 mg/L, silica 50–120 mg/L, hardness 150–600 mg/L and iron/manganese 0.3–3 mg/L.
A standard stainless-steel plate exchanger may pit at chloride above 200 mg/L. At 500 mg/L, 316L is not a safe choice. Sulphide attacks copper and produces odor. Hardness scales the exchanger. Iron and manganese deposit and block the passages.
| Parameter | Spring water | Unit limit | Risk |
|---|---|---|---|
| Chloride | 300–1,200 mg/L | <200 mg/L | Pitting, perforation |
| TDS | 1,500–4,000 mg/L | <500 mg/L | Scale and corrosion |
| Sulphide | 1–10 mg/L | Trace | Copper corrosion, odor |
| Hardness | 150–600 mg/L | <200 mg/L | Scale |
| Iron / manganese | 0.3–3 mg/L | <0.1 mg/L | Deposits |
Indirect heat exchange
The reliable answer is a secondary loop. The heat pump heats softened intermediate water; a titanium plate exchanger transfers that heat to the spring water. The two streams never mix, so the heat pump sees clean water and the titanium handles the chloride.
Titanium costs about 40% more than stainless steel, but 316L may not last three years at 500 mg/L chloride. The selection rule is simple: if chloride is above 300 mg/L, use titanium. If the project is small and the pool is ornamental, a titanium immersion coil is an alternative, but its efficiency is lower.
Do not use a direct-to-pool heat pump on spring water unless the water analysis is within the manufacturer’s limit. A warranty that excludes chloride damage is not a warranty for this site.
Plant selection
The example uses four 65 kW low-temperature heat pumps, three duty and one standby, for 195 kW at 20 °C. At -7 °C each delivers about 45 kW, so three duty units give 135 kW. The pool load is 105 kW, leaving a margin for defrost and a cold snap.
The standby is not pure redundancy. A heat pump loses capacity during defrost; with three duty and one standby, there is always output. A 30 m³ tank, split into two compartments, carries the domestic peak. Each compartment can supply two hours of peak demand.
A standard unit would deliver only 55% of nominal at -8 °C, taking 195 kW down to 107 kW, barely above the 105 kW pool load. One cold snap would force electric backup. The low-temperature unit is not a luxury; it is the difference between meeting the load and not.
Dehumidification and heat recovery
The indoor pool evaporates about 60 kg/h at 40 °C water. If the hall is ventilated at 20,000 m³/h with a 12 K indoor-outdoor difference, the exhaust carries about 80 kW of heat. A dehumidifier with pool-water heat recovery can recover 60–70 kW of that, reducing the pool heater load and controlling the hall humidity.
A three-in-one unit (dehumidification, heat recovery and pool water heating) is common for resorts. It solves the condensation and mold problem as well as the energy bill. The control sequence should prioritize dehumidification when the hall RH rises above 60%, and pool heating when the water falls below the set point.
Seasonal load
The winter load may be 180 kW, the summer load 130 kW. A plant sized for winter runs at low load in summer. Four machines allow staging: one or two in summer, three or four in winter. A single large machine would cycle and lose efficiency.
The summer surplus can preheat the domestic water or run the outdoor pool at a higher temperature. A resort with a spa or a laundry can use the surplus instead of venting it.
Boundary
This design basis is for a resort with published pool areas and guest counts. A real project needs the source-water analysis, the pool operating schedule and the local discharge rules. A spring with high radon, fluoride or heavy metals may need pretreatment before the titanium exchanger, not just a different material.
Common questions
Why can’t spring water go directly into the heat pump?
Chloride at 300–1,200 mg/L pits stainless steel; sulphide attacks copper; hardness scales the exchanger. Use a titanium intermediate exchanger so the heat pump sees clean water.
Is titanium worth the extra cost?
At chloride above 300 mg/L, yes. 316L may fail within three years at 500 mg/L. Titanium costs about 40% more than stainless but avoids a premature replacement.
How is the pool load calculated?
Surface evaporation plus wall loss plus makeup water. For 210 m² indoor and 90 m² outdoor, the example is 105.3 kW. Guest hot water is calculated separately.
Why four heat pumps instead of one?
Four units allow staging from summer to winter and provide output during defrost. Three duty at -7 °C give 135 kW, enough for the 105 kW pool load with a margin.
How much heat can the dehumidifier recover?
A 20,000 m³/h unit can recover 60–70 kW from the exhaust, reducing the pool heater load and controlling hall humidity.
What about silica and iron?
Silica can scale the exchanger and iron/manganese can block passages. Pretreatment or a removable titanium exchanger may be needed; test the water before selecting the material.
Can I use a plate exchanger instead of titanium?
A plate exchanger is compact and efficient, but its thin plates are less tolerant of chloride and fouling. Use titanium or a suitable alloy for the spring-water side, and keep the heat-pump loop clean. Material selection follows the water analysis.
How do I control corrosion in the pool hall?
Keep the chloride source away from the heat pump, use a secondary loop, ventilate the mechanical room, and specify corrosion-resistant cabinets and coils. Wash down surfaces that collect salt. A coated coil is not a substitute for keeping chloride out.
Further technical reading
For the general resort design, see Hot Spring Resort Hot Water: Recover the Tail Water. For pool systems, see Pool Heating with Air-Source Heat Pumps. For low-temperature evidence, see Heat-Pump Factory Audit at -7 °C. For policy evidence, see Clean-Heating Policy: The Evidence a Project Needs.