A covered pool hall is a latent-load machine. Water evaporates from the surface, the air carries the moisture, and the dehumidifier removes it. The pool heat pump adds heat to the water, but it also changes the air temperature and the evaporation rate. If the three are sized separately, the pool is either cold, humid or corroded.
This article treats the pool as a coupled system: water heating, evaporation, dehumidification and chloride corrosion. The example is a 25 m × 10 m pool in a temperate climate.
The water-side load
The pool loses heat through evaporation, convection to the air, radiation and conduction to the floor. Evaporation dominates in an open hall. A common planning range is 0.1–0.2 kg/m²/h of water evaporated, depending on water temperature, air relative humidity and air velocity.
For a 250 m² pool at 27 °C water and 28 °C air at 60% RH, evaporation may be 25–50 kg/h. At 0.68 kWh/kg latent heat, that is 17–34 kW of latent load. The sensible loss from the water surface and walls may add 5–10 kW. The water heater must cover both the standing loss and the heat-up of makeup water.
| Load | Basis | Example |
|---|---|---|
| Evaporation | 0.1–0.2 kg/m²/h | 25–50 kg/h |
| Latent heat | 0.68 kWh/kg | 17–34 kW |
| Surface and wall loss | 10–20 W/m² | 2.5–5 kW |
| Makeup water | 3–5% volume/day | 5–10 m³/day |
The makeup water is often the hidden load. A 250 m² pool at 1.5 m depth holds 375 m³. A 4% daily make-up is 15 m³, and heating it from 15 °C to 27 °C needs 15 × 1.163 × 12 = 209 kWh/day. That is a steady 8.7 kW, before any bather load.
The air-side load
The dehumidifier sees the evaporation load plus the moisture from bathers. A bather releases about 0.1–0.2 kg/h of moisture, and a shower room adds more. The pool hall should be held at 50–60% RH; below 45% the evaporation increases and bathers feel cold, above 65% condensation and chloramine build-up increase.
The dehumidifier is not a separate box that can be sized after the heat pump. In a combined unit, the heat pump’s condenser reheats the dehumidified air, and the evaporator cools and dehumidifies it. The compressor sees both the pool water and the air. If the air is cold and dry, the evaporator has less latent load; if the air is warm and humid, the latent load rises and the water heating capacity falls.
Chloride and corrosion
Pool water is not domestic water. Free chlorine is typically 1–3 mg/L, chloride can be 500–1,500 mg/L, and the pH is 7.2–7.6. The air carries chloramines, which attack copper, aluminum and mild steel. A standard copper-tube heat exchanger in the pool water circuit will fail; a titanium tube or a PVC heat exchanger is the practical choice.
Air-side components need protection too. Aluminum fins in the pool hall should be epoxy-coated or replaced with a corrosion-resistant coil. Electrical enclosures should be at least IP55, with a drip shield. Stainless steel 304 is not enough at the weld in a chloramine environment; 316L or a coated surface is better.
| Part | Risk | Specification |
|---|---|---|
| Pool water heat exchanger | Chloride pitting | Titanium or PVC |
| Air coil | Chloramine attack | Epoxy-coated aluminum |
| Fasteners | Crevice corrosion | 316 stainless |
| Controls | Humidity and chlorine | IP55, separate room |
Sizing the heat pump
Size the water heater for the standing loss plus the make-up load plus a heat-up allowance. For the example, 17–34 kW latent is not the water heater’s load; it is the dehumidifier’s load. The water heater sees the 2.5–5 kW surface loss, the 8.7 kW make-up load and the bather load. A 25–35 kW heat pump covers the steady state; a 50–60 kW unit gives a faster heat-up and a margin for winter.
Do not size the water heater for the latent load. That is a common error: the evaporation is large, so the heat pump is oversized, and it then cycles at low load. The dehumidifier handles the latent load; the water heater handles the water.
COP and air temperature
A pool heat pump in a 28 °C hall has a favorable evaporating temperature, so its COP can be 4.5–5.5. In winter, if the hall air falls to 15 °C, the COP falls to 3.5–4.0 and the capacity falls by 20–30%. The design should use the winter air temperature, not the summer catalog point.
If the heat pump draws air from outdoors, the winter COP is lower still. A pool hall unit that uses indoor air is more efficient but needs a dehumidifier that can handle the moisture. The two decisions belong together.
Control sequence
Hold the water at 26–28 °C and the air at 28–30 °C with 50–60% RH. Heat the water when the pool temperature falls 1 K below the set point, and dehumidify when RH rises above 60%. Do not run both at full output against each other; a combined controller should stage the compressor and the reheater.
Cover the pool when it is not in use. A cover cuts evaporation by 70–90% and is the cheapest energy measure in the building. It also reduces chloramine production and the dehumidifier load. If the pool has no cover, the heat-pump and dehumidifier sizes both rise.
Commissioning checks
Measure the water flow, the entering and leaving water temperature, the air temperature and RH before and after the coil, and the compressor power at a steady load. Compare the water-side temperature rise with the design. A rise that is 2 K low at design flow means low refrigerant charge, a fouled exchanger or a bypass.
Check the pool water chemistry before warranty sign-off: pH, free chlorine, chloride, alkalinity and cyanuric acid. A titanium exchanger can survive chloride, but it cannot survive poor pH and no water treatment. Record the chemistry and set a monthly check.
Boundary
An indoor pool with a separate dehumidifier and a separate water heater can work, but the two units fight over the air temperature. A combined unit is more compact and usually more efficient, but it is less flexible when the pool and the hall have different schedules. The choice should be made on the operating hours, not on the catalog.
Common questions
Is a heat pump suitable for pool heating?
Yes, because the water is only 26–30 °C and the air is warm. The COP can be 4.5–5.5 in a 28 °C hall. The key is to size the water heater and the dehumidifier separately.
Why is the dehumidifier half the load?
Evaporation from a 250 m² pool can be 25–50 kg/h, or 17–34 kW of latent heat. That load must be removed by the dehumidifier, not by the water heater.
What heat exchanger material is needed?
Titanium or PVC for the pool water circuit. Copper will pit at 500–1,500 mg/L chloride. Air coils should be epoxy-coated aluminum; 304 stainless is not enough at welds.
How much makeup water load is there?
A 4% daily make-up on a 375 m³ pool is 15 m³. Heating it from 15 °C to 27 °C needs about 209 kWh/day, or 8.7 kW steady. That is often larger than the surface loss.
Should the heat pump use indoor or outdoor air?
Indoor air gives a higher winter COP but transfers the moisture problem to the dehumidifier. Outdoor air is simpler in summer but loses capacity in winter. The choice depends on the hall design.
Does a pool cover help?
Yes. A cover cuts evaporation by 70–90%, reduces the dehumidifier load and lowers chloramine production. It is usually the cheapest measure available.
How do I size the dehumidifier?
Use the evaporation rate from the pool surface, the number of bathers, and the hall air volume. The dehumidifier must handle the latent load at the design occupancy, not the average. Add margin for door openings and ventilation.
Why does the pool heat pump short-cycle?
Usually because the unit is oversized for the water loop, the flow is low, or the setpoint dead band is too tight. Check the minimum run time, the bypass, and the tank or pool volume. A buffer tank often solves it.
Further technical reading
For pool system design, see Pool Heating with Air-Source Heat Pumps. For piping, see Heat Pump Water Piping. For COP, see How to Read a Heat Pump COP. For service, see Air-Source Heat Pump Maintenance.
Related reading
Pool heat-pump system design · Heat-pump COP rating · Heat-pump maintenance