Pool Heat Pump Efficiency FAQ: COP, AHPF, Part Load, Running Cost, Metering

Efficiency questions are mostly comparison questions: which number, at what conditions, over what period, and with what excluded. Twenty answers below, in that order.

Indicator What it covers Use it for
COP One point, stated conditions Comparing units at identical conditions
Seasonal efficiency Whole year, part load, defrost Running-cost estimates
Part-load ratio Minimum capacity against nominal Judging cycling risk
Specific energy kWh per tonne of water heated Sanity-checking proposals

1. Reading the numbers

Q1. What is the difference between COP and seasonal performance?

COP is one ratio at one set of conditions. Seasonal performance integrates the same ratio across the year, including part-load operation, defrost cycles and ambient variation. It is always lower than the nameplate figure, typically by 15–30%.

Q2. When comparing two units, what must be identical?

Air dry-bulb and wet-bulb, water entering and leaving temperature, and water flow. If any of the four differs, the comparison is meaningless, however similar the numbers look.

Q3. How large is low-temperature derating?

Commonly 15–25% of capacity at 0 °C and 40–50% at −15 °C against nominal, with COP falling further. The unit’s own curve is the only reliable statement.

Q4. What load does a pool actually run at most of the year?

Holding load, which is a modest fraction of installed capacity — often 30–60%. The rest of the capacity exists for first heat-up, cold snaps and recovery after bather surges.

Q5. Why is a single COP number not enough?

Because it hides where the unit will actually operate. A machine excellent at 7 °C and poor at 0 °C is the wrong purchase for a pool that must hold temperature in winter.

2. Running cost

Q6. Does pump energy belong in the running cost?

Yes. Circulation runs continuously and can account for a meaningful share of the bill; heat pump COP figures deliberately exclude it. Compare total kWh, not compressor kWh alone.

Q7. How is annual cost estimated for a 60 kW holding load?

Delivered heat is about 60 kW × the hours the pool is held, typically 3000–5000 a year in a year-round installation. Dividing by a realistic seasonal COP of 3.5–4.5 gives the electrical input; add pumps and controls.

Q8. How does that compare with a gas boiler?

A condensing boiler delivers heat at roughly 90% efficiency, so the comparison is kWh of gas against kWh of electricity at a seasonal COP. Where electricity and gas prices differ by a factor of three or more, the heat pump still wins on cost.

Q9. Does refrigerant choice affect running cost?

It affects the achievable cycle efficiency and, more visibly, the service and spares situation during a transition period. For the buyer, the practical question is whether the refrigerant will remain serviceable for the machine’s life.

Q10. Is an inverter always cheaper to run?

Only where the load spends real time below half capacity. On a pool that runs near nominal most of the day, the inverter’s part-load advantage rarely repays its higher purchase and repair cost.

3. Operating strategy

Q11. How much does a night cover save?

Evaporation is usually more than half the holding load, and a cover cuts evaporative and convective loss by 50–70% while it is on. For a pool covered nightly, that is a large share of annual consumption — and the cheapest measure available.

Q12. Do lower water temperature setpoints save energy?

Yes, strongly: every kelvin lower reduces the condensing temperature and the pressure ratio. But the setpoint is a comfort and compliance decision, so the saving is only available within the allowed band.

Q13. How should time-of-use tariffs be used?

By pre-heating during cheap periods and coasting through expensive ones, using the pool itself or a buffer tank as storage. The pool is a large thermal battery; the control sequence should exploit it.

Q14. How much can heat recovery contribute?

In an indoor pool with dehumidification, the latent heat returned to the water can cover a substantial fraction of the holding load. In an outdoor pool with no hall, there is nothing to recover.

Q15. How is defrost loss accounted for?

As a reduction in the seasonal figure, not in the single-point COP. In humid cold climates frequent defrost can remove 10–20% of a day’s output; the seasonal estimate must include it or it will be optimistic.

4. Hours, measurement and diagnosis

Q16. What annual operating hours should be assumed?

From the pool’s actual schedule: year-round commercial pools run 4000–6000 hours of holding duty; seasonal outdoor pools a few hundred. The number should be stated in the proposal, not buried.

Q17. How is a retrofit’s saving measured?

With a metered baseline before the works and the same metering after, normalised for weather and bather load. Without a baseline, savings are an opinion.

Q18. How much can a variable-speed pump save?

Often 30–50% of pump energy, because pressure demand falls with the square of flow. It pairs naturally with a heat pump that has a minimum flow requirement.

Q19. What does the electricity bill reveal about unit health?

A step change in consumption at constant conditions points at fouling, low charge, a failing fan or a control fault. Tracking monthly kWh against heating degree days is the cheapest condition monitor there is.

Q20. What is the simplest useful metering set?

One electrical meter on the heat pump circuit, one on the pump, a water flow meter and in/out temperature sensors. That combination yields delivered heat and real COP at any time.

Q21. Why do two quotes with the same COP differ so much in running cost?

Because one used the seasonal curve and the other used the nameplate point. The difference is typically 20–40% of the annual bill, and it is settled by asking for the calculation, not the number.

Efficiency and COP · Low temperature FAQ · Market outlook · Pool heat pump FAQ