1. COP is a point; efficiency is a line
COP is heat output divided by electrical input at one set of conditions. It describes a point. A pool heat pump runs a thousand hours or more a year through spring, summer, autumn and winter, at high and low load, day and night — and the annual bill is set by the line, not the point.
The biggest number in the brochure is almost always COP, because it photographs well. In the same project, two units with similar nominal COP can differ by more than 20% on the annual bill, for three reasons: how capacity falls at low ambient, how well the unit modulates at part load, and how much pump energy the exchanger’s pressure drop costs. Judge on COP alone and you will buy a unit that performs on the test bench and not in the plant room.
2. A rating needs five parameters
COP only means something with conditions attached. For a pool heat pump those conditions are five: air dry-bulb, air wet-bulb or relative humidity, entering water temperature, leaving water temperature, and water flow. Drop any one and the number is not comparable.
Commercial heat pump water heaters in China are tested to GB/T 21362-2023, which specifies nominal COP and the annual heating seasonal performance factor for cycling-heating models; efficiency grades refer to GB 29541-2013. Pool heat pumps have no dedicated national efficiency method, so manufacturers work to that standard or to enterprise standards, and the conditions differ.
| Parameter | Why it matters | Common trap |
|---|---|---|
| Air dry-bulb | Sets evaporating temperature | “Normal ambient” with no value given |
| Wet-bulb or RH | Drives latent heat and frost risk | Dry-bulb only, humidity ignored |
| Entering water | Sets condensing temperature | Low water temperature used to inflate COP |
| Leaving water | Sets mean condensing temperature | ΔT quoted too large or too small |
| Water flow | Affects heat transfer and pump energy | No flow quoted, so nothing can be recalculated |
3. Seasonal efficiency and AHPF
AHPF weights capacity and consumption across the year into a single annual figure. It is closer to real use than a point COP, but the result depends on the climate zone, the load model and the operating strategy, and the boundaries are not identical between manufacturers.
For a specific pool, the more useful request is a weather-year simulation for the site, or at minimum a table of capacity, input power and COP at 15 °C, 10 °C, 5 °C, 0 °C and −5 °C. With that table the design institute can weight it against local weather data and produce a defensible annual consumption.
4. Part load is where a pool actually runs
Pool load is flat, and most of the year sits between 30% and 60% of rated capacity. A fixed-speed unit can only cycle in that band, and its real efficiency is well below the nameplate. An inverter unit holds a low frequency and runs continuously, staying nearer its best region.
| Load band | Fixed speed | Inverter | Control response |
|---|---|---|---|
| 80–100% | Near rated | High frequency, COP slightly lower | All units on |
| 50–80% | Frequent cycling | Mid frequency, good efficiency | Stage up as needed |
| 30–50% | Heavy cycling, poor efficiency | Low frequency, continuous | Reduce unit count |
| Below 30% | Unstable | Low frequency or rotation | Rotate, night setback |
Assess part-load capability on four numbers: minimum operating frequency or minimum capacity percentage, modulation range, COP at low load, and starts per hour. “Stepless from 30% to 100%” is the target; what is achieved depends on the compressor’s minimum stable frequency and the control logic.
5. Low-temperature derating: read the curve, not a point
Air-source capacity falls as ambient falls; that is physics. How far it falls depends on coil area, compressor displacement, vapor-injection or two-stage enhancement, and defrost strategy. A mild-climate model may hold only 60–70% of nominal at 0 °C; a cold-climate model may hold around 80%.
The selection rule is to take capacity at the local winter design temperature, not to size on nominal capacity. If the site’s design temperature is −2 °C and the unit gives 30 kW there while the holding load is 60 kW, the answer is two units, not one and a half of a 40 kW nominal unit.
6. System efficiency: pressure drop and pump energy
The heat pump’s COP is only part of the system. The circulation pump runs all year, and pump energy can be 20–40% of total electricity. A higher exchanger pressure drop means more head, more pump power, more heat added to the water by the pump itself — and a lower system efficiency for the same COP.
Two units both rated COP 4.5, one with 15 kPa pressure drop and one with 40 kPa, can end up far apart in system terms. Ask for the pressure-drop curve and carry it into pump selection. Retrofits are especially exposed: the existing pump may lack head, flow falls after the exchanger is changed, capacity falls with it, and the plant gets worse with every “upgrade”.
7. Noise: the indicator that is not on the bill
Noise does not appear in the electricity bill but decides whether the project passes an environmental review and whether it can run at night. Pool units are rated in dB(A), usually at 1 m in front. Read three things alongside the number: distance and direction, whether background noise is included, and behavior at low load at night.
Inverter units can run at reduced speed overnight, and noise falls with speed. For hotels, residential and hospital sites, write a night-mode limit and a speed band into the technical agreement instead of accepting a single nameplate figure.
8. Electric heating versus a heat pump, as a recalculable sum
Assume an indoor pool with a 60 kW holding load, 2 000 full-load-equivalent hours, electricity at 0.65 CNY/kWh, and no allowance for defrost or part-load (a magnitude demonstration only).
| Scheme | Annual electricity (kWh) | Annual cost (CNY) | Note |
|---|---|---|---|
| Electric resistance | 120 000 | 78 000 | COP fixed at 1 |
| Heat pump, COP 4.5 | 26 667 | 17 333 | Mild conditions |
| Heat pump, blended COP 3.6 | 33 333 | 21 667 | Includes cold spells and defrost |
| Heat pump plus night cover | ≈ 22 000–26 000 | ≈ 14 300–16 900 | Evaporation loss reduced |
The blended figure is the one to quote. A single mild-condition COP produces a number nobody can defend after the first winter.
9. Four clauses that put efficiency into the contract
First, attach conditions and curves: name the five nominal parameters and require capacity and input power at 15, 5, 0 and −5 °C. Without that table the savings claim cannot be tested. Second, set a measured tolerance, following normal efficiency practice: measured efficiency should not fall below 95% of the declared value, with the exact percentage per the standard and the contract — this is what stops a “5.5 declared, 4.2 measured” outcome. Third, define the measurement method and who pays for the test. Fourth, state the remedy — correction, re-selection or price adjustment — before the order, not after commissioning.
10. Three common efficiency claims, translated
“80% cheaper than electric heating.” At COP 4.5 the theoretical saving is about 78%, but cold weather, defrost and pump energy erode it. A fair statement carries the conditions and the boundary.
“COP up to 5.8.” Ask for the test conditions. At 24 °C air and 26 °C water the figure is credible but says nothing about the year; at low ambient it needs a test report behind it.
“Inverter, so it saves energy.” Inverters help where the load spends time well below rated — which is most pools — but the saving depends on the minimum frequency, the control logic and whether the unit is staged at all.
Related reading
Heat-pump COP ratings explained · Energy per tonne of hot water · Heat-pump payback periods · Selection mistakes that cost money · Pool heat pump specifications
Related pages in this series
Market outlook · Technical data · Efficiency FAQ · Pool heat pump FAQ