Sludge Dehumidification Drying: Psychrometrics of the Loop

A closed-loop sludge dryer does not “blow hot air at the sludge”. It cools the circulating air below its dew point so that water condenses, then reheats the air so that it can take up water again. The drying rate is set by the difference in humidity ratio between the air entering and leaving the sludge bed, multiplied by the mass flow of dry air.

Understanding that relationship explains why a dryer can run at the right temperature and still be slow, and why a larger compressor does not always fix a capacity problem.

1. Two coupled loops

The refrigerant loop. The compressor, evaporator, expansion valve and condenser move heat. The evaporator is the cold coil that condenses water; the condenser is the hot coil that reheats the air.

The air loop. The fan moves air through the chamber, the evaporator, the condenser and back. The air carries the water from the sludge to the coil and the heat from the condenser to the sludge.

The two loops meet at the coils. The evaporator’s surface temperature must be below the air’s dew point; the condenser’s capacity must be enough to reheat the air and hold the chamber temperature. If either condition fails, the air loop cannot dry.

2. The state points

Point Typical temperature What it means
Air leaving the sludge bed 30–40 °C, near saturation Warm, wet air carrying the evaporated water
Air leaving the evaporator 25–35 °C, dew point reduced Cooled and dehumidified; water condenses
Air leaving the condenser 50–70 °C Reheated, relative humidity low, ready for the bed
Air entering the bed 45–65 °C The drying potential is the humidity ratio difference
Exhaust 5–10% of the loop flow Controls humidity and odor, loses some heat

The temperatures are indicative, not universal. The design values depend on the sludge, the target moisture and the refrigerant. A unit that claims 70 °C supply air and a 25 °C evaporator is asking for a large temperature lift; the compressor power reflects that lift.

3. The dehumidification equation

The water removed per hour is:

m_w = V × ρ × (d_in − d_out)

where m_w is kg/h, V is the volumetric flow in m³/h, ρ is the air density in kg/m³ (about 1.1–1.2 at these temperatures) and d is the humidity ratio in kg water per kg dry air.

Example: 20,000 m³/h, air entering the coil at 45 g/kg and leaving at 25 g/kg, density 1.2 kg/m³:

m_w = 20,000 × 1.2 × (0.045 − 0.025) = 480 kg/h

At 480 kg/h, the dryer removes about 11.5 t/day if it runs continuously. That is the evaporator’s water rate, not the sludge feed rate. The feed rate follows from the inlet and outlet moisture.

4. What changes the rate

Air flow. More air carries more water, but the fan power rises with the cube of the flow and the pressure drop rises with the square. A fan that is increased without checking the coil face velocity can carry water droplets into the duct.

Humidity ratio difference. A lower evaporator temperature lowers the leaving humidity ratio, but it also lowers the evaporating pressure and the compressor capacity. There is an optimum, not a “colder is better”.

Air temperature. Warmer air holds more water at saturation and gives a larger drying potential, but it also raises the condenser load. The chamber temperature is a balance between drying rate and sludge handling.

Exhaust ratio. A 5–10% exhaust prevents the loop from saturating, but every percent of exhaust carries heat out. Too much exhaust lowers the chamber temperature; too little raises the humidity and slows drying.

5. Energy per metric ton of water

A low-temperature dehumidification dryer typically uses 0.25–0.45 kWh per kg of water removed, or 250–450 kWh per metric ton. In a well-designed loop with heat recovery, the figure can be 220–320 kWh/t; a poorly controlled loop with excess exhaust and a fouled coil can exceed 400 kWh/t.

The specific energy is a better comparison than the compressor kW. A 100 kW compressor that removes 300 kg/h uses 333 kWh/t; a 90 kW compressor that removes 250 kg/h uses 360 kWh/t. The smaller machine is the less efficient dryer.

6. Three field symptoms

The dryer holds temperature but does not dry. Check the humidity ratio difference and the air flow. A high leaving humidity means the evaporator is not condensing, or the exhaust is closed and the loop is saturated.

The coil ices. The evaporator surface is below 0 °C, or the air is too humid for the coil. Check the defrost or coil-protection logic and the refrigerant charge. Ice blocks the air path and the drying rate falls sharply.

The condensate volume is low. Water is leaving with the product or with the exhaust, or the coil is not condensing. Measure the discharge moisture and the exhaust humidity; the drain is the third place to look, not the first.

Open or closed loop: the exhaust ratio

A closed-loop dehumidification dryer reuses most of the heat, but it cannot be fully closed. The air picks up water from the sludge; if none is exhausted, the humidity rises until the evaporator can no longer condense water. The exhaust ratio is the control that trades drying speed against energy.

Exhaust ratio Chamber humidity Drying speed Energy Odor load
0% Saturated Stops Low, but the batch stalls None
3–5% High Slow Low Small
5–10% Moderate Normal Medium Medium
Above 15% Low Fast High Large

At 0% exhaust, the chamber reaches saturation and drying stops. At 3–5%, the unit is stable but slow; at 5–10%, most designs run normally. Above 15%, the air is drier and the sludge dries faster, but the make-up air must be heated and the odor unit sees a larger load. A site that opens the damper to 20% to chase output often gains little drying and pays about 30% more energy.

The exhaust ratio is not a fixed damper position. It should be set by the chamber humidity and the product moisture, then checked against the energy per metric ton. If the ratio is too low, the coil runs wet and the compressor works against a high evaporating pressure; if it is too high, the condenser is reheating cold make-up air. Both look like “the dryer is slow” but have opposite fixes.

Heat recovery from the exhaust is the next step. A sensible and latent exchanger can preheat the make-up air and cut 5–10% of the energy, but it adds pressure drop and a fouling surface. It pays on large, continuous lines, not on a small batch unit that runs four hours a day. Longcom’s sludge dryer page gives the loop and exhaust configurations behind these values.

Common questions

Does a lower evaporator temperature always dry faster?

No. It lowers the leaving humidity ratio but also lowers the compressor capacity and increases the risk of icing. The optimum is a design choice.

Why is the supply air at 60 °C when the chamber is 50 °C?

The condenser reheats the air above the chamber temperature to keep the relative humidity low. The chamber temperature is set by the sludge, not by the supply air alone.

How much fresh air does the loop need?

Usually 5–10% exhaust, with make-up air to balance. The exact figure depends on the odor system and the humidity control.

Can I calculate the dryer capacity from the compressor kW?

Only as a rough check. The water rate comes from the air flow and the humidity ratio difference, and the compressor must be sized for that duty.

What is the most common cause of a low drying rate?

A fouled evaporator or a closed exhaust. Both reduce the humidity ratio difference without changing the temperature display.

Is 300 kWh/t a good number?

It is a reasonable target for a low-temperature dehumidification dryer with heat recovery. Compare it at the same inlet and outlet moisture, not across different duties.

What drives the drying rate?

The humidity ratio difference between the air and the product, the air flow and the contact. Compressor kW is secondary. A cold coil below dew point is the first requirement.

How do I set the loop?

Balance the evaporator air, the reheat and the bypass. Measure the condensate. A loop that is too cold may frost; too warm will not dry.

Further technical reading

LONGCOM can calculate the air-side duty, the humidity ratio difference and the specific energy for a specific sludge and climate. For a psychrometric review, contact 400-878-0280 or 13002001280.