Heat Pump vs Electric Heater: The Supply Question

The usual comparison between a heat pump and an electric resistance heater is an energy-cost comparison. It is valid, but incomplete. A 6 m³/day hot-water load can be served by either technology, yet the electrical supply behind them is not the same. One may need a 100 kW feeder and a transformer upgrade; the other may fit the existing supply with a buffer tank. That difference can decide the project before the first electricity bill arrives.

This article keeps the energy numbers, then adds the supply chain: peak kW, cable, breaker, transformer and storage. It does not repeat the full running-cost comparison, which is covered in a separate article.

One metric ton of hot water: 46.4 kWh of heat

Heating 1 metric ton of water from 15 to 55 °C requires 1,000 × 4.187 × 40 ÷ 3,600 ≈ 46.4 kWh. A resistance heater at 95% efficiency draws about 49 kWh. A heat pump at a system COP of 3.5 draws about 13 kWh. At a unit price of CNY 0.80/kWh, the energy cost is about CNY 39 for resistance and CNY 10.6 for the heat pump. The saving is real, and it is the reason heat pumps dominate large hot-water loads.

But the same arithmetic shows the supply problem. To deliver 46.4 kWh in one hour, resistance needs a 49 kW input. The heat pump needs about 13 kW input for the same hour, but it cannot deliver the heat instantaneously from a small unit unless a tank is in the circuit. The comparison is between a large instantaneous load and a smaller, longer load with storage.

Peak kW is the binding constraint

For a dormitory using 6 m³/day, the daily heat is 279 kWh. A resistance system at 49 kWh/t needs about 294 kWh/day. If the load is drawn over three hours, the average input is 98 kW; without storage, the connected load must cover the instantaneous draw, which can be higher. A 98 kW load at 400 V, three-phase, power factor 0.95, draws about 149 A. That is a significant service, not a spare circuit in a distribution board.

A heat pump with a 30 kW thermal unit and an input of about 8.6 kW at COP 3.5 can produce 279 kWh in roughly 11.6 hours. In winter, at a derated 24 kW thermal and about 6.9 kW input, the same daily heat takes about 11.6 hours. The electrical peak is under 7 kW per module, and two modules can be staged. The price is a 5 m³ buffer tank and a control strategy that pre-heats outside the peak.

Item Resistance heater Heat pump with buffer
Daily heat demand 279 kWh 279 kWh
Daily electricity About 294 kWh About 80 kWh at COP 3.5
Typical input per module 49 kW for a 1 t/h unit 8.6 kW for a 30 kW thermal unit
Peak electrical load About 98 kW for a 3 h draw About 17–20 kW with two modules and tank
Storage required Optional, but improves diversity Essential: 5 m³ for this example
Supply upgrade risk High Low to moderate

The table is a scheme-stage comparison, not a design. The actual peak depends on the draw profile. A 6 m³/day load spread over 12 hours needs only 25 kW of resistance, which may fit an existing service. A three-hour peak is the case that forces the upgrade.

Cable, breaker and transformer

For a 98 kW resistance load, a 150 mm² copper feeder may be needed, with a 160 A breaker and a dedicated distribution board. The transformer headroom may be insufficient, especially in an existing building with air-conditioning and kitchen loads. The utility connection fee and the switchgear can add a substantial capital cost that is not in the heater quotation.

For the heat pump, the electrical design is smaller but not trivial. Two 30 kW thermal modules at 6.9–8.6 kW input each need two circuits, isolation, surge protection and a control interlock with the tank. If the units are inverter-driven, the starting current is low; if fixed-speed, check the starting method and the generator capacity if standby power is required.

A 6 m³/day dormitory

Take a 100-person dormitory with a three-hour evening peak. The resistance option needs about 98 kW at the peak and a large service. The heat pump option uses two 30 kW thermal modules, a 5 m³ tank and a pre-heat window from 22:00 to 06:00. The tank covers the evening peak, and the modules recharge overnight. The electrical peak is about 17 kW, and the existing service may not need a transformer upgrade.

The heat pump option also needs floor space for the tank and plant, and a structural check if the tank is on the roof. Those costs belong in the comparison. A resistance system with a small tank can be more compact, but its cable and switchgear are larger. The cheapest first cost is not always the cheapest installed cost.

When a hybrid makes sense

A hybrid uses a heat pump for the base load and a small resistance or electrode boiler for the peak. The heat pump runs at high COP for most of the year; the booster covers the few hours when the tank is depleted. The electrical service is sized for the booster plus the heat pump, but the booster can be much smaller than a full resistance system.

Hybrids are useful where the supply is capped, where the winter COP falls sharply, or where the building needs a backup heat source. They are not useful where the tank can be enlarged at low cost and the supply already has headroom. The control priority should be: heat pump first, tank second, booster last.

Common questions

Is a heat pump always cheaper to run?

At a COP above about 2.5 and a normal electricity tariff, yes, it is usually cheaper per kWh of heat than resistance. At a very low COP, or with a large demand charge, the gap narrows. The supply cost can also change the answer.

Why does a heat pump need a tank?

Because its output is smaller than the instantaneous peak. The tank stores heat made during low-demand hours and delivers it during the peak. Without a tank, the unit would need to be sized for the instantaneous load, which removes much of the cost advantage.

Can I keep the existing electric heater as backup?

Yes, if the electrical interlock prevents both from running beyond the service capacity. Use the heater as a staged booster, not as a parallel full-load source. The control should bring it in only when the tank temperature falls below a set point.

How much transformer capacity is needed?

Calculate the maximum simultaneous demand, not the sum of nameplates. For the heat pump, add the modules, pumps, controls and defrost; for resistance, add the full heater load. Then check the existing transformer and the utility connection limit.

Does a buffer tank increase Legionella risk?

It can if the tank is held in the growth band for long periods. Use a weekly pasteurization cycle to 60 °C for one hour, keep the tank stratified and avoid dead legs. The tank is a hygiene asset only when it is managed.

Which option suits a small hotel?

A heat pump with a tank usually suits a hotel with a steady base load and a morning/evening peak. A small resistance booster can cover a short peak. If the hotel has a very small hot-water demand and no space for a tank, resistance may be the simpler choice.

What electrical headroom is needed?

Add the heat-pump power to the existing peak and compare with the service capacity. A heat pump may need a dedicated circuit and a larger cable. A transformer upgrade can erase the operating saving.

How should the backup heater be controlled?

Yes, and it is often wise. Keep it for peak or cold snap, with a changeover control. The backup also lets the heat pump run at its efficient base load.

Further technical reading

For the energy-cost comparison, see Heat Pump versus Electric Water Heater. For the supply voltage, see 220 V or 380 V. For the demand calculation, see How to Calculate Hot Water Demand. For the tank match, see Matching Heat Pump Capacity to Storage Tank Volume.