A data center chiller plant has two constraints that separate it from a commercial building: it runs 8,760 hours a year, and it spends most of that time at 40–60% load. Selection therefore turns on part-load efficiency and low-load stability, not on a full-load COP headline.
Magnetic-bearing centrifugal chillers have a structural advantage in that band. They are not an unconditional answer: capacity limits, grid quality and controls support all affect whether the advantage survives.
1. The load shape
A commercial plant may run 1,800–2,600 equivalent hours; a data center runs continuously. Every 1% efficiency gain is multiplied by three to four times the hours. The sensible heat ratio is high — above 0.95 — because almost all heat comes from IT equipment and power distribution. Chilled water can therefore run at 18 °C or higher instead of 7 °C. A 2,000 kW IT load might fall to 45% at night and rise to 70% by day; operation above 90% is rare.
| Load band | Share of annual hours | Unit state | Selection focus |
|---|---|---|---|
| 80–100% | 3–5% | All units running | Full-load efficiency, noise |
| 60–80% | 25–30% | Most units running | Part-load efficiency |
| 40–60% | 45–55% | Half the units running | IPLV, stability |
| Below 40% | 15–20% | Single unit at low load | Surge avoidance, minimum load |
2. Four structural advantages of magnetic bearings
Oil-free. Magnetic bearings levitate the rotor, so there is no oil system. In a conventional centrifugal chiller, an oil film on the heat-exchanger tubes can cost 3–5% of heat transfer. Removing it also removes oil changes, oil filters and oil coolers from maintenance.
Part-load efficiency. The isentropic efficiency of a magnetic-bearing machine falls only slightly between 30% and 60% load. Its IPLV can reach 9.5–11.5, against 6.0–6.5 for a conventional centrifugal. In a plant that lives at 40–60%, that is the main economic argument.
Low starting current. A variable-speed drive keeps starting current at or below rated current. A direct-on-line fixed-speed centrifugal may draw two to three times rated current; the transformer capacity can be one frame smaller with the magnetic-bearing machine.
No surge at low load. A conventional centrifugal may need hot-gas bypass below about 25% load; the bypass itself wastes energy. A magnetic-bearing machine can run down to about 10% without surge.
| Item | Magnetic-bearing centrifugal | Conventional centrifugal | Plant implication |
|---|---|---|---|
| Bearings | Magnetic, oil-free | Hydrodynamic, oil system | No oil maintenance; no oil-film resistance |
| IPLV | 9.5–11.5 | 6.0–6.5 | Part-load energy difference above 30% |
| Starting current | ≤ rated | 2–3 × rated (soft start) | Smaller transformer margin |
| Minimum load | About 10%, no surge | About 25%, bypass needed | Better night operation |
| Unit capacity | 100–1,500 kW | Above 3,000 kW possible | Very large duties need multiple units |
| Capital | 20–35% higher | Base | Recovered through running cost |
3. N+1 and high-temperature chilled water
For a 2,000 kW IT load and about 2,100 kW cooling, four 700 kW magnetic-bearing units — three duty, one standby — provide N+1. If one unit fails or is maintained, the other three can carry 2,100 kW. But if the live load is already at 80% of design, losing one unit leaves only 1,400 kW; the operator must shed load or bring in additional capacity. N+1 is not a guarantee at every load level; it must be checked against the actual load.
High-temperature chilled water at 18/24 °C (6 K difference) cuts flow: 2,100 × 0.86 ÷ 6 = 301 m³/h, against 361 m³/h for 7/12 °C — about 17% less. Pumps and pipe sizes can drop one frame. More importantly, the evaporating temperature rises from about 5 °C to 16 °C, improving chiller efficiency by 25–30%.
The catch is the terminal. Computer-room air handlers and in-row or rear-door coils must be selected for 18 °C supply water. If the existing coils were sized for 7/12 °C, they will not deliver the required heat transfer at 18 °C; the coil rows or airflow must increase. Do not change the chiller temperature without changing the terminals.
Free cooling is the third layer. When the wet-bulb temperature is below about 12 °C, the cooling tower can supply chilled water directly or through a plate exchanger, and the chillers stop. Annual free-cooling hours are roughly 2,800 in Beijing, 1,800 in Shanghai and 800 in Guangzhou. Direct free cooling is more efficient than indirect, but water quality requirements are higher.
4. Reliability is a system property
The chiller is only one part of a reliable plant. Four items belong in the scheme:
- Ring main. A looped chilled-water header lets one section be isolated without stopping the hall; terminals have dual connections with automatic changeover.
- Thermal storage. A buffer of 15–20 minutes, about 525–700 kWh for 2,100 kW, or 75–100 m³ at a 6 K difference. Its job is to ride through utility transfer and chiller restart, not to shift peak load.
- Controls. The plant controller must start a standby unit within 30 seconds of a failure and hold supply temperature within ±1 K. Test the logic with fault injection, not only in normal operation.
- Water quality. Magnetic-bearing heat exchangers are compact; scale has a proportionally larger effect. Cooling water needs dosing and side-stream filtration; chilled water needs make-up, pressure control and de-aeration.
5. Life-cycle example
Four 700 kW magnetic-bearing units, three duty and one standby, 2,100 kW cooling, 3,500 equivalent full-load hours: annual cooling 7,350,000 kWh. At an average COP of 7.0, electricity is 1,050,000 kWh. A conventional centrifugal at 5.2 uses 1,413,000 kWh. The saving is 363,000 kWh; at USD 0.09/kWh, about USD 32,700 a year.
If the magnetic-bearing plant costs 25% more — about USD 87,500 on a USD 350,000 base — simple payback is 2.7 years. Add USD 5,000 a year of oil-system maintenance savings and it falls to about 2.3 years. At 2,000 hours, the payback stretches beyond six years, and the case weakens.
6. Where not to use magnetic bearings
Very large single-unit duty. Magnetic-bearing unit capacity is limited; above 1,500 kW, multiple heads or multiple units are needed, and the reliability benefit of one large machine may be lost. A conventional centrifugal may be the better choice for a very large, few-unit plant.
Weak or unstable grid. The drive and bearing controller are sensitive to voltage dips. A site with frequent sags needs a UPS or stabilizer; the added cost belongs in the comparison.
Thin maintenance capability. The controls are complex and diagnostics often depend on remote support. A remote site with no trained team may lose more in downtime than it saves in energy.
7. Common questions
Is a magnetic-bearing chiller always more efficient?
In the 30–70% band it can be 30% better; at full load the gap narrows to 5–10%. A data center lives in the part-load band, so the benefit is real. A plant that runs at full load continuously sees much less.
Can 18/24 °C water cool the IT hall?
Yes, but the terminal coils must be reselected for 18 °C supply. Reusing 7/12 °C coils can lose more than 20% of heat transfer. The chiller and the terminals must be designed together.
Should the standby unit be rotated?
Yes. A unit that never runs can suffer capacitor aging in the drive and controller. Rotate it for about four hours a week through the plant controller.
How large should the buffer be?
About 15–20 minutes of cooling load. For 2,100 kW and a 6 K difference, that is roughly 75–100 m³. It supports transfer and restart; it is not a peak-shaving device.
Can 18/24 °C water be used in an existing data center?
Only if the terminal coils are reselected for the higher supply temperature. Reusing 7/12 °C coils can lose more than 20% of heat transfer, so the chiller and terminals must be designed together. Check the IT inlet envelope, terminal capacity and humidity control before changing the water temperature.
How should N+1 chillers be rotated and buffered?
Rotate the standby unit for about four hours a week so the drive and controller do not sit idle. Provide roughly 15–20 minutes of thermal buffer — about 75–100 m³ at 2,100 kW and a 6 K difference — to support transfer and restart; it is not a peak-shaving device.
Why magnetic bearings?
They remove oil and reduce friction at high speed. The result is a compact, efficient chiller for a data hall.
What redundancy?
N+1 on the largest unit or a standby module. The data hall cannot lose cooling during service.
Related reading
For product specifications, see water chiller systems. For selection guides, visit the chiller knowledge base. Related articles: Piston, Scroll or Screw Chillers: Selection by Load Profile, Not Capacity Alone, GB 19577-2024: How to Read Chiller Efficiency Labels and Use Them in Tenders. To discuss a project, contact our engineering team. · Water Chiller Sizing · Chiller Part Load Selection · Chiller Plant Group Control
Longcom Environmental Protection Equipment Co., Ltd. can review IT load curves, N+1 configuration, high-temperature terminal compatibility and plant controls. Contact 400-878-0280 or admin@longk.com with the IT load profile and cooling design.
Load shares, efficiency values and cost figures are typical estimates; final design must use the IT load curve, local weather, terminal selection and manufacturer data.