Hotel hot-water calculations often start and end with the room count. Two guests per room at 60 L each gives a neat daily figure, and the plant is sized to it. The laundry, the kitchen, the spa and the staff changing rooms are left as an allowance. In a city hotel, that allowance can be 30–40% of the total, and it arrives in peaks that the room load does not.
This article builds a 200-room example from the bottom up. The numbers are planning values; the project must use its own occupancy, laundry contract and kitchen schedule.
Start with the guest load
At 200 rooms, 1.8 guests per room and 60 L per guest per day at 55 °C, the guest demand is 200 × 1.8 × 60 = 21,600 L/d. At 2.0 guests, it is 24,000 L/d. The difference is 10%, which is why occupancy should be stated rather than assumed.
The source guidance for hotels is 50–80 L per guest per day at 55 °C. Use the lower end for a business hotel with showers and the upper end for a resort with baths. Do not use a residential figure; hotel guests shower at different times and expect instant hot water.
Laundry is a separate load
A hotel with its own laundry may process 3–5 kg of linen per room per day. At 200 rooms and 4 kg, that is 800 kg/d. A tunnel washer uses about 8–12 L/kg; a conventional washer may use 15–20 L/kg. At 15 L/kg, the laundry alone is 12,000 L/d of hot water, half the guest load again.
If laundry is outsourced, the load disappears from the site but the linen replacement cost may rise. If it is on site, the laundry usually runs a morning shift and needs 60–70 °C water, hotter than the guest loop. That changes the storage and the heat-pump delivery temperature.
Kitchen demand is peaked
Kitchen hot water is used for sinks, dishwashers, cleaning and hand-wash basins. A planning allowance is 10–15 L per meal, with dishwashers and pot-wash sinks taking the larger share. At 500 meals/day and 12 L, the kitchen needs 6,000 L/d at 60 °C.
The kitchen peak is short. A dinner service may draw 30% of the daily kitchen water in two hours. If the kitchen has its own storage, the main plant can see a smaller, steadier load. If it is fed directly from the guest loop, the dinner peak will depress the guest supply temperature.
The total is not the sum at the peak
| Load | Daily hot water at 55–60 °C | Peak character |
|---|---|---|
| 200 guest rooms | 21.6–24.0 m³/d | Morning and evening, 2–3 h each |
| Laundry, 800 kg/d | 12.0 m³/d at 15 L/kg | Morning shift, 4–6 h |
| Kitchen, 500 meals/d | 6.0 m³/d at 12 L/meal | Lunch and dinner, 1–2 h |
| Spa and staff | 2.0–4.0 m³/d | Afternoon and evening |
| Total | 41.6–46.0 m³/d | Diversity across the day |
The total is 42–46 m³/d, roughly double the guest-only figure. The peak is not the sum of every peak; laundry and guest demand overlap in the morning, while the kitchen peaks later. A diversity factor of 0.8–0.9 on the connected load is reasonable, but it must be checked against the actual schedules.
Heat, plant and storage
For 42 m³/d from 15 to 55 °C, the daily heat is 42,000 × 40 × 4.18 ÷ 3,600 = 1,951 kWh. At a winter system COP of 3.0, the electricity is 650 kWh/d. If the plant runs 14 h, the average input is 46 kW; a 3 × 25 kW installation gives N+1 and covers the morning ramp.
Storage should be 30–60% of daily demand for a hotel, with the upper end where the morning peak is sharp. At 45 m³/d, 50% is 22.5 m³. A 20 m³ tank plus a 5 m³ laundry tank is easier to control than one 25 m³ tank, because the laundry can run at a higher temperature without overheating the guest loop.
Keep the tanks stratified. A single tank with a fast return can be fully mixed in an hour, and the useful capacity falls to 30–40% of the nominal volume. Use a baffle, a low inlet velocity and a return that enters near the top.
Control the peaks, not just the temperature
Give the laundry and kitchen priority signals. When the laundry calls for heat, the guest loop should not be allowed to fall below 45 °C. A simple sequence: maintain the guest tank at 55 °C, allow the laundry to draw to 60 °C only when the guest tank is above 50 °C, and shed the laundry after a timeout if the guest temperature continues to fall.
Install a return pump on the guest loop and insulate both supply and return. A 20 mm insulation layer is a minimum; without it, distribution loss can exceed 10% of the heat delivered. Balance the returns so the furthest bathroom reaches temperature within 10–15 seconds.
What to put in the enquiry
Send the room count, occupancy, laundry kg/d and whether it is on site, meal count, spa demand, the coldest water temperature, the required outlet temperature and the available power. A supplier who quotes on room count alone will undersize the plant or oversize the storage. The enquiry should also state the peak hour and the acceptable temperature drop during laundry.
Common questions
How much hot water does a hotel guest use?
Plan 50–80 L per guest per day at 55 °C. A business hotel is nearer 50–60 L; a resort with baths is nearer 70–80 L. Use actual occupancy, not room count.
Does laundry really need its own hot-water load?
Yes, if it is on site. At 3–5 kg of linen per room per day and 15 L/kg, a 200-room hotel can add 9–15 m³/d. That is too large to treat as a rounding allowance.
Can the kitchen share the guest hot-water tank?
It can, but the kitchen peak is short and hot. A separate kitchen storage or a priority control is better. Otherwise the dinner service can pull the guest loop below a comfortable temperature.
How big should the hot-water tank be?
For a hotel, 30–60% of daily demand. A 200-room hotel with laundry and kitchen at 45 m³/d needs about 20–25 m³ of usable storage, split if the laundry needs a higher temperature.
Why does a 200-room hotel need more than 200 × 60 L?
Because the guest load is only part of the demand. Laundry, kitchen, spa and staff add 30–40%, and their peaks do not coincide neatly with the guest peaks.
What if the hotel has no laundry?
Remove the laundry load but keep the kitchen, spa and staff loads. The daily total may fall by 25–30%, but the morning guest peak remains; storage and recovery still need to be checked.
How much do laundry and kitchen add?
Laundry can add 20–30% and kitchen 10–20%, depending on size and schedule. Measure the actual equipment flow and hours. Do not size the hotel on room count alone.
Should I separate the circuits?
Separate laundry, kitchen and guest hot water if the temperatures or schedules differ. Isolation limits downtime and lets each load run at its own setpoint. A single loop is simpler but couples the peaks.