The most common technical error in a villa heat-pump project is treating a domestic hot-water heat pump as a combined underfloor heating and air-conditioning unit. A capacity table taken at 55 °C outlet is used to cover a heating load that should be calculated at 35–40 °C. The result is insufficient cooling in summer, water that cannot be lowered sufficiently in winter, and a machine that short-cycles between the two.
The same compressor can differ by more than 40% in both capacity and efficiency between 35 °C and 55 °C outlet. Once the operating condition is defined incorrectly, every downstream decision — unit size, buffer volume, pump duty and changeover logic — inherits the error.
A combined unit and a hot-water unit are not the same sample
A combined heating and cooling unit performs two different tasks across the year. In winter it takes heat from outdoor air and delivers 35–45 °C water to underfloor loops. In summer it moves heat from the rooms to outdoor air and delivers 7–12 °C chilled water to fan coils. The evaporator and condenser swap roles, and pressure ratio, refrigerant mass flow and expansion-valve opening all change.
Low-temperature heating saves energy because the pressure ratio is lower. With outdoor air at 7 °C and supply at 40 °C, condensing is about 45 °C and the pressure ratio is around 2.6. Raising supply to 55 °C raises condensing to about 60 °C and the pressure ratio above 3.5. Each 0.5 increase in pressure ratio reduces volumetric efficiency, raises discharge temperature and lowers both capacity and COP.
| Supply temperature | Typical use | Relative capacity | COP reference | Machine requirement |
|---|---|---|---|---|
| 35 °C | Underfloor heating, low-temperature radiant | 1.00 | 4.0–4.6 | Standard combined-unit condition |
| 40 °C | Upper limit for underfloor heating | 0.93 | 3.6–4.2 | Verify the relevant sample row |
| 45 °C | Radiators, fan-coil heating | 0.85 | 3.1–3.7 | Low-temperature machine may cover |
| 55 °C | Domestic hot water, high-temperature radiators | 0.70–0.75 | 2.5–2.9 | Hot-water machine required |
The table shows the trend for one low-temperature machine; it is not a substitute for the manufacturer’s data, because compressor and heat-exchanger designs differ, especially above 45 °C. A second difference is often ignored: domestic hot water is heated once to 55 °C and stored, whereas a combined unit circulates at 35–40 °C for long periods. The latter places greater demand on stable operation at low load. Once the floor reaches temperature, the actual load may be only 20% of design. If the machine cannot unload to that level, it runs ten minutes and stops five, and the COP is consumed by starting losses. This is where inverter control earns its cost, not in the nominal capacity figure.
Calculate winter and summer loads separately, then take the larger
Winter heating and summer cooling cannot share one load number. Winter is governed by envelope heat loss; summer by solar and internal gains. For a 300 m² detached house with insulation meeting current energy standards and low-E double glazing, a winter index of 60 W/m² gives 18 kW, while a summer index of 90 W/m² gives 27 kW. These are design-day peaks, not annual averages. Add 10% for distribution and equipment margin: 19.8 kW winter and 29.7 kW summer.
Select the unit on the larger value, a nominal 30 kW combined unit. Then check the winter condition: at 7 °C outdoor and 40 °C supply, the actual heating capacity may be only 85–90% of nominal cooling capacity, or 25–27 kW, which covers 19.8 kW. North of the Yangtze, at −7 °C outdoor, capacity may fall to 55–60% of nominal, or 17–18 kW, below the design load. That project needs electric backup or one size larger.
Annual electricity can be estimated from the same loads. Winter: 120 days, 8 effective hours per day, average load factor 0.6, COP 3.8: 18 × 960 × 0.6 ÷ 3.8 ≈ 2,730 kWh. Summer: 90 days, 8 hours, load factor 0.5, COP 3.2: 27 × 720 × 0.5 ÷ 3.2 ≈ 3,040 kWh. Total about 5,800 kWh, or about 3,480 CNY at 0.6 CNY/kWh. A gas boiler at 90% efficiency and 10 kWh/m³ would use about 1,152 m³ for winter alone, costing about 3,690 CNY at 3.2 CNY/m³. The comparison only holds at the assumed tariffs; it is not a universal conclusion.
Buffer tank and manifold decide whether the system is stable
The underfloor loops contain a significant water volume, but the flow on the unit side and the flow on the emitter side rarely match. A buffer tank decouples them. If it is too small, the unit sees a change in return temperature before its outlet has stabilized and short-cycles. If it is too large, heat-up is slow, space is wasted and the first start takes a long time.
Two estimates should agree. From pipe volume: DN20 underfloor pipe at 150 mm spacing is about 6.7 m per m²; with a 16 mm bore, water volume is about 0.2 L/m, so 300 m² gives about 400 L. From minimum run volume: a 30 kW unit at 5 K difference has a flow of 30 ÷ (1.163 × 5) ≈ 5.2 m³/h; if the protection logic requires three minutes of continuous running, the minimum system volume is 5.2 × 3 ÷ 60 ≈ 0.26 m³. Adding the two and leaving margin gives 0.6–1.0 m³; 0.8 m³ is reasonable for this example.
Divide the manifold into 15–20 m² per circuit, so 300 m² needs 15–20 circuits at about 0.2–0.3 m³/h each. Each circuit needs a flow meter or balancing valve. Without balancing, the circuits near the header overheat and the far circuits stay cold, and the owner concludes that the unit is undersized. The underfloor pump should be selected for 3–4 m³/h at the worst-loop resistance plus 3–5 m head, with variable-speed control on differential pressure. The unit-side pump should be separate; do not use the underfloor pump to serve both sides, because the temperature difference and resistance requirements are different.
| Item | Example value | Basis | Site check |
|---|---|---|---|
| Winter design heat load | 18 kW | 300 m² × 60 W/m² | Verify insulation and glazing |
| Summer design cooling load | 27 kW | 300 m² × 90 W/m² | Verify glazing area and orientation |
| Nominal cooling capacity | 30 kW | Larger load plus 10% | Check the relevant sample row |
| Buffer volume | 0.8 m³ | 0.4 m³ pipe volume + start volume | Watch outlet temperature stability |
| Underfloor flow | 3.1 m³/h | 18 ÷ (1.163 × 5) | Balance each circuit with a meter |
| Manifold circuits | 15–20 | 15–20 m² per circuit | Check return temperature by touch |
Changeover logic and three site failures
Mode change should not depend on manual valves. In spring and autumn, a building may need cooling by day and heating at night. The controller should decide from outdoor and room temperature, and should complete a stop delay before reversing the refrigerant direction. The reversing valve needs a pressure difference; the compressor must remain stopped for at least three minutes before changeover. This should be fixed in the control program, not left to the installer.
Frost protection is a real villa risk. Many owners leave the system in low-temperature operation rather than shutting it down. The water side should contain antifreeze or keep the pump running at low speed. The unit’s own frost protection only works if the sensor is intact; a sensor that has fallen off or scaled over reads high, the protection does not act, and a cold snap can split the underfloor loops. The outdoor unit’s condensate drain needs slope and a trap, otherwise defrost water freezes in the base pan and gradually blocks the lower part of the coil.
The third failure is treating domestic hot water as part of the heating loop. A combined unit serves heating and cooling; it cannot supply potable hot water directly from the underfloor circuit. The heating circuit is closed at 35–45 °C, while hot water must be stored at 55 °C and meet hygiene requirements. Use a plate heat exchanger or a separate hot-water heat pump. If a villa needs heating, cooling and hot water, the usual arrangement is a combined unit plus a hot-water unit, or a combined unit with a declared hot-water mode, using the hot-water condition data rather than the heating data.
Common questions
Can a combined unit replace a gas boiler directly?
It can replace the heating function, but check two things: the actual heating capacity at the local design outdoor temperature, and whether the existing radiators can work at 45 °C or below. Old cast-iron radiators designed for 75 °C may deliver only about 55% of their rated output at low temperature, so they need more sections or a different emitter.
Why does 35 °C underfloor heating use so much less electricity than 55 °C hot water?
Supply temperature sets condensing temperature, and condensing temperature sets pressure ratio. At 35 °C the ratio is about 2.6; at 55 °C it exceeds 3.5. The COP difference of 40–50% is thermodynamic, not a brand effect.
What buffer volume suits a 300 m² villa?
The example gives 0.6–1.0 m³, with 0.8 m³ selected. The check is the loop volume of about 0.4 m³ plus the volume needed for three minutes of minimum run, then margin. Above 1.5 m³ is rarely necessary in a villa and slows heat-up.
Should summer and winter use different unit sizes?
No. Select one unit on the larger of the two loads, then verify the other condition. In severe cold regions, the winter low-temperature capacity may exceed the summer load, and the winter condition governs.
If the floor is not warm, is the unit undersized?
First measure supply and return temperature at each manifold circuit. If the overall difference is below 3 K and flows are uneven, the problem is hydraulic balance. If the overall difference exceeds 8 K and distant circuits are cold, check strainers and loop length. Only if the supply temperature itself cannot reach setpoint should unit capacity or low-temperature derating be considered.
Can the combined unit and underfloor loop share one hot-water tank?
No. The heating loop is closed at 35–45 °C; potable water must be stored at 55 °C or above with Legionella control, and the water quality requirements differ. Use a separate hot-water tank with a plate heat exchanger, or a hot-water machine with declared capacity, and check both operating conditions separately.
How do I size the buffer?
Size from the peak draw gap and the heat-pump output, not from the floor area. A 300 m² villa may need 500–1,000 L. Check the recovery time.
Can one unit do all three?
Only if the temperatures and simultaneity allow. Heating, cooling and hot water may conflict. A combined unit is convenient but couples the loads.