Heat-Pump Energy per Metric ton of Hot Water

“How many kWh does it take to heat one metric ton of hot water?” is a fair question with a misleadingly simple answer. The heat demand is fixed by physics; the electricity demand is not. It depends on the temperature rise, the ambient condition, the heat pump’s COP at that condition, and the boundary of the measurement.

Start with the heat, then divide by a realistic COP. A quotation that uses the nominal COP for a winter project is not a calculation; it is a hope.

1. The heat demand is fixed

For water, the energy needed is:

Q = 1.163 × volume in m³ × temperature rise in K.

One metric ton of water is one cubic meter. Heating from 15 °C to 55 °C is a 40 K rise, so Q = 1.163 × 1 × 40 = 46.5 kWh. That heat is the same whether it comes from a heat pump, an electric element or a gas burner.

Temperature rise Heat per metric ton Electricity at COP 4.0 Electricity at COP 3.0 Electricity at COP 2.2
30 K (15–45 °C) 34.9 kWh 8.7 kWh 11.6 kWh 15.9 kWh
40 K (15–55 °C) 46.5 kWh 11.6 kWh 15.5 kWh 21.1 kWh
45 K (10–55 °C) 52.3 kWh 13.1 kWh 17.4 kWh 23.8 kWh
50 K (5–55 °C) 58.2 kWh 14.6 kWh 19.4 kWh 26.5 kWh

The table already shows the range: the same metric ton of water can require 8.7 or 26.5 kWh of electricity depending on the temperature rise and the COP. A single “kWh per metric ton” figure without those two conditions is not a specification.

2. COP is a site number, not a label number

A heat pump’s nominal COP is usually measured at a mild ambient condition and a moderate outlet temperature. In winter, the evaporating temperature falls and the condensing temperature rises, so the compressor lifts against a larger difference and the COP drops. The effect is large enough to change the electricity bill by 50% or more.

Condition Typical COP Electricity per metric ton, 40 K rise
20 °C ambient, 55 °C outlet 4.2 11.1 kWh
7 °C ambient, 55 °C outlet 3.5 13.3 kWh
−7 °C ambient, 55 °C outlet 2.4 19.4 kWh
−15 °C ambient, 55 °C outlet 1.9 24.5 kWh

The values are indicative; a specific model’s low-temperature table should replace them. The important point is that the winter COP, not the catalog COP, sizes the electricity supply and the operating budget.

3. Two worked examples

A 10 HP unit. A 10 HP unit with 39 kW heating capacity and 10.5 kW input has a nominal COP of about 3.7. Running at full load for one hour produces 39 kWh of heat. One metric ton at a 40 K rise needs 46.5 kWh, so the unit needs about 1.19 hours and 12.5 kWh of electricity. That is close to the 11.6 kWh from the COP 4.0 column, because the nominal condition is mild.

One metric ton per day for a year. At 15 °C inlet, 55 °C outlet and an annual average COP of 3.2, the electricity is 46.5 ÷ 3.2 = 14.5 kWh/day, or 5,290 kWh/year. At 0.7 CNY/kWh, the annual cost is about 3,700 CNY. At a winter COP of 2.4, the same daily metric ton costs 19.4 kWh, or 13.6 CNY/day; over a 120-day winter, that is 1,630 CNY instead of 1,220 CNY. The difference is the seasonal COP, not the tariff.

This is why a heat-pump proposal should show at least two conditions: an annual average and a coldest-month case. A single annual number understates the winter peak and the electrical demand.

4. What the boundary excludes

The formula covers the energy delivered to the water at the heat-pump outlet. A working system also has:

Storage loss. A tank standing at 55 °C loses heat through insulation. A well-insulated tank may lose 1–3 K over 24 hours; a poorly insulated tank can lose much more. Add 3–8% to the heat demand, depending on tank quality and draw pattern.

Circulation loss. The distribution loop and return pump add heat loss and pump energy. In a large building, another 5–10% is realistic.

Defrost loss. In cold and humid conditions, defrost consumes energy without producing useful heat. Add 8–12% for a cold-climate site.

Part-load cycling. A unit that starts and stops frequently spends energy on each start and runs below its best efficiency. A buffer tank and a wider differential reduce this, but they do not eliminate it.

A practical planning figure is therefore 10–20% above the outlet heat calculation. Do not use the bare formula as a guarantee number; use it as the thermodynamic minimum.

5. Compare with electric and gas honestly

An electric element has a COP of about 1.0, so one metric ton at a 40 K rise uses 46.5 kWh. At 0.7 CNY/kWh, that is 32.6 CNY. A heat pump at a winter COP of 2.4 uses 19.4 kWh, or 13.6 CNY, a saving of 58%. At a summer COP of 4.0, the saving is 75%.

A gas boiler at 90% efficiency and 10 kWh/m³ burns 46.5 ÷ 0.9 ÷ 10 = 5.2 m³. At 2.8 CNY/m³, that is 14.6 CNY, close to the winter heat-pump cost. The heat pump’s advantage over gas is smaller in winter and larger in mild weather; the local gas and electricity prices decide the ranking. A comparison that uses the summer COP against gas is not honest.

6. Selection consequences

Three numbers follow from the energy calculation. First, the heating capacity must cover the daily heat demand within the allowed running hours, using the winter capacity table. Second, the electrical supply must cover the compressor input at the coldest condition, not the nominal input. Third, the tank must be large enough to decouple the heat-pump run time from the draw peak.

If the calculated winter electricity is 20 kWh per metric ton and the site has 10 metric tons/day, the daily winter demand is 200 kWh before losses. A 30 kW unit running 8 hours at a winter output of 18 kW delivers 144 kWh; it is short. The answer is a larger unit, a longer run time or a bigger tank, not a higher setpoint.

Common questions

Is 11.6 kWh the standard figure for one metric ton of hot water?

Only at a 40 K rise and a COP of 4.0. At a winter COP of 2.4, the figure is 19.4 kWh. Always state the inlet, outlet and ambient conditions.

Why does the annual average COP differ from the catalog COP?

The catalog value is measured at a nominal condition. The annual average includes colder ambient, defrost, part-load cycling and standby losses. A site-specific estimate is usually 10–25% lower.

Should I use the peak or the average COP for sizing the electrical supply?

The coldest-condition COP and the corresponding input power. The supply must survive the winter peak; the annual average is for the energy budget, not the cable and breaker.

How much do tank and pipe losses add?

Typically 5–15% for a commercial system, depending on insulation, loop length and return strategy. A poorly insulated tank or a continuously running return pump can add more.

Does a higher storage temperature reduce energy use?

No. A higher tank temperature increases standing loss and lowers the COP. Store at the temperature required for Legionella control and the terminal, and blend at the point of use.

Can I compare a heat pump with a gas boiler on kWh per metric ton alone?

No. The units differ: electricity is kWh, gas is m³, and the efficiencies differ. Compare cost per metric ton at local tariffs and at the same seasonal conditions.

Why does COP change the energy number?

Electricity = heat load / COP. A lower winter COP raises the electricity per metric ton. The 46.4 kWh heat for one metric ton at 55 °C is fixed; the COP is the variable that decides the bill.

How do I calculate annual energy?

Multiply the daily heat by the number of equivalent days, divide by the seasonal COP, and add the pump and standby. Use the site’s winter COP, not the catalog value.

Further technical reading

LONGCOM can calculate the heat and electricity per metric ton at the site’s inlet, outlet and winter ambient, and size the unit and supply on the coldest condition. For an energy check, contact 400-878-0280 or 13002001280.