Sizing a chiller for an injection molding machine is often done with one of two methods. The first estimates from clamp force: 5–8 kW for 100 t, 25–35 kW for 500 t. It is fast and approximate. The second calculates the heat brought into the mold by the polymer melt. It is more accurate but needs mold and process data. Many projects use only the first method, and end up either oversized — wasting capital and running at low load — or undersized, unable to hold mold temperature and forced to extend the cycle.
The correct approach is to calculate both and take the larger result. The method below gives the formulas, a complete 300 t example and the diversity factor for a workshop with several machines.
Clamp-force estimate: fast, but know its error band
The empirical range is 0.05–0.07 kW per metric ton of clamp force. It comes from the statistical relationship between injection-unit heating power and clamp force, but individual machines vary widely. A 300 t machine running thin-wall food containers and a 300 t machine running thick-wall pipe fittings can differ by a factor of two in cooling load.
| Clamp force (t) | Estimated cooling (kW) | Chilled water (m³/h at ΔT 5 K) | Typical product |
|---|---|---|---|
| 100 | 5–8 | 0.9–1.4 | Small parts, electronics |
| 200 | 10–15 | 1.7–2.6 | Household goods, appliances |
| 300 | 15–22 | 2.6–3.8 | Tableware, automotive parts |
| 500 | 25–35 | 4.3–6.0 | Totes, appliance shells |
| 800 | 40–55 | 6.9–9.5 | Automotive interior parts |
| 1,000 | 50–70 | 8.6–12.0 | Large automotive parts |
The estimate is useful for a quick quotation and an initial screen, not for final selection. Thin-wall high-speed molding often lands above the upper bound; thick-wall long-cycle molding can land below the lower bound.
Process calculation: heat from the melt to the mold
When polymer cools from melt temperature to ejection temperature, most of the heat is removed by mold cooling water; a small fraction leaves with the part and through the open mold. The formula is Q = n × m × Cp × ΔT ÷ t, where n is the number of cavities, m is part mass in kg, Cp is specific heat in kJ/(kg·K), ΔT is melt minus ejection temperature and t is cycle time in seconds.
Example: a 300 t machine running PP food containers, 8 cavities, 45 g per part, 25 s cycle, melt 230 °C, ejection 60 °C, PP specific heat 1.9 kJ/(kg·K). Shot mass is 8 × 0.045 = 0.36 kg. Heat released is 0.36 × 1.9 × (230 − 60) = 116.3 kJ. Averaged over 25 s, the mean load is 116.3 ÷ 25 = 4.65 kW.
This is far below the 15–22 kW clamp-force estimate for a 300 t machine. There are two reasons: not all heat is removed by the mold water, and the cooling load is concentrated in the cooling phase rather than spread evenly across the cycle. Selection must use a peak value, not the mean. Multiply the calculated mean by a peak factor of 1.8–2.5, using the upper end for thin-wall parts and the lower end for thick-wall parts. The example gives 4.65 × 2.2 ≈ 10.2 kW. Compared with the 15 kW clamp-force estimate, the larger value — 15 kW — is the safer selection.
From cooling capacity to water flow and temperature
Cooling capacity and chilled-water flow are related by Q = 4.18 × m × ΔT. At a 5 K difference, each kW requires about 0.172 m³/h. A 15 kW load therefore needs about 2.6 m³/h.
Water temperature difference affects both pump and pipe size. At 5 K, flow is higher and mold temperature is more uniform; at 8–10 K, flow and pipe size fall, but the temperature difference across the mold rises and thick-wall parts can cool unevenly. Precision parts and multi-cavity molds should use 4–5 K.
| Product | Chilled water | Mold temperature | Note |
|---|---|---|---|
| General household goods | 18–22 °C | 30–50 °C | Standard machine |
| Precision electronics | 15–18 °C | 40–60 °C | ±1 °C control |
| PET preforms | 8–12 °C | 10–15 °C | Low-temperature machine |
| Thin-wall food containers | 12–16 °C | 15–25 °C | Fast cooling, high flow |
| Thick-wall pipe fittings | 20–25 °C | 40–60 °C | Large ΔT, stress control |
A chiller and a mold-temperature controller are not the same machine. The chiller removes heat from the mold and supplies water at about 8–22 °C. The mold-temperature controller holds the mold at 40–90 °C using electric heat and its own circulation. Both work on the same mold, on separate circuits or through a heat exchanger. Connecting them incorrectly produces either “the mold will not reach temperature” or “the chiller runs at full load continuously”.
For multiple machines on one chiller, each machine branch needs a stop valve and flow meter, and the main needs a differential-pressure bypass. Without a bypass, when one machine stops, the flow through the remaining machines rises and the temperature becomes unstable.
Multi-machine diversity: do not add every nameplate
Ten injection machines do not require the sum of all ten cooling loads. The load is intermittent: injection, packing and cooling each occupy part of the cycle, and the peaks do not coincide. Use a diversity factor of 0.9–1.0 for up to three machines, 0.8–0.9 for four to eight, and 0.7–0.8 for more than ten. The more machines and the more mixed the products, the lower the factor.
Example: eight machines at 15 kW each give 120 kW; with a factor of 0.85, the design load is 102 kW. Select one 110 kW machine or two 55 kW machines in parallel. The single machine has a lower capital cost, but a failure stops the whole line. Two machines allow maintenance rotation and better part-load efficiency. For precision work, two or more in parallel are preferred.
There are boundary conditions. Molds requiring below 8 °C water, such as PET preforms and some optical parts, need a low-temperature machine and glycol, not a standard chiller forced to a low evaporating temperature; the pressure ratio and discharge temperature rise and the machine will protect itself. If the workshop is above 35 °C with poor ventilation, an air-cooled chiller’s condensing temperature rises and capacity should be derated by 0.9–0.95.
Start-up load is often forgotten. After an overnight stop, the water system may be at room temperature. A 2 m³ system cooled from 30 °C to 18 °C needs 2 × 1,000 × 4.18 × 12 ÷ 3,600 ≈ 27.9 kWh. At 15 kW, that is about two hours before production can begin. If the chiller is selected only on steady-state load, the first-part delay can be half a day.
| Parameter | Recommended value | Effect of deviation | Check method |
|---|---|---|---|
| Cooling margin | 10–15% | Too much: low-load running; too little: mold over-temperature | Compare with peak load |
| Chilled-water ΔT | 4–5 K | Above 8 K: uneven mold cooling | Supply and return thermometers |
| Peak factor | 1.8–2.5 | Too low: cycle extended | Select by wall thickness |
| Diversity factor | 0.7–1.0 | Too high: wasted capital | Count machines |
| Temperature stability | ±1 °C | Precision parts out of tolerance | Continuous water-temperature record |
| Ambient derating | 0.9–0.95 above 35 °C | Short capacity in summer | mechanical room thermometer |
Common questions
What chiller size suits a 300 t machine?
Clamp-force estimation gives 15–22 kW; the process calculation often gives 10–18 kW. Take the larger, 18–22 kW. For thin-wall fast-cycle containers, use the upper end plus 15% margin, about 25 kW.
What happens if the chiller is oversized?
Capital cost rises and the machine runs below 30% load. A fixed-speed machine short-cycles and loses efficiency; an inverter machine can turn down, but very low load can cause poor oil return. Keep the margin at 10–15%.
What mold water temperature difference is correct?
Typically 4–5 K. Above 8 K suggests insufficient flow and uneven mold surface temperature, which can cause sink marks and internal stress in thick parts. Too small a difference means excessive flow and pump power.
Can several machines share one chiller?
Yes, with a diversity factor: 0.8–0.9 for eight machines. The disadvantage is single-point failure. Use two machines in parallel or one standby, especially on a continuous line.
Why do PET preforms need a low-temperature chiller?
Preform molds run at 10–15 °C and need 8–12 °C water. A standard machine at that evaporating temperature has a high pressure ratio and discharge temperature and will eventually trip. A low-temperature machine with glycol is required.
Can the chiller be installed in the workshop?
Yes, but heat and noise must be managed. An air-cooled chiller rejects heat into the workshop and can raise the ambient by 3–5 °C, which in turn reduces capacity. Prefer a ventilated separate mechanical room or outdoor location, keeping the room below 35 °C.
Clamp force or melt heat?
Use both. Clamp force sets the machine load; melt heat sets the process load. The larger of the two sizes the chiller. A 300 t PP example shows the gap.
How do I add diversity?
Use the simultaneity of the machines, not the sum. A park with 20 machines rarely runs all at full load. Measure the actual profile.