Heat-Pump Buffer Tank and Pump: Flow Before Volume

In a central hot-water system, the heat pump only makes heat. The tank and the pumps decide whether hot water reaches the tap. A 30 kW unit with a 3 m³ tank will short-cycle and run dry at the evening peak; the same unit with an 8 m³ tank may take too long to recover and lose more heat overnight. The tank volume should come from the gap between peak draw and unit output, not from a fixed liters-per-person rule.

This worked example uses a 100-person dormitory. It connects the tank, the primary pump, the return pump, the expansion vessel and the stratification details in one calculation chain.

Start with the peak gap, not liters per person

At 60 liters per person per day, the dormitory uses 6 m³/day. With water at 55 °C and make-up at 15 °C, the daily heat is 6 × 4.18 × 40 ÷ 3.6 ≈ 279 kWh. A nominal 30 kW unit derated to 0.8 in winter delivers 24 kW; over 12 effective hours it can produce 288 kWh, just enough for the day.

Demand is not spread evenly. The dormitory draws about 2 m³/h between 19:00 and 22:00, so the three-hour peak needs 6 m³. The unit produces 24 ÷ (4.18 × 40 ÷ 3.6) ≈ 0.52 m³/h, or 1.6 m³ over the same three hours. The gap is 4.4 m³. A 3 m³ tank cannot cover it, however good the insulation.

Tank volume: peak plus cycling buffer

The tank also has to buffer compressor cycling. A 30 kW unit at a 5 K primary temperature difference circulates about 5.2 m³/h. If the controller requires a minimum run time of five minutes, the minimum active volume is about 0.43 m³. Adding the peak gap and the buffer gives about 5 m³, which is the value used here. This assumes the tank is full before the peak and the unit has pre-heated during the low-tariff period. With a well-insulated tank and all-day operation, 4 m³ may be enough; with a shorter pre-heat window, 6 m³ is safer.

Application Daily use Peak pattern Typical tank share of daily use
Hotel guest rooms 100 L/person/day Spread through the day 30–50%
School dormitory 50–60 L/person/day Three-hour evening peak 70–100%
Factory dormitory 60–80 L/person/day Shift-based peaks 50–70%
Gym showers Per user Morning and evening peaks 80–100%

The percentages are scheme-stage values. The final volume should be checked hour by hour against the draw profile and the unit’s winter output.

Primary pump: unit flow and head

The primary pump moves water between the heat pump and the tank. Flow follows the unit capacity: 30 ÷ (1.163 × 5) ≈ 5.2 m³/h. Head includes the evaporator or condenser resistance, pipe friction, valves and tank entry/exit losses. In this example the total is about 16 m; with 10% margin, select 18 m. Shaft power is ρgH × V ÷ η = 1,000 × 9.81 × 18 × (5.2 ÷ 3,600) ÷ 0.65 ≈ 393 W, so a 0.75 kW motor is appropriate.

If continuity matters, use two half-flow pumps in parallel rather than one. One pump failure then leaves half the heat output, and the unit can keep running. Fit non-return valves on each pump outlet to prevent backflow through the idle pump.

Return pump: heat loss, not a timetable

The secondary return pump circulates hot water through the distribution loop. Its flow comes from pipe heat loss, not from a fixed timer. In this example the loop is about 150 m, with 30 W/m after insulation, or 4.5 kW total. At a 5 K return temperature drop, the flow is 4.5 ÷ (1.163 × 5) ≈ 0.77 m³/h. At 8–12 m head, a 0.25 kW pump is adequate.

Control the return pump by temperature: start below 45 °C and stop at 52 °C. A timer alone over-circulates in summer and under-circulates in winter. Put the return inlet in the lower-middle of the tank, not at the top; a top connection short-circuits hot water straight to the outlet and destroys stratification.

Expansion vessel and stratification

The expansion vessel is sized from the system water volume and the temperature swing. Here the tank is 5 m³, the pipework about 0.5 m³ and the unit heat exchanger 0.1 m³, giving 5.6 m³. Water expanding from 15 to 55 °C increases by about 0.8%, or 45 liters. A vessel volume of 1.5 times that is 68 liters, so an 80-liter vessel is selected. The pre-charge should equal the static pressure plus 0.1 MPa, checked after installation.

Stratification depends on connections. Hot water from the unit enters at the top; hot water to the load leaves at the top; cold make-up enters at the bottom; the return connects at the lower-middle. The top-to-bottom temperature difference should be 8–12 K. A difference below 5 K indicates short-circuiting, usually because the inlet pipe stops short of the top or the return is connected at the top. Once stratification is lost, usable capacity can fall by 30% or more, and the tank appears to “run out” just after the peak.

Legionella and freeze protection

Domestic hot water held at 40–55 °C is in the Legionella growth band. The system needs a weekly pasteurization cycle: raise the tank to 60 °C and hold for one hour, with no dead legs and no over-long branches. This is a hygiene requirement and should not be removed to save energy.

Insulate the tank and pipework separately. A 5 m³ tank with 50 mm polyurethane may lose 3–5 K in 24 hours; a loss above 8 K points to wet insulation or a damaged jacket. Outdoor pipes need trace heating and freeze protection, and the mechanical room should stay above 5 °C in freezing weather. A 5 m³ tank weighs about 5 t when full; the structural engineer must confirm the roof or floor load before the tank is ordered.

Common questions

What tank size does a 100-person dormitory need?

At 60 L/person/day the daily demand is 6 m³. The three-hour peak needs 6 m³, while the unit produces 1.6 m³ in the same period. The 4.4 m³ gap plus a cycling buffer gives about 5 m³. A 3 m³ tank will run short before the peak ends.

Why separate primary and secondary circuits?

The primary circuit can use softened water and a stable flow; the secondary circuit is drinking water with a fluctuating draw. Separating them protects the heat exchanger and stops tap demand from disturbing the compressor.

Should the return pump run continuously?

No. Start at 45 °C and stop at 52 °C. Continuous running wastes energy in summer and may still leave cold legs in winter if the pipe layout is poor.

How do I check stratification?

Measure the tank top and bottom temperatures. Normal is 8–12 K; below 5 K means short-circuiting. Check the hot inlet, the cold make-up and the return connection positions before adding tank volume.

What size expansion vessel is needed?

Calculate the expansion volume first. For 5.6 m³ of system water and a 40 K rise, about 45 liters expands; multiply by 1.5 for 68 liters and select 80 liters. Set the pre-charge to static pressure plus 0.1 MPa.

Can a 5 m³ tank go on the roof?

Only after a structural check. The full tank weighs about 5 t, before the frame and piping. Many projects discover the roof limit after the equipment is ordered and end up moving the tank to ground level.

How do I size the primary pump?

Use the heat-pump design flow and the pressure drop of the unit, tank, valves and piping. Add a margin for fouling. The pump must handle the tank’s static head and the minimum flow for the unit.

Can I use one pump for tank and loop?

Only if the flow and head match both duties and the control can separate them. A single pump often oversizes the tank loop and starves the heat pump. Separate primary and secondary pumps are easier to balance.