The choice between a circulating and a direct heat-pump hot-water plant is often presented as a preference. It is not. The two designs have different water flows, condensing temperatures, tank duties and control logic. A plant that is correct in one form will be wrong in the other, and the mistake usually appears as a tank that is too large, a unit that is too small, or hot water that falls below 40 °C at the morning peak.
The distinction can be reduced to one number: the temperature rise across the condenser. A circulating unit lifts the tank by 5–10 K per pass. A direct unit lifts fresh water from 5–15 °C to 55 °C in a single pass, a rise of about 40 K. Everything else — flow, pipe diameter, condensing pressure, tank volume and part-load behavior — is a consequence of that difference.
1. A closed loop that repeats, or a single pass that ends
In a circulating plant, water is drawn from the bottom of the storage tank, passed through the condenser, and returned to the top of the tank. The unit and the tank form a closed heating loop. The flow through the condenser is set by the circulation pump and is independent of what the building is drawing at that moment. The tank temperature rises slowly and uniformly; the unit stops when the tank reaches its setpoint.
In a direct plant, cold water enters the condenser once, is heated to the delivery temperature, and goes directly to the tank or to the fixture. There is no heating loop. The flow is the demand, and the outlet temperature is held by modulating the water flow: more flow gives a smaller rise, less flow gives a larger rise. That is why a direct plant needs a pressure-reducing valve, a flow meter and a modulating valve or variable-speed pump on the inlet side.
The direct design has a constraint the circulating design does not: minimum flow. A once-through condenser has a fixed heat-transfer area. Below about 30% of rated flow, the water stays in the condenser too long, the outlet temperature climbs by 5–8 K, and the high-temperature cut-out may trip. A minimum-flow switch, a bypass, or a variable-speed pump is not optional.
2. Flow follows the temperature rise, and so does pipe size
Take a 40 kW heat output. A direct unit with a 40 K rise needs m = 40 ÷ (4.187 × 40) = 0.239 kg/s, or 0.86 m³/h. A circulating unit with a 5 K rise needs 1.91 kg/s, or 6.9 m³/h. The ratio is eight, and the pipe sizes are roughly DN20 versus DN50.
The pipe size difference is visible in the mechanical room: valves, strainers, pumps and headers all move by two nominal sizes. The direct plant is cheaper on pipework but more expensive on control hardware. The circulating plant is simpler on control but needs a larger pump and a larger tank.
Condensing temperature follows the same logic. A circulating unit only needs to be 3–6 K above the tank, so 57–60 °C at a 55 °C tank. A direct unit must lift 15 °C water to 55 °C in one pass, so the condensing temperature is typically 62–65 °C. At a fixed evaporating temperature, that higher lift reduces COP by about 5–8%; the exact figure depends on the refrigerant and compressor.
| Item | Circulating | Direct |
|---|---|---|
| Water path | Closed loop between unit and tank | Once through the condenser |
| Rise per pass | 5–10 K | About 40 K |
| Flow at 40 kW | 6.9 m³/h at 5 K | 0.86 m³/h at 40 K |
| Typical pipe | DN50 | DN20 |
| Condensing temperature | 57–60 °C | 62–65 °C |
| COP effect | Reference | About 5–8% lower |
3. A storage tank and a buffer tank are not the same
The circulating tank is a thermal store. Its job is to hold heat produced during the low-tariff window and release it during the day. The volume is usually 50–100% of daily demand: the lower end for hotels and guesthouses where demand is spread across the day, the upper end for schools and bathhouses where demand is concentrated.
The direct tank is a buffer. Its job is to absorb the difference between instantaneous demand and unit output, stabilize pressure, and prevent the burner-like cycling of a fixed-speed unit. The volume is usually 30–50% of peak-hour demand. Below 30%, a single shower block can empty the tank and the outlet temperature swings; above 50%, the tank is large enough that the circulating design becomes more sensible.
An 80-room hotel at 75% occupancy, 120 L per room per day, uses 7.2 m³/d at 55 °C. Heating from 15 °C to 55 °C requires 7,200 × 4.187 × 40 ÷ 3,600 = 335 kW·h. A circulating plant with a 9 h heating window needs 37 kW, so a 40 kW unit is sufficient, with a 3.6–5.4 m³ tank. A direct plant sized for a 2.0 m³/h peak needs 2,000 × 4.187 × 40 ÷ 3,600 = 93 kW, so two 50 kW units, with a 0.6–1.0 m³ buffer.
| Item | Circulating | Direct |
|---|---|---|
| Daily demand | 7.2 m³/d | 7.2 m³/d |
| Daily heat | 335 kW·h | 335 kW·h |
| Unit size | 40 kW, 9 h window | 2 × 50 kW, 2.0 m³/h peak |
| Tank duty | Storage, 3.6–5.4 m³ | Buffer, 0.6–1.0 m³ |
| Mechanical room | 8–12 m² with tank | Compact, no large tank |
4. Capital cost and running cost move in opposite directions
The direct plant usually costs 15–25% more. The unit is larger, and the control set — pressure-reducing valve, flow meter, modulating valve, minimum-flow protection — is more extensive. The smaller tank offsets part of the difference, but not all of it.
Running cost is driven by two effects: the 5–8% lower COP, and the inability to shift heat into the low-tariff window. For the 80-room example, annual heat is 335 × 365 = 122,275 kW·h. A circulating plant at COP 3.4 uses about 35,963 kW·h. If 70% is bought at 0.35 CNY/kWh and 30% at 0.75 CNY/kWh, the annual bill is about 16,900 CNY. A direct plant at COP 3.2 uses 38,211 kW·h; at a flat 0.75 CNY/kWh, the bill is about 28,700 CNY. The difference is about 11,800 CNY/year.
That difference only exists if the tariff spread is real and the tank can actually be filled during the low-tariff window. Without a time-of-use tariff, the circulating advantage falls to 5–8% in energy, and the extra tank losses — roughly 5–10 kW·h/d for a well-insulated 4 m³ tank — plus the mechanical room area can erase most of it.
5. Five checks before choosing
Peak-hour share. Calculate daily demand and peak-hour demand. If the peak hour is more than 25% of daily demand, a direct plant with a buffer is easier to control at the fixtures. If it is below 15%, a circulating plant with storage is usually the better fit.
Tariff spread. A spread above 0.3 CNY/kWh, with a tank that can be charged in the low-tariff window, makes storage worthwhile. Without that spread, do not pay for a large tank.
mechanical room area. A 4.5 m³ tank with its plinth needs 8–12 m². Rooftop plants often cannot provide it; a direct plant may be the only practical option.
Water hardness. A direct plant has small passages and more valves. Above 300 mg/L hardness, add softening or specify a cleanable heat exchanger, otherwise the flow will fall as scale forms.
Operating capability. A direct plant needs periodic verification of its flow control and minimum-flow protection. For a remote, unmanned site, a circulating plant is more forgiving.
Mixing, stratification and the outlet temperature
A circulating plant depends on the tank staying stratified: cold water at the bottom, hot water at the top. A direct plant has no such store, but it has a different outlet problem when several taps open at once. The end user feels both as “the hot water went cold”.
| Arrangement | What it does well | Where it fails | Design check |
|---|---|---|---|
| Circulating unit with stratified tank | Stores heat for the peak; stable supply while the unit runs | High pump flow or bottom return destroys the layers | Inlet stabilizer; return to mid-tank; 5 K across the unit |
| Direct once-through unit | No mixing delay; hot water at the set point | Multi-outlet pressure imbalance | Static balancing valve on each branch; differential bypass on the main |
| Direct unit with buffer | Handles short peaks without cycling | Buffer too small for simultaneous showers | Size for the peak hour; above 25% of daily demand a buffer helps |
In a circulating system, a tank that reads 55 °C at the sensor can deliver water that falls to 40 °C within ten minutes. The sensor is measuring the top layer; the pump has mixed the tank. Reduce the circulation flow, move the return to the middle of the tank and fit a flow stabilizer at the inlet. These three changes can lift usable hot water from below 50% to 65–75%.
A direct unit avoids stratification loss but needs hydraulic balance. Without balancing valves, the nearest shower takes most of the flow and the farthest one goes cold. For a hospital or nursing home, the safety case also depends on the delivery temperature: a 55 °C tank plus a failed mixing valve can deliver above 60 °C, while a direct unit set to 50 °C removes one mixing step but must respect the storage-time limit for Legionella control. Longcom’s air-source heat pump page lists the circulating and direct configurations.
Common questions
Does a direct plant need a tank at all?
Yes, but as a buffer, not a store. Size it at 30–50% of peak-hour demand. For the 80-room example, that is 0.6–1.0 m³, compared with 3.6–5.4 m³ for a circulating plant.
Why is the direct flow only 0.86 m³/h at 40 kW?
Because the rise is 40 K rather than 5 K. The same heat output divided by a larger temperature rise gives a smaller mass flow. The pipe and pump follow the flow, not the heat output.
Is the direct plant always less efficient?
No. At the design point it is 5–8% lower because the condensing temperature is higher. In a plant with no storage and a high peak, the direct design can avoid a large tank and a long distribution loop, which may recover part of that penalty.
Which form is cheaper to run?
The circulating form, when there is a real tariff spread and the tank can be charged off-peak. In the 80-room example, the difference is about 11,800 CNY/year, which is larger than the usual capital premium.
Why does a direct unit overheat at low flow?
The condenser has fixed area and the heat input is fixed. At low flow, the water stays longer and leaves hotter. A minimum-flow switch, a bypass or a variable-speed pump is required; do not rely on the high-temperature cut-out as normal control.
Can a circulating tank be too large?
Yes. Above 100% of daily demand, standby losses and floor area keep rising while the peak-shaving benefit stops. Below 50%, the tank may be exhausted before the morning peak and the unit runs at the expensive time.
Which layout fits a small house?
A direct unit heats the water once through; a circulation unit heats a loop and stores it. A small house with low demand can use direct; a larger draw needs storage and circulation.
What return temperature?
Keep the return close to the setpoint to avoid a cold shock. A 5–10 °C drop is common. Too much drop reduces capacity and comfort.