1. A data sheet is not a leaderboard
A usable pool heat pump data sheet answers four questions: how much heat at which conditions, how much water it needs, how much space it occupies, and what it connects to electrically. If any one is missing, the sheet is a brochure.
Two failures recur. The first is incomplete data — capacity and COP given, flow, pressure drop, connection sizes and supply omitted, leaving the buyer unable to do hydraulic or electrical design. The second is unaligned data — capacity quoted at 24 °C air, input power quoted at another condition, and the COP simply divided out of the two. The result looks good and cannot be recalculated.
2. Capacity always carries its conditions
Heating capacity in kW is the core figure, but it is a curve, not a constant. The nominal value corresponds to a mild condition set; winter capacity is lower.
Ask for three things: nominal capacity; capacity at the project’s winter design temperature; and a capacity-versus-ambient curve with at least four points — 15 °C, 5 °C, 0 °C and −5 °C. A manufacturer who can only quote a nominal figure either has no cold-climate test data or will not release it.
3. Input power and current are the electrical design basis
Input power sets the supply capacity and the running cost. The sheet should give input power and running current at nominal conditions, plus maximum input power including fans, pumps and any electric backup.
Three points matter for design. Starting current on fixed-speed units can be several times rated current, so parallel units need staggered starting or soft starters. Voltage deviation at the far end of a 380 V three-phase system can be enough to affect compressor starting. And inverter units inject harmonics, which need filtering where sensitive control equipment shares the plant room.
4. Flow and pressure drop decide the pump and the pipework
Flow is the interface between the heat pump and the water system. The sheet must state rated flow in m³/h, the pressure drop at that flow in kPa, and the permitted flow range.
Below minimum flow, velocity in the exchanger is too low, the heat-transfer coefficient falls, the water temperature difference widens and the unit trips on high pressure. Above maximum flow, pressure drop, pump energy and long-term erosion all rise. Keep operation between 90% and 110% of rated flow.
5. Connections and physical size
Connections cover water in and out, condensate drain on dehumidification models, and electrical entry. The sheet should give sizes (DN25, DN32, DN40, DN50, DN65), positions and orientation.
Connection size is not a detail. A DN25 port on DN50 pipework gives low velocity and trapped air; a small port at high flow gives high local resistance and noise. On retrofits, check the match between the existing pipework and the new unit, and allow reducers and unions where needed.
6. Reference capacity ladder
The table below is a planning-stage reference for common pool heat pump capacity steps. Actual capacity, power, flow, connections and dimensions follow the selection sheet and the nameplate, and vary with conditions.
| Capacity (kW) | Input power (kW) | COP | Flow (m³/h at ΔT 4 K) | Connection | Supply |
|---|---|---|---|---|---|
| 10 | 2.2–2.6 | 3.9–4.6 | 2.2 | DN25 | 220 V single phase |
| 15 | 3.3–3.8 | 3.9–4.6 | 3.2 | DN25/DN32 | 220 V or 380 V |
| 20 | 4.3–5.0 | 3.9–4.6 | 4.3 | DN32 | 380 V three phase |
| 25 | 5.4–6.2 | 3.9–4.6 | 5.4 | DN32/DN40 | 380 V three phase |
| 30 | 6.4–7.5 | 3.9–4.6 | 6.4 | DN40 | 380 V three phase |
| 40 | 8.6–10.0 | 3.9–4.6 | 8.6 | DN40/DN50 | 380 V three phase |
| 50 | 10.8–12.5 | 3.9–4.6 | 10.8 | DN50 | 380 V three phase |
| 60 | 12.9–15.0 | 3.9–4.6 | 12.9 | DN50/DN65 | 380 V three phase |
Flow is estimated as Q/(cΔT) at ΔT = 4 K; the manufacturer’s rated flow and pressure-drop curve take precedence. COP is a mild-condition band and falls at low ambient.
7. Noise, dimensions and weight
Noise is quoted in dB(A), usually at 1 m in front of the unit. Read the test conditions as well as the number: background noise included or not, full load or part load, fan at maximum speed. For noise-sensitive projects ask for data at several fan speeds and write a night-mode limit into the technical agreement.
Dimensions and weight drive transport, lifting and foundation design. Roof installations must allow for operating weight including water and snow load; plant-room installations need slab capacity checked; lift transport needs cabin size and rated load. Modular units should quote the weight of a single module so they can be moved in sections.
8. The protection list is the column worth reading
Half the value of a pool heat pump is capacity and half is protection. The sheet should list: high pressure; low pressure; discharge temperature; over-current and overload; phase loss and phase sequence; water flow or differential pressure; frost protection at low water temperature; sensor diagnostics; communication diagnostics; power-failure memory and auto restart; compressor start delay; and abnormal-defrost protection. Check them off one by one at purchase.
9. Options: add what the project needs
RS-485/Modbus is worth adding where the unit must report to a BMS or energy platform, but only with a point list — register addresses, data types, read/write rights — otherwise it will not connect. Master control is worth adding on parallel installations: without it, units tend to run independently, and rotation, staging and load sharing never happen.
10. Three checks before you accept a data sheet
Check the footnotes: does every key number carry its condition? Check the curves: are capacity, pressure drop and noise given as curves rather than single points? Check the nameplate and the factory test sheet against the brochure — the nameplate is the only figure that binds.
Where a value is given as a range, the selection sheet should state the value the project will actually get, and a range should never be treated as a commitment.
11. An inquiry checklist you can send as-is
Nominal condition: five parameters — dry-bulb, wet-bulb, entering water, leaving water, flow. Capacity and COP at the local winter design temperature, with a derating curve. Rated flow, minimum flow, pressure drop at rated flow and the pressure-drop curve. Exchanger material and wall thickness. Connection sizes and positions; dimensions, operating weight and transport weight; noise at 1 m and at reduced speed. Protection list. Compressor and fan type, refrigerant, charge. Optional: Modbus point list, master-control functions, remote monitoring and the behavior on network loss. Ask for all of it in writing at quotation stage — it is much harder to obtain after the order.
Related reading
Sizing an air-source heat pump · Reading COP ratings · Heat pump noise levels · Pool heat pump efficiency parameters · Air-source heat pump range
Related pages in this series
Efficiency and COP · Performance classes · Sizing · Sizing FAQ