An air-source hot-water heat pump and an air-source floor-heating/air-conditioning combination unit are often compared as two grades of the same product. They are not. One produces domestic hot water only; the other uses the same compressor to provide heating, cooling and sometimes hot water. Comparing the purchase price alone produces a simple conclusion — the combined unit costs more but does more — and then a system that runs heating all winter while hot water still comes from an electric element.

The useful order is: answer three questions about the house, check whether the loads actually coincide, then compare the cost. Starting with the equipment price reverses the logic.

1. Three questions before the equipment

Does the house already have floor heating or fan-coil terminals? A combined unit usually produces 35–45 °C water for floor heating. Fan coils for cooling need 7–12 °C chilled water, which most dual-function units provide by switching and mixing. If the only terminals are radiators requiring 70 °C or more, a low-temperature combined unit will not work.

Are both heating and cooling required? If the house needs heating but not cooling, the cooling function is idle capital. If it needs cooling but not heating, paying for a heating function is equally wasteful. The answer is climate- and house-specific, not a product preference.

Will hot water and heating be used at the same time? This is the question most often skipped. In the coldest weeks, heating runs continuously while hot water draws cluster in the morning and evening. Under a heating-priority logic, the unit may switch briefly or reduce heating output, and the room temperature can drop 1–2 K.

If all three answers are yes, a combined unit is a reasonable candidate. If any answer is no, re-open the comparison.

2. The loads do not match

Heating is continuous and low-intensity; hot water is intermittent and high-intensity. A 120 m² house at 70 W/m² needs 8.4 kW of heating, running all day at part load. A household using 150 L/day from 15 °C to 55 °C needs about 7.0 kWh/day; if heated over two hours, the average power is 3.5 kW.

The combined peak is about 12 kW, but the heating unit is typically selected at 8–10 kW. In the coldest period, simultaneous hot water means either reduced heating output or a longer hot-water recovery. That is not a defect; it is the consequence of allocating capacity.

Load Character Peak What it sizes
Heating Continuous, low intensity 8.4 kW Heat-pump capacity
Hot water Intermittent, high intensity 3.5 kW over 2 h Tank volume and recovery
Combined Winter morning and evening About 12 kW for 1–2 h Control strategy

The answer is not to select a 12 kW unit. It is to make hot water storage-based: a 150–200 L tank heated slowly outside the heating peak. The heat pump stays sized on heating, the investment does not rise, and the comfort does not collapse.

3. Two temperatures, one hydraulic system

Floor heating needs 35–45 °C; domestic hot water needs at least 55 °C for Legionella control. The two circuits cannot share one direct water path.

Mixing center. The unit produces 55 °C; one branch is mixed down to 40 °C for floor heating, the other supplies hot water. It is simple and compact, but the heating season runs at a higher condensing temperature, cutting COP by about 8–12%.

Dual tanks. A buffer tank on the heating side and a potable tank on the hot-water side, switched by a three-way valve. The unit runs at 40 °C in heating mode and 55 °C in hot-water mode. It is the most efficient arrangement, but needs more space and higher first cost.

Plate heat exchanger. A plate exchanger separates the heating loop from the potable loop; the unit side runs at a higher temperature. It suits large houses and multiple bathrooms, at the highest cost.

Most houses use a mixing center because it is compact and cheap. A large heating area or a high-efficiency target favors dual tanks. There is no universal answer; local electricity price and heating-season length decide.

4. Four options on one cost table

Using the same 120 m² house, a 120-day heating season, 60 kWh/day of heat including part load and pipe loss, 150 L/day hot water, electricity at 0.55 CNY/kWh and gas at 2.8 CNY/m³:

Option First cost Heating/year Hot water/year Total/year
Heat-pump water heater + gas boiler CNY 32,000 2,240 500 2,740
Heat-pump water heater + electric heating CNY 24,000 3,960 500 4,460
Combined unit, mixing center CNY 46,000 1,440 520 1,960
Combined unit, dual tanks CNY 54,000 1,320 500 1,820

The heating calculation: 120 × 60 = 7,200 kWh/year. At a seasonal COP of 3.0, electricity is 2,400 kWh, or 1,320 CNY; add 10% for pumps and defrost, about 1,440 CNY. A gas boiler at 90% efficiency and 10 kWh/m³ burns 800 m³, or 2,240 CNY. Electric heating at 100% efficiency uses 7,200 kWh, or 3,960 CNY.

Two conclusions. Electric heating is the most expensive, 77% above gas and almost three times the heat pump. The combined unit costs CNY 14,000 more than “water heater + gas boiler” and saves about 780 CNY/year, a simple payback of about 18 years. On cash flow alone, it is not attractive.

Its value lies elsewhere: a house without a gas connection, a client who wants no combustion products indoors, or a house that also needs summer cooling. If none of those applies, a gas boiler plus a heat-pump water heater is the more pragmatic choice.

5. Three real weaknesses of a combined unit

Single point of failure. One machine provides heating, cooling and hot water. If it fails, all three stop. In a split system, a failed water heater still leaves the boiler for heating. Warranty does not restore that reliability.

Complex changeover logic. Heating, cooling and hot water have different priorities; defrost protection, tank temperature and room temperature are coupled. A poor controller produces “the room goes cold while someone showers” or “room temperature drops 3 K after defrost”.

Part-load efficiency. When only hot water is needed, a large combined unit is doing a small job, cycling or running at minimum speed. A dedicated water heater is more efficient in that mode. Condenser heat recovery during summer cooling helps, but the recoverable heat is limited by hot-water demand.

6. Decision checklist

Ask five questions in order:

Is there a gas connection? No gas points to a combined unit or an all-electric solution.

Is summer cooling needed and absent? If yes, a combined unit can replace a separate air-conditioning system.

Are the terminals floor heating or fan coils? Radiators at 70 °C rule out a low-temperature combined unit.

Is winter hot water demand large — four or more people, multiple bathrooms? If yes, choose dual tanks or a separate water heater.

Can the owner accept a single point of failure? If not, split the functions.

This sequence is more reliable than comparing feature counts. The real comparison is lifecycle cost, and that depends on local gas price, electricity price and heating-season length. The same equipment can rank differently in two provinces.

Common questions

Can a combined unit produce hot water and heating at full output simultaneously?

Most cannot. Under heating priority, a hot-water draw briefly switches the mode or reduces heating output, and room temperature may move 1–2 K. A storage tank heated outside the peak avoids the visible effect.

How does one unit serve 35 °C floor heating and 55 °C hot water?

Through the water circuit, not the compressor alone: a mixing center, dual tanks or a plate heat exchanger. The mixing center is cheapest but loses 8–12% seasonal COP; dual tanks are more efficient but take more space.

For a southern house that only needs cooling and hot water, what is the best choice?

A heat-pump water heater plus a normal air-conditioner, not a dual-function unit. The heating premium is not recovered, and condenser heat recovery is limited by hot-water demand.

If the combined unit fails, do heating and hot water both stop?

Yes. That is the inherent cost of combining functions. A household that cannot accept a cold house should keep a separate water heater and a boiler or electric backup.

Can an old house be converted to a combined unit?

Check three things: floor heating or fan-coil terminals, an electrical service of at least 8 kW, and a route for the hydraulic pipework. A radiator-only house cannot use a low-temperature combined unit; adding terminals often costs more than the equipment.

Is a combined unit cheaper than a water heater plus a boiler?

It depends on gas and electricity prices. At 0.55 CNY/kWh and 2.8 CNY/m³, the example is CNY 14,000 more and saves about 780 CNY/year, an 18-year payback. In a high-gas-price or no-gas area, the result reverses.

Can one unit do both?

A combined heat pump can heat and cool, but the loads are coupled. If one mode dominates, the unit may run inefficiently or cycle. Separate units are simpler and provide diversity; one unit saves space and piping.

What supply temperature should I use?

Use the lowest temperature that satisfies the floor loop, typically 35–45 °C. A lower temperature improves COP but may need more pipe or a larger emitter. Do not size the floor for 60 °C if the heat pump will run at 40 °C.