Ten Reasons a Heat Pump Stops Heating in Winter

In winter, “the heat pump is not heating” covers two very different situations. One is normal capacity loss: at 7 °C the unit may deliver 75–80% of its nominal heat, and at −7 °C only 55–60%. The water still heats, but slowly. The other is a real fault: flow, defrost, charge, valve or control. Treating the first as a fault leads to unnecessary parts; treating the second as “normal” leads to a cold building.

The ten causes below are ordered by field diagnosis, not by probability. Check temperature and flow first, pressure and current second, refrigerant last.

1. Ambient derating

An air-source heat pump takes heat from the air. As the outdoor temperature falls, the evaporating temperature falls, the compression ratio rises and the available heat drops. A unit rated at 20 °C may deliver 0.75–0.80 of nominal at 7 °C and 0.55–0.60 at −7 °C. If the unit was selected on a 20 °C catalog, winter “low output” is a selection issue, not a failure.

2. Setpoint too high

The condensing temperature follows the hot-water setpoint. Raising the setpoint from 45 °C to 55 °C can cut heat output by about 15% and COP by 20–25%. A unit held at 60 °C all winter runs near its limit, and any frost or flow shortfall becomes a “no heat” complaint. A two-level schedule, higher during the cheap tariff window and lower afterward, is often a better compromise.

3. Wrong low-temperature model

A standard hot-water heat pump may have an operating limit of −5 to −7 °C; a “low-temperature” model may be rated to −15 °C or −25 °C. In a cold climate, a standard model without electric backup will trip on low pressure or discharge temperature. Check the model’s operating envelope, not the compressor brand.

Outdoor temperature Standard model Low-temperature model Field symptom
20 °C 1.00 1.00 Catalog value
7 °C 0.75–0.80 0.82–0.88 Longer heat-up time
0 °C 0.60–0.68 0.72–0.78 Defrost becomes important
−7 °C 0.55–0.60 0.62–0.70 Standard model may trip

4. Water flow too low

Low flow is the most common real winter fault. A blocked Y-strainer, a reversed or worn pump, a partly closed valve or an air pocket reduces the flow. The water-side temperature difference rises and the unit may trip on low pressure. For a 20 kW unit at a design ΔT of 4 K, a measured ΔT above 7 K suggests the flow is roughly 60% of design. Clean the strainer, check the pump rotation and open the valves before touching the refrigerant.

5. Heat-exchanger scale

Hard water scales the plate heat exchanger. The same flow then gives a smaller water-side ΔT, a higher discharge temperature and a higher condensing pressure. If the high pressure is 0.1–0.15 MPa above the previous season at the same ambient and setpoint, and cleaning the strainer does not help, inspect or chemically clean the exchanger. Acid cleaning must be controlled by a competent technician.

6. A bypass left open

A bypass valve opened for summer commissioning and not closed for winter short-circuits the supply and return. The unit’s hot outlet is diluted by the return, and the tank sits at 40 °C. Touch the bypass pipe: if both ends are at nearly the same temperature, the valve is open. Close it and the system recovers without touching the heat pump.

7. Tank and pipe insulation

A damaged or thin tank insulation can lose 5–8% of the stored heat per hour in cold weather. A continuously running return pump can lose heat in unoccupied pipe runs. Measure the tank temperature drop over a six-hour standby period; more than 5 K points to insulation or return control.

8. Low refrigerant charge

A leak lowers the suction pressure, raises the superheat and raises the discharge temperature. A low-side pressure more than 15% below the same-condition catalog value, a superheat above 8 K and bubbles in the sight glass point to undercharge. Leak-test and repair before charging; do not “top up” a leaking circuit.

9. Reversing valve leakage

In heating mode, a reversing valve that leaks between high and low sides reduces the pressure difference, lowers the discharge temperature rise and raises the low-side pressure. The compressor current may be low because the load is bypassing the condenser. A discharge temperature rise below 15 K with abnormal pressures points to the valve, not the charge.

10. Electric backup or control signal

Low-temperature models often use electric backup. A failed contactor, a low thermostat setting or a blown fuse removes that capacity. On the control side, a drifting water sensor that reads 55 °C while the tank is at 49 °C stops the unit early; a supply voltage of 340 V on a 380 V system raises the current 10–15% and can trip the overload. Check the sensor against a calibrated thermometer and the supply against the nameplate.

Diagnostic order

First, compare the outdoor temperature and the setpoint with the model’s capacity table. Second, measure the water-side ΔT, flow and strainer. Third, check defrost and the outdoor coil. Fourth, read the pressures, superheat and discharge temperature. Fifth, check the reversing valve and the control signals. Refrigerant charging comes after a leak test, not before.

Common questions

Is 78% capacity at 7 °C normal?

For many standard models, yes. The exact figure is in the model’s capacity table. It is normal derating, not a fault.

Can I fix low winter output by adding gas?

No, unless the charge is actually low. Adding gas to a correctly charged unit raises the pressure and can cause high-pressure trips.

Why does the unit keep defrosting?

Defrost is normal in cold, humid weather. If it defrosts with no frost, or more often than the manual allows, check the coil sensor, the reversing valve and the defrost termination setting.

How do I know the flow is low?

Measure the water-side ΔT and compare it with the design. A ΔT well above design at the same load means low flow. Check the strainer, pump and valves.

Should the electric backup run all winter?

No. It is a capacity supplement for the coldest hours. Continuous reliance suggests the unit is undersized or the setpoint is too high.

What is the first measurement?

The outdoor temperature, the setpoint and the water-side ΔT. These three separate normal derating from a flow or control fault before any pressure gauge is connected.

Is no heat normal?

At low ambient, capacity falls. A unit sized at 7 °C may not meet a -5 °C day. Separate derating from a fault.

What order to check?

Ambient and setpoint, flow, defrost, charge, then controls. Fix the cheapest cause first. Do not add refrigerant before the sensor check.

Further technical reading

LONGCOM can check the model’s winter capacity table against the site’s design temperature, and separate derating from a flow, defrost or charge fault. For a winter performance review, contact 400-878-0280 or 13002001280.

Related reading

Compressor will not start · Heat-pump maintenance · Four failure modes